Exam Cheat Sheet · Quick Reference

Maryland Journey Natural Gas Fitter

Maryland  ·  PSI Services Contractor

Verified, not estimated. Every figure below is drawn from the official exam structure we maintain — question counts, passing standard and topic weighting. Practice questions are grounded in the source law with statute citations. We omit any figure we can't verify rather than guess at it.
Total questions
40
Passing score
70%
Exam time
90 min
Administered by
PSI Services Contractor
Format
Reference materials allowed

Maryland State Portion 40 questions

General Piping 15 Q · 38%
Allowable pressure drop and maximum operating pressure for indoor piping systemsApproved piping materials and tubing standards (steel, copper, CSST, polyethylene, aluminum)Piping joints, fittings, and connection methods (threaded, brazed, welded, press-connect, flared)Piping system installation requirements (prohibited locations, underground burial depth, protection from physical damage, corrosion protection)Pressure testing and inspection of gas piping (test medium, test pressure, test duration, leak detection)Purging procedures for gas piping systemsPipe support spacing, shutoff valves, drips, sediment traps, and flow controls
Pipe Sizing/Math 10 Q · 25%
Gas pipe sizing using longest length, branch length, and hybrid pressure methodsCalculating maximum gas demand in CFH from appliance BTU ratingsPressure drop allowances and equivalent lengths for fittings and valvesFitting allowances and end-to-end pipe length calculations for threaded, copper, and welded fittingsOffset, diagonal, rise, and run calculations using angle constants (45°, 60°, 22.5°)Grade, percent grade, drop, and run calculations for sloped pipingVolume, pressure, and capacity calculations for pipe and water systemsFraction, decimal, and unit conversion for pipe measurements
Chimney and Flues 5 Q · 12%
Appliance venting categories and type of venting system selectionVent and chimney termination height and location requirementsVent connector materials, sizing, slope, and clearancesMasonry chimney construction, lining, and inspection requirementsSizing Category I appliance venting systems using tablesGas vent types (Type B, BW, L) and installation requirementsDirect-vent and mechanical draft system termination clearancesDraft hoods, draft controls, and vent dampers
Combustion 5 Q · 12%
Combustion air requirements: indoor vs. outdoor methods (IFGC Section 304)Combustion air opening sizing and location (minimum free area per Btu/h)Flammability limits of natural gas and propane (ignition threshold percentages)Properties of natural gas vs. propane: weight relative to air, toxicity, odorizationDefinition and composition of combustion air, combustion products, and flue gasesCombustion chamber and burner definitions (main burner, power burner, induced-draft burner)Mechanical and engineered combustion air supply systems (Sections 304.8–304.9)Latent heat, heat transfer (Btu), and temperature conversion as applied to combustion processes
Appliances 5 Q · 12%
Listing, labeling, and testing standards for specific appliance typesInstallation clearances to combustible materials for heating appliancesClothes dryer exhaust duct requirements (materials, length, termination)Unvented room heater restrictions (input rating, oxygen-depletion safety shutoff, prohibited locations)Cooking appliance installation requirements and vertical clearancesWater heater installation and dual-use (space heating) requirementsSafety inspection procedures for existing appliance installations (gas leak checks, CO measurement thresholds, combustion air and vent draft testing)Flame safeguard and ignition device requirements for decorative and vented fireplace appliances

Key Distinctions

Flue gasesvsCombustion products

Flue gases are combustion products plus excess air in appliance flues or heat exchangers, whereas combustion products are the constituents resulting from combustion of fuel with oxygen (including inert gases) but exclude excess air.

IFGC 2018 Chapter 2 Definitions
Wood louver (free area unknown)vsMetal louver or grille (free area unknown)

Where the design and free area are not known, wood louvers are assumed to have 25% free area while metal louvers and grilles are assumed to have 75% free area (screens not smaller than 1/4-inch mesh).

IFGC 2018 Chapter 3 General Regulations, Section 304.10
PipevsTubing

Pipe is a rigid conduit of iron, steel, copper, copper-alloy, or plastic, while tubing is a semirigid conduit of copper, copper-alloy, aluminum, plastic, or steel.

IFGC 2018 Section 202, Definitions
Pressure testvsLeak check

A pressure test verifies the gas-tight integrity of gas piping following installation or modification, while a leak check verifies that the system does not leak (typically during or after placing in service).

IFGC 2018 Section 202, Definitions
Pressure testvsPurge

A pressure test verifies gas-tight integrity after installation or modification, whereas purging frees a gas conduit of air or gas, or a mixture of gas and air.

IFGC 2018 Section 202, Definitions
Code scope — natural gas pipingvsCode scope — LP-gas piping

The code covers natural gas piping systems operating at 125 psig or less, but LP-gas piping systems only at 20 psig or less (except as provided in Section 402.7).

IFGC 2018 Section 101.2.2
Indoor piping at 5 psig maximum (general rule)vsIndoor piping permitted above 5 psig (exception)

Indoor piping systems must not exceed 5 psig unless a listed condition is met, such as welded/brazed joints, piping in a ventilated chase or otherwise enclosed against accidental gas accumulation, industrial/warehouse/boiler rooms, temporary installations, or agricultural use; residential kitchens, finished basements, and cast-iron threaded fittings are not qualifying conditions.

IFGC 2018 Section 402.7
Holes bored in wood joistsvsHoles bored in wood studs (exterior bearing wall)

Bored hole diameter in joists must not exceed one-third the member depth (and not within 2 inches of top or bottom), while bored holes in wood studs must not exceed 40 percent of stud depth (60 percent allowed only in nonbearing partitions or doubled studs under certain conditions).

IFGC 2018 Section 302.3.2
Underground piping — 12 inches minimum burialvsUnderground piping — 8 inches reduced burial

Underground piping systems must be at least 12 inches below grade; the reduced 8-inch depth is allowed only for individual lines to outdoor lights, grills, and similar appliances under specific conditions.

IFGC 2018 Section 404.12
Service shutoff valvevsAppliance shutoff valve

A service shutoff valve is installed by the serving gas supplier between the meter/source of supply and the customer piping system to shut off the entire system, while an appliance shutoff valve must be in the same room as the appliance, within 6 feet of it, and upstream of the union, connector, or quick-disconnect it serves.

IFGC 2018 Section 202, Definitions
Steel pipe fitting equivalent lengths (table values)vsCopper or copper-alloy valve equivalent lengths

Table equivalent-length values are calculated for steel pipe and may be used with reasonable accuracy for copper/copper-alloy fittings and bends, but for copper or copper-alloy valves the equivalent length must be taken as 45 percent longer than the listed values.

IFGC 2018 Appendix A, Section A.3.1
Prohibited piping material — cast ironvsPermitted piping materials

Cast-iron pipe shall not be used for gas piping, while steel pipe (Schedule 10 or heavier), copper tubing, and CSST are permitted under appropriate conditions; aluminum-alloy pipe is permitted but not in exterior locations or underground, and copper/copper alloy may not be used where the gas contains more than an average of 0.3 grains of hydrogen sulfide per 100 standard cubic feet.

IFGC 2018 Section 403.4.1

Key Terms

Drip IFGC 2018 Section 202, Definitions
The container placed at a low point in a system of piping to collect condensate and from which the condensate is removable.
Piping system IFGC 2018 Section 202, Definitions
The fuel piping, valves and fittings from the outlet of the point of delivery to the outlets of the appliance shutoff valves.
Service shutoff valve IFGC 2018 Section 202, Definitions
A valve installed by the serving gas supplier between the service meter or source of supply and the customer piping system, to shut off the entire piping system.
Appliance shutoff valve IFGC 2018 Section 409.5.1
The shutoff valve required to be located in the same room as the appliance and within 6 feet of it, installed upstream of the union, connector, or quick-disconnect device it serves.
Purge IFGC 2018 Section 202, Definitions
To free a gas conduit of air or gas, or a mixture of gas and air; purging operations that introduce fuel gas must be stopped when 90 percent fuel gas by volume is detected within the pipe (large systems requiring outdoor discharge).
Pressure test IFGC 2018 Section 202, Definitions
An operation performed to verify the gas-tight integrity of gas piping following its installation or modification; the test pressure must be at least 1½ times the proposed maximum working pressure but not less than 3 psig irrespective of design pressure, and the duration must be at least 10 minutes for systems under 10 cubic feet or in a single-family dwelling.
Leak check IFGC 2018 Section 202, Definitions
An operation performed on a gas piping system to verify that the system does not leak.
Pressure drop IFGC 2018 Section 202
The loss in pressure due to friction or obstruction in pipes, valves, fittings, regulators and burners.
Brazing IFGC 2018 Section 202, Definitions
A metal-joining process using a nonferrous filler metal with a melting point above 1,000°F but lower than the base metal; brazing alloys for gas piping joints shall not contain more than 0.05-percent phosphorus.
Combustion air IFGC 2018 Chapter 2 Definitions
Air necessary for complete combustion of a fuel, including theoretical air and excess air; it is distinct from ventilation air or dilution air although all three may come through the same openings.
Combustion products IFGC 2018 Chapter 2 Definitions
Constituents resulting from the combustion of fuel with oxygen, including inert gases but excluding excess air.
Induced-draft burner IFGC 2018 Chapter 2 Definitions
A burner that depends on draft induced by a fan that is an integral part of the appliance and is located downstream from the burner.
Longest Length Method IFGC 2018 Appendix A, Section A.3.1
A sizing method in which the length of piping from the point of delivery to the most remote outlet is the only length used to size every section of the gas piping system.
Shield plate (concealed piping protection) IFGC 2018 Section 404.7.3
Steel protection of not less than 0.0575 inch thickness (No. 16 gage) required where piping in a light-frame assembly is less than 1½ inches from the face of the framing member to which membranes will be attached.
Test medium (pressure testing) IFGC 2018 Section 406.2
The test medium shall be air, nitrogen, carbon dioxide, or an inert gas; oxygen, natural gas, and acetylene are not permitted.
Underground piping beneath buildings IFGC 2018 Section 404.14
Prohibited except where encased in a conduit of wrought iron, plastic pipe, steel pipe, a piping or encasement system listed for installation beneath buildings, or other approved conduit material.

Formulas to Know

Appliance gas demand in cubic feet per hour (CFH)CFH = total BTU/h input ÷ heating value (BTU per cubic foot); e.g., 75,000 ÷ 1,000 = 75 CFH. Where appliance ratings are unknown, use the approximate consumption values in Table 402.2.
Spare (or short) pipe capacity from the sizing tableSpare cfh = table capacity of the installed pipe size at that length − appliance demand (Table 402.4(2), Schedule 40 metallic, <2 psi inlet, 0.5 in. w.c. drop, SG 0.60); e.g., 247 − 35 = 212 cfh; 137 − 80 = 57 cfh; 44 − 40 = 4 cfh; 117 − 40 = 77 cfh.
Equivalent length allowance for fittings and valvesAdd equivalent length whenever a run has four or more fittings: total = number of fittings × table equivalent length (e.g., 6 × 2.62 ft = 15.72 ft for screwed 90° ells on 1-in. Sch 40; 4 × 2.41 ft = 9.64 ft for screwed 45° ells on 2-in. Sch 40). For copper or copper-alloy valves, take equivalent length as 45% longer than the table values.
Offset constants (parallel-pipe offsets)45°: diagonal = offset × 1.414 (10 × 1.414 = 14.14 in.). 60°: diagonal = offset × 1.1547 (10 × 1.1547 ≈ 11.55 in.); run = diagonal × 0.5000 (24 × 0.5 = 12 in.); run = offset × 0.5774 (18 × 0.5774 = 10.39 in.). 30°: diagonal = offset × 2.000 (14 × 2 = 28.00 in.).
Rolling offset true offsetTrue offset = √(rise² + horizontal offset²); e.g., √(6² + 8²) = √100 = 10 in.; then apply the fitting-angle constant to get the diagonal.
Grade, drop, and percent gradeDrop = grade × run (¼ in./ft × 18 ft = 4½ in.); Grade = drop ÷ run (10 in. ÷ 50 ft = 0.20 in./ft); Percent grade = (drop ÷ run) × 100 with drop and run in the same units (8 in. = 0.667 ft; 0.667 ÷ 60 × 100 ≈ 1.1%; 3.5 ft ÷ 200 ft × 100 = 1.75%).
Water head and pressure conversionsPressure = 0.434 psi × height in feet (0.434 × 42 ft ≈ 18.2 psi); Height = 2.304 ft × psi (2.304 × 25 = 57.60 ft); based on water weighing 62.5 lb per cubic foot.
Volume and weight of water; standard measuresPipe volume shortcut: V (gal) = 0.0408 × d²(in.) × h(ft) → 0.0408 × 3² × 8 ≈ 2.94 gal (a 1-in. dia., 1-ft long cylinder holds 0.0408 gal). Weight = 62.5 lb/cu ft × cu ft (15 × 62.5 = 937.5 lb). 1 gal water ≈ 8.33 lb; 1 U.S. gal = 231 cu in.; 1 cu ft = 12 × 12 × 12 = 1,728 cu in.
Decimal-to-fraction (nearest sixteenth) conversionMultiply the decimal by 16 and round when the next digit is 5 or greater: 0.375 × 16 = 6/16 = 3/8 in.; 0.725 × 16 = 11.6 → 12/16 = 3/4 in.; 1.78 ft × 12 = 21.36 in., 0.36 × 16 = 5.76 → 6/16 = 21 3/8 in.
Cut-length (fitting allowance) rulesThreaded: allowance per fitting = center-to-face − thread-in (1⅛ − ½ = ⅝ in.), end-to-end = c-c − total allowance (10 − 1¼ = 8¾ in.). Copper: e-e = c-c − sum of fitting allowances (10 − (½ + ¼) = 9¼ in.). Butt-weld elbows: long-radius 90° = 1½ × pipe size (1.5 × 4 = 6 in.), short-radius 90° = 1 × pipe size (6-in. pipe = 6 in.), 45° = ⅝ × pipe size (⅝ × 8 = 5 in.), and reduce e-e an additional ⅛ in. per butt-weld fitting for the weld gap (3-in. pipe: 24 − 2[(1.5 × 3) + 0.125] = 14¾ in.).