Exam Cheat Sheet · Quick Reference
ICC G18 Residential Electrician Exam (2017 NEC)
National · Pearson Vue
National State Portion 60 questions
Key Distinctions
The main bonding jumper connects the grounded circuit conductor to the equipment grounding conductor at the service, while a system bonding jumper serves the same function at a separately derived system rather than at the service.
NEC 2017 Article 100 (Definition: Bonding Jumper, Main)A continuous load is one whose maximum current is expected to continue for 3 hours or more and is taken at 125% for sizing conductors/overcurrent devices, while noncontinuous load is added at 100%.
NEC 2017 Article 100 — Continuous Load definitionIn a series circuit the total current equals the current in any other part of the circuit and resistances add, while resistors in parallel combine as (R1×R2)/(R1+R2) (two equal resistors give R/2).
Ugly's Electrical References, 2023 ed., Series Circuits, Page 3 (2020 ed.: Series Circuits)Single-phase uses the factor 2 (round-trip distance) in Vd = (2K × L × I) ÷ Cm, while three-phase circuits use 1.73 in place of the 2.
Ugly's Electrical References 2020, Voltage Drop CalculationsThe grounded neutral is white or gray (an insulated grounded conductor 6 AWG or smaller uses a continuous white or gray outer finish or three white/gray stripes on other than green insulation), while the two ungrounded line conductors are black (line one) and red (line two).
Ugly's Electrical References, 2023 ed., Common Electrical Distribution Systems, Page 13 (2020 ed.: Common Electrical Distribution Systems)The single-phase three-wire system uses black and red ungrounded conductors with a white/gray neutral, whereas the delta high-leg system has a B phase (high leg) that must be colored orange or tagged, with caution noted for 208 volts orange to white.
Ugly's Electrical References, 2023 ed., Common Electrical Distribution Systems, Page 13 (2020 ed.: Common Electrical Distribution Systems)Class 1 circuits are not permitted to exceed 600 volts, while Article 411 low-voltage lighting systems operate at no more than 30 volts ac or 60 volts dc and their secondary circuits shall not be grounded.
NEC 2017 Section 725.41(B)Article 760 classifies every fire alarm circuit as either non–power-limited or power-limited, and that classification determines which installation requirements apply.
NEC 2017 Section 760.2 (Fire Alarm Circuit)Per 225.6(A)(1), open individual conductors must be not smaller than 10 AWG copper for spans up to 50 ft, but not smaller than 8 AWG copper for longer spans unless supported by a messenger wire.
NEC 2017 Section 225.6(A)A tap conductor is defined by 240.2 as a conductor OTHER than a service conductor that has overcurrent protection ahead of its point of supply exceeding the value permitted for similar conductors protected per 240.4.
NEC 2017 Section 240.2At 40°C (104°F) ambient the correction factor is 0.88 for 75°C-rated conductors, but 0.91 for 90°C-rated conductors in the 36–40°C range.
NEC 2017 Table 310.15(B)(2)(a)Derating factors may be applied to the higher 90°C ampacity (e.g., 1/0 AWG THHN copper at 170 A × 0.91 = 154.7 A), but the final ampacity used cannot exceed the 75°C terminal rating of that conductor (150 A for 1/0).
NEC 2017 Table 310.15(B)(2)(a) and Section 110.14(C)Currents that introduce noise or data errors in electronic equipment shall NOT be considered the objectionable currents addressed in 250.6, so they do not justify the alterations permitted by 250.6(B).
NEC 2017 Section 250.6(D)Key Terms
Formulas to Know
I = W ÷ E (1500 W ÷ 120 V = 12.5 A); R = E ÷ I (240 V ÷ 8 A = 30 Ω); E = I × R (10 A × 12 Ω = 120 V); P = E × I (120 V × 5 A = 600 W; 120 V × 12.5 A = 1500 W); P = E² ÷ R (240² ÷ 20 = 2880 W); R = E² ÷ P (14,400 ÷ 1200 = 12 Ω)Vd = (2K × L × I) ÷ Cm, where K = 12.9 for copper at 75°C, L = one-way length in feet, I = amperes, Cm = circular mils; three-phase uses 1.73 in place of 2. Example: (2 × 12.9 × 150 × 30) ÷ 16,510 ≈ 7 volts for #8 THWN copper.%VD = Voltage Drop ÷ Source Voltage × 100; example: 7 V ÷ 240 V = 2.9%. NEC recommends total feeder plus branch-circuit drop not exceed 5%, with 3% recommended on each individually. Since VD is proportional to length, a 20% longer run raises a 3% design to 3.6%, and one standard AWG size up (~26% more circular mils, ~20% less VD) restores it to within 3%.Minimum rating = noncontinuous load + (125% × continuous load). Examples: 40 A + (1.25 × 80 A) = 140 A OCPD (215.3); (100 A × 125%) + 30 A = 155 A minimum feeder conductor ampacity (NEC 2026 215.4(A)(1); NEC 2023 215.2(A)(1)).Total VA = (area in sq ft × 3 VA/sq ft) + (1500 VA × number of small appliance circuits) + (1500 VA × number of laundry circuits). Examples: 2000 sq ft + 2 SA + 1 laundry = 6000 + 3000 + 1500 = 10,500 VA; 1800 sq ft + 3 SA + 2 laundry = 5400 + 4500 + 3000 = 12,900 VA; 2500 sq ft + 3 SA + 1 laundry = 7500 + 4500 + 1500 = 13,500 VA; per unit 1200 sq ft + 2 SA + 1 laundry = 8100 VA, × 4 units = 32,400 VA before demand factors.Corrected ampacity = base (table) ampacity × correction factor, applied where ambient differs from the 30°C (86°F) baseline. Example: 1/0 AWG THHN copper 170 A (90°C) × 0.91 (36–40°C ambient) = 154.7 A, but the result may not exceed the 75°C terminal rating (150 A for 1/0).Total ampacity = per-set ampacity × number of sets; example: 350 kcmil THHN copper at 350 A (90°C column, Table 310.16) × 2 sets = 700 A.Series: Rt = R1 + R2 + ...; two equal resistors in parallel: R ÷ 2; two unequal in parallel: (R1 × R2) ÷ (R1 + R2). Examples: 7 Ω + (30 Ω ÷ 2) = 22 Ω, with I = E ÷ R = 44 V ÷ 22 Ω = 2 A; (8×8)/(8+8) = 4 Ω plus (20×20)/(20+20) = 10 Ω in series = 14 Ω.Heating load = 100% of heat pump compressor nameplate + 65% of supplemental electric heating where the compressor is not prevented from operating at the same time; example: 5000 VA + (15,000 VA × 0.65) = 14,750 VA.For a 3-wire, single-phase dwelling unit service, service conductors are permitted an ampacity of 83% of the service rating; example: a 200-ampere service permits 2/0 AWG THW copper instead of 3/0 AWG.