Kansas City, MO Low-Voltage Electrician Exam (ICC G21, 2017 NEC)

Missouri  ·  Pearson Vue

Verified, not estimated. Every figure below is drawn from the official exam structure we maintain — question counts, passing standard and topic weighting. Practice questions are grounded in the source law with statute citations. We omit any figure we can't verify rather than guess at it.
Total questions
50
Passing score
70%
Exam time
180 min
Administered by
Pearson Vue
Format
Reference materials allowed

Missouri State Portion 50 questions

General Knowledge 12 Q · 24%
Ohm's Law and power formulas (P, E, I, R relationships)Series, parallel, and combination circuit calculationsAC circuit concepts: impedance, reactance, inductance, and capacitanceElectrical formulas for amperes, kilowatts, kVA, and horsepower (single-phase and three-phase)Grounding and bonding principles and terminology (NEC Article 250)NEC code structure, scope, definitions, and general installation requirementsPower factor, power factor correction, and efficiency calculationsElectrical symbols, field terms vs. NEC terms, and units of measurement/conversion
LV Remote Control & Alarm Systems 11 Q · 22%
Class 1 vs. Class 2 vs. Class 3 circuit classifications and definitionsPower source requirements for Class 2 and Class 3 circuitsClass 1 circuit overcurrent protection and conductor sizingSeparation of Class 2/Class 3 circuits from power and Class 1 conductorsCable types and substitution hierarchy for Class 2, Class 3, and PLTC cablesFire alarm circuit classifications: NPLFA vs. PLFAPower source and branch circuit requirements for fire alarm systemsFire alarm cable types, listing requirements, and installation by building location
LV Communications & Sound 18 Q · 36%
Communications cable types and listing requirements (CMP, CMR, CMG, CM, CMX, CMUC)Cable installation locations — plenums, risers, and general-purpose spaces (Article 800)Grounding and bonding of communications cables and primary protectors (Article 800)Primary and secondary protectors — application, location, and typesCATV coaxial cable types, installation, and grounding of outer conductive shield (Article 820)Network-powered broadband communications systems — power classifications, cable types, and installation (Article 830)Audio signal processing and reproduction equipment — wiring methods, grounding, and loudspeaker installation (Article 640)Radio and television antenna systems — materials, clearances, discharge units, and bonding conductors (Article 810)
LV Control Circuits 7 Q · 14%
Motor control circuit overcurrent protection and conductor sizing (NEC 430.72)Electrical arrangement and grounding of control circuits (NEC 430.74)Disconnection of motor control circuits from all power sources (NEC 430.75)Class 1 vs. Class 2 vs. Class 3 remote-control circuit classifications and power source requirementsThree-wire stop-start station wiring and seal-in contact operationMultiple stop-start stations and hand-off-automatic (HOA) control circuit configurationsJogging circuits and control relay wiring for inching operationsControl circuit transformer protection and reduced-voltage control wiring methods
Fiber Optical 2 Q · 4%
Optical fiber cable types and listing requirements (OFNP, OFCP, OFNR, OFCR, OFNG, OFCG, OFN, OFC)Installation locations within buildings (plenums, risers, general spaces, cable trays)Grounding and bonding of metallic members of optical fiber cablesSeparation requirements when installed with electrical conductorsOverhead and underground optical fiber cables entering buildingsCable substitution hierarchy for optical fiber cable typesAbandoned optical fiber cable requirements and fire spread preventionUnlisted optical fiber cables entering buildings (50 ft rule, raceway requirements)

Key Distinctions

Main bonding jumpervsSystem bonding jumper

Per NEC Article 100, the main bonding jumper is the connection between the grounded circuit conductor and the equipment grounding conductor at the service, while the system bonding jumper makes that connection (to the supply-side bonding jumper, the equipment grounding conductor, or both) at a separately derived system.

NEC 2017 Article 100 (Definition: Bonding Jumper, Main)
Class 1 power-limited circuitvsClass 1 remote-control and signaling circuit

Per NEC 725.41, Class 1 circuits are classified as either Class 1 power-limited circuits meeting the power limitations of 725.41(A) or Class 1 remote-control and signaling circuits used for remote-control or signaling and meeting 725.41(B).

NEC 2017 Section 725.41
Power-limited fire alarm (PLFA) circuitvsNon-power-limited fire alarm (NPLFA) circuit

Per the NEC 760.2 definition, fire alarm circuits are classified as either non–power-limited or power-limited, and the classification determines the applicable installation requirements (e.g., NPLFA raceway fill follows 300.17 per 760.3(J), while PLFA cable per 760.179(I) shall not be marked with a voltage rating except where multiple listings require it).

NEC 2017 Section 760.2 (Fire Alarm Circuit)
820.100(D) bonding jumper between separate electrodesvs820.100(A)(3) shield bonding conductor/grounding electrode conductor

Where a CATV system uses its own separate electrode, 820.100(D) requires a bonding jumper not smaller than 6 AWG copper (or equivalent) between that electrode and the power grounding electrode system, whereas 14 AWG is the minimum size for the shield bonding/grounding electrode conductor itself under 820.100(A)(3).

NEC 2017 Section 820.100(D)
Bonding metal water piping (250.104(A))vsBonding other metal piping such as gas (250.104(B))

Per NEC 250.104(B), other metal piping systems, including gas piping, that are likely to become energized must be bonded to the equipment grounding conductor of the circuit likely to energize the piping, which differs from the metal water piping bonding required by 250.104(A).

NEC 2017 Section 250.104(B)
Coaxial drop clearance at the polevsCoaxial/communications drop clearance at other points in the span

Per NEC 820.44(A)(4) Exception, where proximity to electric light, power, Class 1, or non-power-limited fire alarm conductors cannot be avoided the clearance is 1.0 m (40 in.) at the pole while a minimum of 300 mm (12 in.) is required at all other points along the drop; similarly, 800.44(A)(4) allows 300 mm (12 in.) separation at any point in the span for 0–750 V supply drops above and parallel to communications drops provided ungrounded conductors are insulated and not less than 1.0 m (40 in.) is maintained at the pole.

NEC 2017 Section 820.44(A)(4)
16 AWG Class 1 control conductor overcurrent limitvs18 AWG Class 1 control conductor overcurrent limit

Per NEC 725.43, overcurrent protection shall not exceed 10 amperes for 16 AWG and shall not exceed 7 amperes for 18 AWG, while 14 AWG and larger conductors are protected in accordance with conductor ampacity.

NEC 2017 Section 725.43
Listed communications primary protector (800.170(A))vsFused-type primary protector (800.90(A)(2))

Per 800.170(A), the listed primary protector consists of an arrester connected between each line conductor and ground in an appropriate mounting with terminals marked line and ground, whereas a fuse in series with each line conductor is a feature of the fused-type primary protector described in 800.90(A)(2).

NEC 2017 Section 800.170(A)
Series resistancesvsParallel resistances

Series resistances add directly (R1 + R2 + …), while parallel resistances combine as 1/Rp = 1/R1 + 1/R2 + 1/R3 (or product-over-sum for two resistors), giving a value smaller than any single branch.

Table 250.66 (grounding electrode conductor sizing)vsTable 250.102(C)(1) (main bonding jumper sizing)

Table 250.66 sizes the grounding electrode conductor from the largest ungrounded service-entrance conductor (e.g., over 3/0 AWG through 350 kcmil copper requires 2 AWG copper), while per 250.28(D) the main bonding jumper shall not be smaller than the sizes shown in Table 250.102(C)(1).

NEC 2017 Table 250.66
Motor control conductors with separate overcurrent protection (Table 430.72(B), Column A)vsControl conductors protected by the motor branch-circuit device (Columns B and C)

For separate protection of 14 AWG and larger conductors, Note 1 directs the user to the ampacity value specified in 310.15, whereas the 400 percent and 300 percent multipliers of Notes 2 and 3 apply only where the motor branch-circuit short-circuit and ground-fault protective device protects control conductors larger than 10 AWG; the 500 percent figure belongs to 430.72(C)(4) for control transformer primaries rated less than 2 amperes.

NEC 2017 Table 430.72(B), Note 1
Antenna lead-in clearance from power conductors (810.18(A))vsAntenna lead-in clearance from lightning protection conductors (810.18(A)) and indoor lead-in separation (810.18(B))

Lead-in conductors attached to buildings shall not be able to swing closer than 600 mm (2 ft) to conductors of circuits of 250 volts or less between conductors, the clearance from any conductor of a lightning protection system shall not be less than 1.8 m (6 ft), and indoor antennas/lead-ins shall not be run nearer than 50 mm (2 in.) to conductors of other wiring systems unless those conductors are in metal raceway/cable armor or permanently separated by a continuous, firmly fixed nonconductor.

NEC 2017 Section 810.18(A)

Key Terms

Authority Having Jurisdiction (AHJ) NEC 2017 Article 100 (Definitions)
Per NEC Article 100, an organization, office, or individual responsible for enforcing the requirements of a code or standard, or for approving equipment, materials, an installation, or a procedure.
Bonding Jumper, Main NEC 2017 Article 100 (Definition: Bonding Jumper, Main)
Per NEC Article 100, the connection between the grounded circuit conductor and the equipment grounding conductor at the service; per 250.28(D) it shall not be smaller than the sizes shown in Table 250.102(C)(1).
Bonding Jumper, System NEC 2017 Article 100 (Definition: Bonding Jumper, System)
Per NEC Article 100, the connection between the grounded circuit conductor and the supply-side bonding jumper, the equipment grounding conductor, or both, at a separately derived system.
Fire Alarm Circuit NEC 2017 Section 760.2 (Fire Alarm Circuit)
Per the NEC 760.2 definition, a fire alarm circuit is classified as either non–power-limited or power-limited, and that classification determines the applicable installation requirements.
Class 1 circuit classification (725.41) NEC 2017 Section 725.41
Class 1 circuits are either Class 1 power-limited circuits meeting 725.41(A) or Class 1 remote-control and signaling circuits meeting 725.41(B).
Physical protection of Class 1 circuits (725.31(B)) NEC 2017 Section 725.31(B)
Where damage to a Class 1 remote-control or signaling circuit would introduce a hazard as covered in 725.31, the circuit is required to have physical protection.
Antenna discharge unit (810.20(A)) NEC 2017 Section 810.20(A)
A listed device required on each conductor of a lead-in from an outdoor antenna, except where the lead-in conductors are enclosed in a continuous metallic shield that is grounded with a conductor in accordance with 810.21 or is protected by an antenna discharge unit.
Listed communications primary protector (800.170(A)) NEC 2017 Section 800.170(A)
Equipment consisting of an arrester connected between each line conductor and ground in an appropriate mounting, with terminals marked to indicate line and ground.
Premises-powered broadband communications system (840.1) NEC 2017 Section 840.1
Per Article 840.1 Informational Note No. 1, a typical system is an optical fiber, twisted pair, or coaxial cable to the premises supplying a broadband signal to a network terminal that converts it into component electrical signals, with powering typically accomplished through a premises power supply; per 840.101(B), where premises circuits do not leave the building and the terminal is served by nonconductive optical fiber cable (or metallic members are interrupted by an insulating joint), communications circuits shall not be required to be grounded.
Medium-power network-powered broadband communications source (Table 830.15) NEC 2017 Table 830.15
A source whose circuit voltage Vmax is 0–150 volts, i.e., a maximum of 150 volts.
Coaxial cable power delivery (820.15) NEC 2017 Section 820.15
Coaxial cable is permitted to deliver power to equipment directly associated with the radio frequency distribution system if the voltage is not over 60 volts and if the current is supplied by a transformer or other device that has power-limiting characteristics; power shall be blocked from premises devices not intended to be powered via the coaxial cable.
Type CATVP plenum coaxial cable (820.179(A)) NEC 2017 Section 820.179(A)
Plenum coaxial cable listed as having adequate fire-resistant and low-smoke-producing characteristics; the Informational Note gives one method as a maximum peak optical density of 0.50 or less, an average optical density of 0.15 or less, and a maximum flame spread distance of 1.52 m (5 ft) or less when tested per NFPA 262.
NEC scope, 90.2(A) NEC 2017 Section 90.2(A)
The Code covers the installation and removal of electrical conductors, equipment, and raceways; signaling and communications conductors, equipment, and raceways; and optical fiber cables and raceways.
Conductor material default (110.5) NEC 2017 Section 110.5
Conductors normally used to carry current shall be copper or aluminum unless otherwise provided; where the material is not specified, the sizes given in the Code apply to copper conductors, and sizes shall be changed accordingly for other materials.
Conductor size expression (110.6) and Chapter 3 voltage scope (300.2(A)) NEC 2017 Section 110.6
Conductor sizes are expressed in American Wire Gage (AWG) or circular mils (AWG up to 4/0, kcmil above 4/0), and Chapter 3 wiring methods shall be used for 1000 volts, nominal, or less where not specifically limited, and are permitted over 1000 volts where specifically permitted elsewhere in the Code.
Limited Approach Boundary (Movable) — NFPA 70E Table 130.4(D)(a) Ugly's Electrical References 2020, Page 180
For phase-to-phase voltages of 151–750 volts (such as a 480-volt system), the Limited Approach Boundary for a movable conductor is 10 ft.

Formulas to Know

Ohm's Law — current from watts and voltsAmperes = Watts ÷ Volts; example: I = 1500 W ÷ 120 V = 12.5 A
Ohm's Law — resistanceOhms = Volts ÷ Amperes; example: R = 240 V ÷ 8 A = 30 Ω. Also R = E²/P; example: R = 14,400 ÷ 1200 = 12 Ω (or I = P/E = 1200/120 = 10 A, then R = 120/10 = 12 Ω)
Ohm's Law — voltageE = I × R; example: 10 A × 12 Ω = 120 V
Power formulasP = E × I (volts × amperes = watts); P = E² ÷ R; example: (240 V)² ÷ 20 Ω = 57,600 ÷ 20 = 2,880 W
Three-phase amperes when kilowatts are knownI = (kW × 1000) ÷ (E × PF × 1.73), where 1.73 is the approximate square root of 3 used as the three-phase multiplier
Apparent power (kVA) from real power and power factorS = P ÷ PF; example: 200 kW ÷ 0.8 = 250 kVA (check: 250 kVA × 0.8 = 200 kW)
Series circuit rulesTotal current equals the current in any other part of the circuit (IT = I1 = I2 = I3); series resistances add: RT = R1 + R2 + …; example: 3 Ω + 6 Ω + 5 Ω = 14 Ω, then I = E/R = 28 V ÷ 14 Ω = 2 A
Parallel resistance combiningTwo resistors: Rp = (R1 × R2) ÷ (R1 + R2); example: (10 × 15)/(10 + 15) = 6 Ω. Three or more: 1/Rp = 1/R1 + 1/R2 + 1/R3; example: 1/12 + 1/12 + 1/6 = 1/3, Rp = 3 Ω. Equal resistors: Rp = R ÷ number of branches (18 Ω ÷ 3 = 6 Ω)
Class 1 power-limited source overcurrent protection (power sources other than transformers)Overcurrent device rating shall be not more than 167 percent of (volt-ampere rating of the source ÷ rated voltage); the device may be integral to the supply but shall not be interchangeable with devices of higher ratings
Primary-side protection of a two-wire motor control transformer secondary (430.72(B) Exc. No. 2)Primary protection shall not exceed the appropriate maximum secondary conductor rating from Table 430.72(B) × the secondary-to-primary voltage ratio; secondaries other than two-wire are not considered protected by the primary device