Exam Cheat Sheet · Quick Reference
ICC F11 General Building Contractor (A) Exam (2015 IBC)
National · Pearson Vue
National State Portion 90 questions
Key Distinctions
A 'mark' is an identification applied by the manufacturer giving the manufacturer's name and the function of the product, while a 'label' additionally carries performance characteristics and the identification of an approved agency (a 'manufacturer's designation' instead indicates compliance with a specified standard or set of rules).
IBC 2015 Chapter 2 — Definitions of 'Mark,' 'Label' and 'Manufacturer's Designation'The 0.3-inch-per-occupant factor is the general stairway capacity rule, and the reduced 0.2-inch factor applies only to buildings (other than Groups H and I-2) equipped throughout with an automatic sprinkler system AND an emergency voice/alarm communication system.
IBC 2015 Chapter 10 — Section 1005.3.1 StairwaysBooths are computed at one person per 24 inches of booth seat length measured at the backrest, while fixed seating without dividing arms is computed at not less than one person per 18 inches of seating length.
IBC 2015 Chapter 10 — Section 1004.4 Fixed SeatingJoists or structural floors closer than 18 inches to exposed ground must be naturally durable or preservative-treated, while for girders the threshold is closer than 12 inches to exposed ground.
IBC 2015 Section 2304.12.1.1 (Chapter 23)Prescriptive rafter tables use a deflection limit of L/240 when the ceiling is attached to the rafters and L/180 when it is not, while prescriptive floor joist span tables (both 30 psf sleeping and 40 psf living live loads) use L/360; uninhabitable attic ceiling joist tables use L/240.
IBC 2015 Chapter 23 — Section 2308.7.2 and Tables 2308.7.2(1) through 2308.7.2(6)An incinerator room requires both a 2-hour separation AND an automatic sprinkler system, whereas furnace rooms and refrigerant machinery rooms require 1 hour OR sprinklers.
IBC 2015 Chapter 5 — Table 509 Incidental UsesDead ends are limited to 20 feet where more than one exit or exit access doorway is required, but Exception 2 permits up to 50 feet in Groups B, E, F, I-1, M, R-1, R-2, R-4, S and U where the building is sprinklered throughout per Section 903.3.1.1.
IBC 2015 Chapter 10 — Section 1020.4 Corridors, Dead EndsHandrail height above stair tread nosings must be uniform at not less than 34 inches and not more than 38 inches, while the 30-to-34-inch range applies only to alternating tread devices and ships ladders.
IBC 2015 Chapter 10 — Section 1014.2 Handrails, HeightGuards are required where the vertical drop exceeds 30 inches at any point within 36 inches horizontally of the open side, while 42 inches is the required height of the guard itself under Section 1015.3.
IBC 2015 Chapter 10 — Section 1015.2 Guards, Where RequiredWhere a general requirement conflicts with a specific requirement addressing the same condition, the specific requirement governs; the separate 'most restrictive governs' rule applies where different sections specify different materials, methods of construction or other requirements for the same case.
IBC 2015 Chapter 1 — Section 102.1 GeneralFor concrete exposed to sulfate soils or solutions, Type V sulfate-resistant cement is used in severe exposures and Type II in moderate exposures (Type III is high-early-strength, not sulfate-resisting).
Concrete Manual (2015 IBC / ACI 318-14), Chapter 4 — Section 4.2 (Deficiencies of the Concrete Itself)A stairway serving as part of an accessible means of egress must have not less than 48 inches clear between handrails (Exception 2 waives this in buildings sprinklered throughout), while 44 inches is only the general minimum stairway width of Section 1011.2.
IBC 2015 Chapter 10 — Section 1009.3 Accessible Means of Egress, StairwaysBefore use, fire-retardant-treated wood must be dried to 19% or less moisture content when it is lumber and 15% or less when it is wood structural panels.
IBC 2015 Section 2303.2Combustible framing must be not less than 2 inches from flues, chimneys and fireplaces, but must be 6 inches away from flue openings specifically.
IBC 2015 Section 2304.5 (Chapter 23)Key Terms
Formulas to Know
Required stairway width = occupant load × 0.3 inch per occupant; worked example: 300 occupants × 0.3 = 90 inches (the 44-inch general minimum stairway width does not override the larger required capacity)W/C (by weight) × 94 lb cement per bag ÷ 8.33 lb/gal = gallons per bag; worked example: 0.44 × 94 = 41.4 lb ÷ 8.33 ≈ 5.0 gal/bag(actual number of dwelling units ÷ 4) + (ratio for the other occupancy) shall not exceed 1One 30-inch by 48-inch wheelchair space for each 200 occupants or portion thereof of the occupant load servedBooths: 1 person per 24 inches of booth seat length measured at the backrest; fixed seating without dividing arms: not less than 1 person per 18 inches of seating lengthDesign wind force shall be not less than 16 psf × area of the structure projected on a plane normal to the assumed wind direction; components and cladding net pressure not less than 16 psf in either direction normal to the surfaceCombustible exterior wall coverings shall not exceed 10 percent of the exterior wall surface area where the fire separation distance is 5 feet or less (example: a 4-foot fire separation distance triggers the 10 percent limit)For clay, sandy clay, silty clay, clayey silt, silt and sandy silt, resistance = cohesion × contact area, but in no case shall it exceed one-half the dead loadTaking a standard 6-by-12-inch cylinder (L/D = 2.0) as 100 percent, a 6-inch-diameter specimen 9 inches long indicates about 104 percent of that strength; correction factors for L/D less than 2.0 are applied for direct comparison (ASTM C39, C42)f2 = 0.7 for roof configurations (such as saw tooth) that do not shed snow off the structure; f2 = 0.2 for other roof configurations (f1 = 0.5 for ordinary live loads and 1 for public assembly live loads over 100 psf and parking garages)