Kansas General Building Contractor (A) Exam (ICC KGA, 2018 IBC)
Kansas · Pearson Vue
Kansas State Portion 90 questions
Key Distinctions
A dwelling unit has complete independent living facilities including permanent provisions for living, sleeping, eating, cooking AND sanitation, while a sleeping unit may have provisions for living, eating and either sanitation or kitchen facilities, but not both.
IBC 2018 Chapter 2 (Definitions), 'Dwelling Unit' and 'Sleeping Unit'A structure is 'that which is built or constructed,' while a building is any structure utilized or intended for supporting or sheltering an occupancy — support/shelter of an occupancy is the distinguishing element.
IBC 2018 Chapter 2 (Definitions), 'Building' and 'Structure'An approved agency is an established, recognized agency regularly engaged in conducting tests, furnishing inspection services or product certification and approved by the building official; an approved source is an independent person, firm or corporation approved by the building official, competent and experienced in applying engineering principles to materials, methods or systems analyses.
IBC 2018 Chapter 2 (Definitions), Section 202 — 'Approved Agency' (Book )A label carries the manufacturer's name, the product's function AND performance characteristics plus the name/identification of an approved agency indicating a representative sample was tested and evaluated; a mark carries only the manufacturer's name and the product's function.
IBC 2018 Chapter 2 (Definitions), Section 202 — 'Label'An addition is an extension or increase in floor area, number of stories or height (raising a roof to increase height is an addition even with no added floor area); an alteration is any construction or renovation to an existing structure other than a repair or addition.
IBC 2018 Chapter 2 (Definitions), 'Addition'Stairway capacity is the occupant load served × 0.3 inch per occupant (without sprinkler/emergency voice alarm reductions), while all other means of egress components use 0.2 inch per occupant.
IBC 2018 Section 1005.3.1For fixed seating without dividing arms the occupant load is not less than one person per 18 inches of seating length, whereas booths are computed at one person per 24 inches of booth seat length measured at the backrest.
IBC 2018 Page 259In the multistory allowable area equation, Sa (actual stories above grade plane) shall not exceed three for NFPA 13 sprinklered buildings, but the limit is four for buildings sprinklered under Section 903.3.1.2 (NFPA 13R), which itself is permitted in Group R up to four stories and 60 feet above grade plane.
IBC 2018 Section 506.2.3Lateral force on runway beams with electrically powered trolleys is 20 percent of the sum of the crane's rated capacity plus hoist and trolley weight, while longitudinal force (except bridge cranes with hand-geared bridges) is 10 percent of the maximum wheel loads; 25 percent is a vertical impact value.
IBC 2018 Section 1607.14.3Openable area of openings to the outdoors must be not less than 4 percent of the floor area ventilated (Section 1202.5.1), whereas the 8 percent figure applies to natural light glazing (Section 1204.2) and to openings between an interior room and an adjoining room.
IBC 2018 Section 1202.5.1Wood shakes shall only be used on slopes of not less than 4 units vertical in 12 horizontal, which is steeper than wood shingles (3:12) and clay/concrete tile (2½:12).
IBC 2018 Section 1507.9.2Guards generally shall not allow passage of a 4-inch-diameter sphere, but the triangular openings at the open side of a stair formed by riser, tread and bottom rail shall not allow passage of a 6-inch-diameter sphere (Exception 2).
IBC 2018 Section 1015.4Key Terms
Formulas to Know
Required stair width = occupant load served × 0.3 inch per occupant (factor without sprinkler/emergency voice alarm reductions)Required width = occupant load served × 0.2 inch (5.1 mm) per occupantAa = At + (NS × If), where NS is the tabular allowable area factor from Table 506.2 for a nonsprinklered building (used even if the building is sprinklered) and the sprinklered factor S1 is used only as AtIf = [F/P – 0.25] W/30; permitted only where not less than 25 percent of the building perimeter is on a public way or open spaceVasd = V × √0.6 (example from Table 1609.3.1: V = 130 mph gives Vasd = 101 mph)SDS = 2/3 × SMS; SD1 = 2/3 × SM1Not less than 220 sq ft, plus 100 sq ft for each occupant in excess of two (worked example: 3 occupants = 220 + 100 = 320 sq ft)W/C = 0.44 lb water per lb cement × 94 lb/bag = 41.4 lb water; 41.4 ÷ 8.33 lb/gal ≈ 5 gallons per bagLateral force (electrically powered trolley) = 20% × (rated crane capacity + weight of hoist and trolley), acting horizontally at the traction surface; longitudinal force (except bridge cranes with hand-geared bridges) = 10% × maximum wheel loads, acting horizontally at the traction surface parallel to the beamld = 0.002 db fs, but not less than 12 inches and not less than 40 bar diameters