Exam Cheat Sheet · Quick Reference

Kansas Residential Electrician Exam (ICC KGX, 2017 NEC)

Kansas  ·  Pearson Vue

Verified, not estimated. Every figure below is drawn from the official exam structure we maintain — question counts, passing standard and topic weighting. Practice questions are grounded in the source law with statute citations. We omit any figure we can't verify rather than guess at it.
Total questions
60
Passing score
75%
Exam time
180 min
Administered by
Pearson Vue
Format
Reference materials allowed

Kansas State Portion 60 questions

General Knowledge 7 Q · 12%
Electrical Theory and General Electrical Load CalculationsCode Definitions and TermsNEC Purpose, Scope, and Code ArrangementEquipment Approval, Listing, and Labeling RequirementsGeneral Installation Requirements (Article 110)Working Space and Clearances Around Electrical EquipmentConductor Materials, Sizes, and Temperature RatingsElectrical Symbols and Wiring DiagramsField Terms Versus NEC TermsUnits of Measurement, Conversions, and Basic Math for Electricians
Services and Service Equipment 13 Q · 22%
Service Load CalculationsService Equipment & Service ConductorsSystem Grounding and BondingService disconnect requirements and ratingsOverhead and underground service conductor installationGrounding electrode system and electrode typesEquipment grounding conductors — types, sizing, and identificationBonding methods at service equipment and piping systemsDemand factors for dwelling unit appliances and cooking equipmentOptional load calculation methods for dwelling units
Feeders 8 Q · 13%
Load CalculationsEquipment GroundingFeeder conductor ampacity and minimum sizing (NEC Article 215)Overcurrent protection for feedersFeeder neutral load calculations and permitted reductionsGround-fault protection of equipment on feeders rated 1000A or moreOutside feeder installation requirements (clearances, wiring methods, disconnecting means)Demand factors for dwelling unit appliance loads (dryers, ranges, cooking equipment)Feeder conductor identification (grounded, ungrounded, and equipment grounding conductors)
Branch Circuits and Conductors 15 Q · 25%
Branch Circuit CalculationsRequired Outlets & GFCI/AFCI ProtectionOvercurrent ProtectionEquipment GroundingConductorsVoltage Drop Calculations and Conductor SizingConductor Ampacity Tables and Temperature RatingsAmpacity Correction and Adjustment FactorsConductor Insulation Types and ApplicationsGrounded Conductor Identification and UseMultiwire Branch CircuitsBranch-Circuit Voltage Limitations
Wiring Methods and Materials 8 Q · 13%
Raceway InstallationsBoxes and EnclosuresFlexible Cords and CablesCable Wiring Methods (NM, MC, SE, UF, and Type UF underground installations)Conductor Protection Against Physical Damage (nail plates, clearances, framing members)Underground Installation Requirements and Burial DepthsConduit Fill Calculations and Conductor Count LimitsConduit Bending Techniques (90° stubs, offsets, saddle bends, back-to-back)Securing and Supporting Requirements for Cables and RacewaysCorrosion Protection for Raceways and EnclosuresProtection of Conductors in Vertical Raceways
Equipment and Devices 5 Q · 8%
LuminairesReceptacles, Switches and Other DevicesAppliances and Other EquipmentLuminaire location requirements (wet, damp, closets, bathtub/shower zones)Recessed luminaire installation (Type IC vs. non-IC, thermal protection, clearances)Lighting track installation and construction requirementsLow-voltage lighting system requirements (Article 411)Switch ratings, types, and installation requirementsNEMA receptacle and attachment plug configurationsDisconnecting means for appliancesGFCI protection requirements for appliances
Special Occupancies, Equipment, and Conditions 4 Q · 7%
Swimming Pools and Similar InstallationsLow Voltage Circuits, Alarm & Similar SystemsFire Alarm Circuit Classifications (NPLFA vs. PLFA) and Power Source RequirementsFire Alarm Cable Types and Installation by Location (FPLP, FPLR, FPL, NPLFP, NPLFR, NPLF)Class 1, Class 2, and Class 3 Circuit Definitions and Power Source LimitationsSeparation and Mixing Rules for Class 2/3 Circuits with Other Circuit TypesCommunications Circuit Wiring Methods, Cable Types (CMP, CMR, CM, CMX), and Installation by LocationPrimary Protector Requirements and Grounding/Bonding for Communications SystemsRadio and Television Antenna Systems: Grounding, Clearances, and Discharge Units

Key Distinctions

Main bonding jumpervsSystem bonding jumper

The main bonding jumper is the connection between the grounded circuit conductor and the equipment grounding conductor at the service, while a system bonding jumper serves a similar function at a separately derived system.

NEC 2017 Article 100 (Definition: Bonding Jumper, Main)
Ungrounded conductors in a 120/240V, single-phase, three-wire systemvsGrounded neutral conductor in a 120/240V, single-phase, three-wire system

Ungrounded line one is black and line two is red, while the grounded neutral conductor is white or gray.

Ugly's Electrical References, 2023 ed., Common Electrical Distribution Systems, Page 13 (2020 ed.: Common Electrical Distribution Systems)
120/240-volt, single-phase, three-wire systemvs120/240-volt, three-phase, four-wire system (Delta high leg)

The single-phase three-wire system uses black and red ungrounded conductors with a white/gray neutral, while the delta high-leg system has a B phase that must be colored orange or tagged (caution: 208 volts orange to white).

Ugly's Electrical References, 2023 ed., Common Electrical Distribution Systems, Page 13 (2020 ed.: Common Electrical Distribution Systems)
Installations covered by the NECvsInstallations not covered by the NEC

Per Article 90.2(B), the Code does not cover ships, watercraft other than floating buildings, railway rolling stock, aircraft, or automotive vehicles other than mobile homes and recreational vehicles.

NEC 2017 Section 90.2(B)(1)
Continuous loadvsNoncontinuous load

A continuous load is one where the maximum current is expected to continue for 3 hours or more and is taken at 125% in feeder sizing, while noncontinuous load is counted at 100%.

NEC 2017 Article 100 — Continuous Load definition
Minimum feeder conductor ampacity (215.2(A)(1)(a), 2017)vsMinimum feeder overcurrent device rating (215.3)

Both use noncontinuous load plus 125% of continuous load, but one sizes the conductor ampacity and the other sizes the overcurrent protective device.

NEC 2017 Section 215.2(A)(1)(a)
Tap conductorvsService conductor

Per NEC 240.2 a tap conductor is a conductor, other than a service conductor, that has overcurrent protection ahead of its point of supply exceeding the value permitted for similar conductors protected per 240.4.

NEC 2017 Section 240.2
Class 1 remote-control and signaling circuits (Art. 725)vsLow-voltage lighting systems (Art. 411)

Class 1 circuits are not permitted to exceed 600 volts, while Article 411 low-voltage lighting systems operate at no more than 30 volts ac or 60 volts dc.

NEC 2017 Section 725.41(B)
Non-power-limited fire alarm circuitsvsPower-limited fire alarm circuits

Per the Article 760 definition, fire alarm circuits are classified as either non-power-limited or power-limited, and this classification determines the applicable installation requirements.

NEC 2017 Section 760.2 (Fire Alarm Circuit)
Open conductor span up to 50 ft (225.6(A)(1))vsOpen conductor span longer than 50 ft

For spans of 1000 volts or less, open individual conductors must be not smaller than 10 AWG copper for spans up to 50 ft and not smaller than 8 AWG copper for longer spans unless supported by a messenger wire.

NEC 2017 Section 225.6(A)
Standard ampacity table sizingvsDwelling service allowance of 310.15(B)(7)

For a 3-wire, single-phase dwelling unit service, conductors are permitted to have an ampacity of 83% of the service rating, allowing 2/0 AWG THW copper for a 200-ampere service instead of the 3/0 AWG otherwise required.

NEC 2017 Section 310.15(B)(7) with Table 310.15(B)(16)
90°C conductor ampacity used for deratingvs75°C terminal rating limit (110.14(C))

Derating factors may be applied to the higher 90°C ampacity, but the final derated ampacity cannot exceed the terminal temperature rating (for 1/0 AWG copper, the 75°C rating of 150 amps).

NEC 2017 Table 310.15(B)(2)(a) and Section 110.14(C)
Surface-type enclosure airspace rule (312.2)vsException for nonmetallic enclosures

Surface-type enclosures in damp or wet locations require at least 1/4 in. airspace from the wall, but the exception permits nonmetallic enclosures to be installed without the airspace on concrete, masonry, tile, or similar surfaces.

NEC 2017 Section 312.2
Series circuit currentvsParallel resistor combination

In a series circuit the total current equals the current in any other part (IT = I1 = I2 = I3) and resistances add, while equal resistors in parallel combine to a lower resistance (e.g., two 30 Ω in parallel = 15 Ω).

Ugly's Electrical References, 2023 ed., Series Circuits, Page 3 (2020 ed.: Series Circuits)

Key Terms

Continuous load (Article 100) NEC 2017 Article 100 — Continuous Load definition
A load where the maximum current is expected to continue for 3 hours or more.
Main bonding jumper (Article 100) NEC 2017 Article 100 (Definition: Bonding Jumper, Main)
The connection between the grounded circuit conductor and the equipment grounding conductor at the service.
Tap conductor (240.2) NEC 2017 Section 240.2
A conductor, other than a service conductor, that has overcurrent protection ahead of its point of supply exceeding the value permitted for similar conductors protected as described elsewhere in 240.4.
Fire alarm circuit (760.2) NEC 2017 Section 760.2 (Fire Alarm Circuit)
A circuit of a fire alarm system, classified as either non-power-limited or power-limited.
Authority having jurisdiction (90.4) NEC 2017 Section 90.4
The enforcement authority responsible for interpreting NEC rules, deciding on approval of equipment and materials, and granting special permission contemplated in a number of the rules.
Ambient temperature correction baseline (310.15(B)) NEC 2017 Section 310.15(B)
Ampacity correction factors shall be applied where the ambient temperature is other than the 30°C (86°F) baseline of the standard ampacity tables.
Grounded conductor identification (200.6(A)) NEC 2017 Section 200.6(A)
An insulated grounded conductor 6 AWG or smaller shall be identified by a continuous white outer finish, a continuous gray outer finish, or three continuous white or gray stripes along its entire length on other than green insulation.
Continuity of the grounded conductor (200.2(B)) NEC 2017 Section 200.2(B)
The continuity of a grounded conductor shall not depend on a connection to a metallic enclosure, raceway, or cable armor.
Objectionable current exclusion (250.6(D)) NEC 2017 Section 250.6(D)
Currents that introduce noise or data errors in electronic equipment shall NOT be considered the objectionable currents addressed in 250.6.
Low-voltage lighting system (411.1) NEC 2017 Section 411.1
Lighting systems and associated components operating at no more than 30 volts ac or 60 volts dc; secondary circuits shall not be grounded (411.6(A)).
Class 1 remote-control and signaling circuit (725.41(B)) NEC 2017 Section 725.41(B)
A circuit that is not permitted to exceed 600 volts.
Service conductor routing restriction (230.3) NEC 2017 Section 230.3
Service conductors supplying a building or other structure shall not pass through the interior of another building or other structure.
Common neutral for feeders (215.4(A)) NEC 2017 Section 215.4(A)
Up to three sets of 3-wire feeders, or two sets of 4-wire or 5-wire feeders, shall be permitted to utilize a common neutral.
Feeder diagram (215.5) NEC 2017 Section 215.5
Where required by the AHJ, a diagram provided prior to installation showing the area in square feet, the total calculated load before demand factors, the demand factors used, the calculated load after demand factors, and the size and type of conductors.
Coordination system basis (240.12) NEC 2017 Section 240.12
Where an orderly shutdown is required to minimize hazards, a system of coordination based on (1) coordinated short-circuit protection and (2) overload indication based on monitoring systems or devices shall be permitted.
Ground-fault protection of equipment (240.13) NEC 2017 Section 240.13
Required for solidly grounded wye systems of more than 150 volts to ground but not exceeding 1000 volts phase-to-phase for each individual device used as a building or structure main disconnecting means rated 1000 amperes or more.
Expansion fittings for PVC conduit (352.44) NEC 2017 Section 352.44
Fittings that must be provided to compensate for thermal expansion and contraction where the expected length change is 1/4 in. or greater in a straight run between securely mounted items.
Storable pool cord-connected filter pump GFCI (680.31) NEC 2017 Section 680.31
A cord-connected pool filter pump must have GFCI protection that is integral to the attachment plug or located in the power-supply cord within 12 in. of the attachment plug.

Formulas to Know

Ohm's Law — current, voltage, and resistanceI = E ÷ R; E = I × R; R = E ÷ I (e.g., R = 240 V ÷ 8 A = 30 Ω; E = 10 A × 12 Ω = 120 V)
Power from volts and amperesP = E × I (e.g., 120 V × 5 A = 600 W; 120 V × 12.5 A = 1,500 W); rearranged, I = Watts ÷ Volts (1500 W ÷ 120 V = 12.5 A)
Power from voltage and resistanceP = E² ÷ R (e.g., 240² ÷ 20 Ω = 57,600 ÷ 20 = 2,880 W)
Resistance from watts and voltsI = P ÷ E then R = E ÷ I, or directly R = E² ÷ P (e.g., 1200 W on 120 V: R = 14,400 ÷ 1,200 = 12 Ω)
Series/parallel resistance combinationSeries: RT = R1 + R2 + ...; two equal resistors in parallel: R ÷ 2; two resistors in parallel: (R1×R2)÷(R1+R2); series current IT = I1 = I2 = I3 (e.g., 7 Ω + (30 Ω ÷ 2) = 22 Ω; 44 V ÷ 22 Ω = 2 A; (8×8)/16 = 4 Ω plus (20×20)/40 = 10 Ω → 14 Ω)
Single-phase voltage drop (inductance negligible)Vd = (2 × K × L × I) ÷ Cm, where K = 12.9 for copper at 75°C, L = one-way length in feet, I = amperes, Cm = circular mils; three-phase uses 1.73 in place of 2 (e.g., (2 × 12.9 × 150 × 30) ÷ 16,510 ≈ 7 volts)
Percent voltage drop% VD = Voltage Drop ÷ Source Voltage × 100 (e.g., 7 V ÷ 240 V = 2.9%); NEC recommends total feeder plus branch-circuit drop not exceed 5%, with 3% recommended on each individually
Voltage drop proportional to lengthVD ∝ length: a 20% longer run raises a 3% drop to 3% × 1.20 = 3.6%; each standard AWG step up increases circular mils ~26% and reduces VD ~20%, so one size up restores the 3% maximum
Minimum feeder conductor ampacity / OCPD rating with continuous and noncontinuous loads(Continuous load × 125%) + noncontinuous load (e.g., conductor: (100 A × 1.25) + 30 A = 155 A; OCPD per 215.3: 40 A + (1.25 × 80 A) = 140 A)
Dwelling general load components (Article 220 examples)General lighting = sq ft × 3 VA/sq ft; each small-appliance circuit = 1,500 VA; each laundry circuit = 1,500 VA; sum for total before demand factors (e.g., 2,000 sq ft + 2 SA + 1 laundry = 6,000 + 3,000 + 1,500 = 10,500 VA; 1,200 sq ft unit = 8,100 VA × 4 units = 32,400 VA)
Ambient temperature correction of ampacityCorrected ampacity = table ampacity × correction factor (75°C conductors at 40°C: 0.88; 90°C conductors at 36–40°C: 0.91, e.g., 170 A × 0.91 = 154.7 A, capped by the 75°C terminal rating of 150 A per 110.14(C))
Parallel conductor ampacityTotal ampacity = per-set ampacity × number of parallel sets (e.g., Table 310.16 90°C column, 350 kcmil copper = 350 A; two sets = 700 A)
Optional dwelling calculation — central electric space heating with heat pump (220.82(C)(3))100% of heat pump compressor nameplate + 65% of supplemental electric heating where the compressor is not prevented from operating with the supplementary heat (e.g., 5,000 VA + (15,000 VA × 0.65) = 14,750 VA)
Conductor DC resistance temperature adjustmentR2 = R1[1 + α(T2 − 75)], with α(copper) = 0.00323 at 75°C (167°F)
Grounded conductor / bonding jumper for very large supply conductorsWhere ungrounded supply conductors are larger than 1100 kcmil copper (or 1750 kcmil aluminum), the grounded conductor or bonding jumper shall have an area not less than 12½ percent of the area of the largest ungrounded supply conductor; with multiple sets, the equivalent size is the largest sum of the areas of corresponding conductors of each set
Receptacle outlet load (220.14(I))Not less than 180 VA per single or multiple receptacle on one yoke; a single piece of equipment of four or more receptacles is calculated at not less than 90 VA per receptacle