Exam Cheat Sheet · Quick Reference
ICC F16 Master Electrician Exam (2014 NEC)
National · Pearson Vue
National State Portion 100 questions
Key Distinctions
Article 100 defines a device as a unit of an electrical system, other than a conductor, that carries or controls electric energy as its principal function (e.g., a snap switch), while utilization equipment such as luminaires and motors uses electric energy rather than merely carrying or controlling it.
NEC 2014 Article 100 — Definitions of Device and Utilization EquipmentLabeled means a label, symbol, or mark of an AHJ-acceptable organization that maintains periodic production inspection is attached and by which the manufacturer indicates compliance, whereas Listed means inclusion in a published list of such an organization (Approved = acceptable to the AHJ; Identified = recognizable as suitable for a specific purpose).
NEC 2014 Article 100 — Definitions of Labeled, Listed, Approved, and IdentifiedA service lateral is the underground conductors between the utility electric supply system and the service point, a service drop is the overhead equivalent of a lateral, and underground service conductors run between the service point and the first point of connection to the service-entrance conductors.
NEC 2014 Article 100 — Definitions of Service Lateral, Service Conductors, Underground, and Service DropA feeder is all circuit conductors between the service equipment, the source of a separately derived system, or other power supply source and the final branch-circuit overcurrent device; a branch circuit begins at that final overcurrent device, and service/service-entrance conductors exist only on the supply side of the service disconnect.
NEC 2014 Article 100 — Definitions of Feeder, Branch Circuit, and Service ConductorsA guest suite is two or more contiguous rooms forming a compartment providing living, sleeping, sanitary, and storage facilities; a guest room is a single compartment with those facilities; a dwelling unit additionally requires permanent provisions for cooking.
NEC 2014 Article 100 — Definitions of Guest Suite, Guest Room, and Dwelling UnitShort-circuit current rating is the prospective symmetrical fault current at nominal voltage to which an apparatus or system can be connected without sustaining damage exceeding defined acceptance criteria, while interrupting rating is the highest current at rated voltage a device is identified to interrupt under standard test conditions.
NEC 2014 Article 100 — Definitions of Short-Circuit Current Rating and Interrupting RatingA panelboard includes buses and automatic overcurrent devices designed to be placed in a cabinet or cutout box in or against a wall and accessible only from the front; a switchboard is generally accessible from the rear as well as the front and is not intended for cabinets, switchgear is a completely metal-enclosed assembly, and a motor control center is an assembly of sections with a common power bus containing motor control units.
NEC 2014 Article 100 — Definitions of Panelboard, Switchboard, Switchgear, and Motor Control CenterOverload is operation of equipment above its normal full-load rating or of a conductor above its rated ampacity that, if it persists, would cause damage or dangerous overheating; the Article 100 definition expressly states a fault such as a short circuit or ground fault is not an overload.
NEC 2014 Article 100 — Definition of OverloadWet locations include installations underground or in concrete slabs or masonry in direct contact with earth, locations subject to saturation such as vehicle washing areas, and unprotected locations exposed to weather; roofed open porches and moist basements are damp locations, and a location only temporarily wet during construction remains a dry location.
NEC 2014 Article 100 — Definitions of Location, Wet; Location, Damp; Location, DryType 1 is permanently connected on the line side of the service disconnect overcurrent device (between the service transformer secondary and that device); Type 2 is permanently connected on the load side including at the branch panel, Type 3 is point-of-utilization, and Type 4 is a component SPD.
NEC 2014 Article 100 — Definition of Surge-Protective Device (SPD)Schedule 80 PVC is identified for use in areas of physical damage (352.10(F) Informational Note); Schedule 40 is not identified for physical damage, Type EB is a concrete-encased burial product, and Type XW is the RTRC product identified for physical damage under 355.10(F).
NEC 2014 Section 352.10(F)Under 430.32(C), when a motor will not start with the sized overload device, a higher sensing element may be used but trip current shall not exceed 140 percent of nameplate full-load current for motors marked with a service factor of 1.15 or greater (or a marked temperature rise of 40°C or less) and 130 percent for all other motors.
NEC 2014 Section 430.32(C)Key Terms
Formulas to Know
P = E × I (e.g., 120 V × 12.5 A = 1,500 W); I = P / E (e.g., 1,800 W / 120 V = 15 A); kW = W ÷ 1,000 (2,400 W = 2.4 kW)VD = (2 × K × I × L) / CM; L = (VD × CM) / (2 × K × I); CM = (2 × K × I × L) / VD; I = (VD × CM) / (2 × K × L). K = 12.9 copper, K = 21.2 aluminum (aluminum has roughly 1.6 times the resistance of copper). Allowable drop at 3 percent = source voltage × 0.03.VD = (1.732 × K × I × L) / CM — use 1.732 (√3) instead of the single-phase factor 2; example: (1.732 × 12.9 × 24 A × 90 ft) / 10,380 cmil = 4.65 V% VD = voltage drop ÷ source voltage (example: 8.4 V / 240 V = 3.5 percent, which exceeds the 3 percent recommended for a branch circuit alone)125% of the largest motor FLC + sum of the other motors' FLC; example with three 5 HP, 230 V, 3-phase motors at 15.2 A each: (1.25 × 15.2) + 15.2 + 15.2 = 49.4 ATable 430.52(C)(1): inverse time breaker up to 250% of motor FLC (example: 50 A × 2.5 = 125 A). Per 430.52(C)(1) Exception No. 2, where the motor fails to start, the rating may be increased but shall in no case exceed 400% of FLC for motors of 100 A or less (300% above 100 A): 50 A × 4 = 200 A; 60 A × 4 = 240 A. The 400% value is a cap, not simply the next standard size.Conductors not less than 125% of RLA (440.32): 1.25 × 20 A = 25 A; OCPD rated not more than 175% of RLA (440.22(A)): 1.75 × 20 A = 35 AGeneral lighting = floor area × 3 VA/sq ft; add 1,500 VA for each small-appliance circuit and 1,500 VA for each laundry circuit (example: 2,000 sq ft × 3 = 6,000 VA + 2 × 1,500 + 1,500 = 10,500 VA, before demand factors)Distance between the two bend marks = multiplier × offset depth (30° multiplier 2.0: 2.0 × 4 in = 8 in; 45° multiplier 1.4: 1.4 × 4 in = 5-5/8 in). Shrink varies with the bend angle per the chart — for a 30° offset it is 1/4 in per inch of offset depth (1/4 × 4 in = 1 in). Locate the first mark by adding that offset's shrink to the measured distance, moving the marks toward the far end: 30 + 1 = 31 in (30° offset, marks 8 in apart); 42 + 1-7/8 = 43-7/8 in (marks 26 in apart); 48 + 1-1/2 = 49-1/2 in (45° offset, marks 5-5/8 in apart).3-point saddle: side marks = 2.5 × obstruction height each side of the center mark (2.5 × 3 = 7-1/2 in; 2.5 × 5 = 12-1/2 in; 2.5 × 6 = 15 in), center bent 45° and sides 22-1/2°, shrink = 3/16 × obstruction height. Stub-up: mark = stub height − take-up (18 − 5 = 13 in for 1/2 in EMT; 16 − 11 = 5 in for 1-1/4 in EMT).