Exam Cheat Sheet · Quick Reference
Kansas Residential Electrician Exam (ICC KGX, 2017 NEC)
Kansas · Pearson Vue
Kansas State Portion 60 questions
Key Distinctions
The main bonding jumper is the connection between the grounded circuit conductor and the equipment grounding conductor at the service, while a system bonding jumper serves a similar function at a separately derived system.
NEC 2017 Article 100 (Definition: Bonding Jumper, Main)Ungrounded line one is black and line two is red, while the grounded neutral conductor is white or gray.
Ugly's Electrical References, 2023 ed., Common Electrical Distribution Systems, Page 13 (2020 ed.: Common Electrical Distribution Systems)The single-phase three-wire system uses black and red ungrounded conductors with a white/gray neutral, while the delta high-leg system has a B phase that must be colored orange or tagged (caution: 208 volts orange to white).
Ugly's Electrical References, 2023 ed., Common Electrical Distribution Systems, Page 13 (2020 ed.: Common Electrical Distribution Systems)Per Article 90.2(B), the Code does not cover ships, watercraft other than floating buildings, railway rolling stock, aircraft, or automotive vehicles other than mobile homes and recreational vehicles.
NEC 2017 Section 90.2(B)(1)A continuous load is one where the maximum current is expected to continue for 3 hours or more and is taken at 125% in feeder sizing, while noncontinuous load is counted at 100%.
NEC 2017 Article 100 — Continuous Load definitionBoth use noncontinuous load plus 125% of continuous load, but one sizes the conductor ampacity and the other sizes the overcurrent protective device.
NEC 2017 Section 215.2(A)(1)(a)Per NEC 240.2 a tap conductor is a conductor, other than a service conductor, that has overcurrent protection ahead of its point of supply exceeding the value permitted for similar conductors protected per 240.4.
NEC 2017 Section 240.2Class 1 circuits are not permitted to exceed 600 volts, while Article 411 low-voltage lighting systems operate at no more than 30 volts ac or 60 volts dc.
NEC 2017 Section 725.41(B)Per the Article 760 definition, fire alarm circuits are classified as either non-power-limited or power-limited, and this classification determines the applicable installation requirements.
NEC 2017 Section 760.2 (Fire Alarm Circuit)For spans of 1000 volts or less, open individual conductors must be not smaller than 10 AWG copper for spans up to 50 ft and not smaller than 8 AWG copper for longer spans unless supported by a messenger wire.
NEC 2017 Section 225.6(A)For a 3-wire, single-phase dwelling unit service, conductors are permitted to have an ampacity of 83% of the service rating, allowing 2/0 AWG THW copper for a 200-ampere service instead of the 3/0 AWG otherwise required.
NEC 2017 Section 310.15(B)(7) with Table 310.15(B)(16)Derating factors may be applied to the higher 90°C ampacity, but the final derated ampacity cannot exceed the terminal temperature rating (for 1/0 AWG copper, the 75°C rating of 150 amps).
NEC 2017 Table 310.15(B)(2)(a) and Section 110.14(C)Surface-type enclosures in damp or wet locations require at least 1/4 in. airspace from the wall, but the exception permits nonmetallic enclosures to be installed without the airspace on concrete, masonry, tile, or similar surfaces.
NEC 2017 Section 312.2In a series circuit the total current equals the current in any other part (IT = I1 = I2 = I3) and resistances add, while equal resistors in parallel combine to a lower resistance (e.g., two 30 Ω in parallel = 15 Ω).
Ugly's Electrical References, 2023 ed., Series Circuits, Page 3 (2020 ed.: Series Circuits)Key Terms
Formulas to Know
I = E ÷ R; E = I × R; R = E ÷ I (e.g., R = 240 V ÷ 8 A = 30 Ω; E = 10 A × 12 Ω = 120 V)P = E × I (e.g., 120 V × 5 A = 600 W; 120 V × 12.5 A = 1,500 W); rearranged, I = Watts ÷ Volts (1500 W ÷ 120 V = 12.5 A)P = E² ÷ R (e.g., 240² ÷ 20 Ω = 57,600 ÷ 20 = 2,880 W)I = P ÷ E then R = E ÷ I, or directly R = E² ÷ P (e.g., 1200 W on 120 V: R = 14,400 ÷ 1,200 = 12 Ω)Series: RT = R1 + R2 + ...; two equal resistors in parallel: R ÷ 2; two resistors in parallel: (R1×R2)÷(R1+R2); series current IT = I1 = I2 = I3 (e.g., 7 Ω + (30 Ω ÷ 2) = 22 Ω; 44 V ÷ 22 Ω = 2 A; (8×8)/16 = 4 Ω plus (20×20)/40 = 10 Ω → 14 Ω)Vd = (2 × K × L × I) ÷ Cm, where K = 12.9 for copper at 75°C, L = one-way length in feet, I = amperes, Cm = circular mils; three-phase uses 1.73 in place of 2 (e.g., (2 × 12.9 × 150 × 30) ÷ 16,510 ≈ 7 volts)% VD = Voltage Drop ÷ Source Voltage × 100 (e.g., 7 V ÷ 240 V = 2.9%); NEC recommends total feeder plus branch-circuit drop not exceed 5%, with 3% recommended on each individuallyVD ∝ length: a 20% longer run raises a 3% drop to 3% × 1.20 = 3.6%; each standard AWG step up increases circular mils ~26% and reduces VD ~20%, so one size up restores the 3% maximum(Continuous load × 125%) + noncontinuous load (e.g., conductor: (100 A × 1.25) + 30 A = 155 A; OCPD per 215.3: 40 A + (1.25 × 80 A) = 140 A)General lighting = sq ft × 3 VA/sq ft; each small-appliance circuit = 1,500 VA; each laundry circuit = 1,500 VA; sum for total before demand factors (e.g., 2,000 sq ft + 2 SA + 1 laundry = 6,000 + 3,000 + 1,500 = 10,500 VA; 1,200 sq ft unit = 8,100 VA × 4 units = 32,400 VA)Corrected ampacity = table ampacity × correction factor (75°C conductors at 40°C: 0.88; 90°C conductors at 36–40°C: 0.91, e.g., 170 A × 0.91 = 154.7 A, capped by the 75°C terminal rating of 150 A per 110.14(C))Total ampacity = per-set ampacity × number of parallel sets (e.g., Table 310.16 90°C column, 350 kcmil copper = 350 A; two sets = 700 A)100% of heat pump compressor nameplate + 65% of supplemental electric heating where the compressor is not prevented from operating with the supplementary heat (e.g., 5,000 VA + (15,000 VA × 0.65) = 14,750 VA)R2 = R1[1 + α(T2 − 75)], with α(copper) = 0.00323 at 75°C (167°F)Where ungrounded supply conductors are larger than 1100 kcmil copper (or 1750 kcmil aluminum), the grounded conductor or bonding jumper shall have an area not less than 12½ percent of the area of the largest ungrounded supply conductor; with multiple sets, the equivalent size is the largest sum of the areas of corresponding conductors of each setNot less than 180 VA per single or multiple receptacle on one yoke; a single piece of equipment of four or more receptacles is calculated at not less than 90 VA per receptacle