Exam Cheat Sheet · Quick Reference
Idaho - ID JOURNEYMAN ELECTRICIAN EXAM
Idaho · PSI Services Contractor
Idaho State Portion 100 questions
Key Distinctions
Mandatory rules use 'shall' or 'shall not' (required or prohibited actions), while permissive rules use 'shall be permitted' or 'shall not be required'.
Article 90.5(A)In a series circuit, current is equal in all parts (IT = I1 = I2 = I3), while total resistance is the sum of all individual resistances (RT = R1 + R2 + R3).
Series CircuitsChapters 1–7 apply generally to all covered installations, while Chapter 8 is independent and not subject to Chapters 1–7 except where specifically referenced therein.
NEC 90.3Direct burial cables require a minimum cover of 600 mm (24 in.) in general locations, while rigid metal conduit or IMC requires only 150 mm (6 in.).
NEC Table 300.5(A)Bored holes must keep the edge at least 32 mm (1-1/4 in.) from the wood edge or a steel plate is required, while cables in notches must always be covered by a steel plate at least 1.6 mm (1/16 in.) thick.
NEC 300.4(A)(1)The grounded neutral conductor is white or gray, while the two ungrounded conductors are black (L1) and red (L2).
Ugly's Electrical References, Common Electrical Distribution SystemsIn a 120/208 V three-phase four-wire wye system the C phase is blue, while in a 120/240 V delta high-leg system the B phase (high leg) is orange.
Ugly's Electrical References, Common Electrical Distribution SystemsThe NEC's purpose is the practical safeguarding of persons and property from electrical hazards; it is explicitly NOT intended as a design specification or instruction manual for untrained persons.
Article 90.2(A)Per NEC 404.7, the up position of a vertically operated switch handle is the closed (on) position, implying the down position is the open (off) position.
NEC 404.7Elevator installations allow a maximum of 50% raceway fill per Article 620.33, which differs from the standard fill percentages in Chapter 9, Table 1 used for general wiring.
Article 620.33Ohm's Law calculates current from voltage and resistance (I = E ÷ R), while Watt's Law calculates current from power and voltage (I = P ÷ E); both appear on the Ohm's Law wheel but are technically distinct formulas.
Ugly's Electrical References, Ohm's LawFeeder conductors must be sized at 125% of continuous loads per NEC 215.2(A)(1), while conductors in a raceway containing 7–9 current-carrying conductors must have their ampacity derated to 70% per NEC Table 310.15(C)(1).
NEC 215.2(A)(1)Key Terms
Formulas to Know
I = E ÷ RE = I × RR = E ÷ IP = E × II = P ÷ ERT = R1 + R2 + R3 + ...IT = I1 = I2 = I3Minimum Ampacity = Noncontinuous Load + (1.25 × Continuous Load)Derated Ampacity = Table Ampacity × Adjustment Factor (e.g., 0.70 for 7–9 conductors)