Exam Cheat Sheet · Quick Reference

Maryland Journeyperson Electrician

Maryland  ·  PSI Services Contractor

Verified, not estimated. Every figure below is drawn from the official exam structure we maintain — question counts, passing standard and topic weighting. Practice questions are grounded in the source law with statute citations. We omit any figure we can't verify rather than guess at it.
Total questions
70
Passing score
70%
Exam time
210 min
Administered by
PSI Services Contractor
Format
Reference materials allowed

Maryland State Portion 70 questions

Electrical Theory 20 Q · 29%
DefinitionsTheory Including Ohm's LawTechniquesTroubleshootingEquipment/DevicesInstrumentsMaterialsMathConversionsDiagramsSymbols
Wiring and Protection 20 Q · 29%
NEC Article 100NEC Article 110NEC Article 200-210NEC Article 215-225NEC Article 230NEC Article 240NEC Article 250-285
Wiring Methods and Materials 12 Q · 17%
NEC Article 300NEC Article 310-314NEC Article 320-330NEC Article 332-356NEC Article 358-374NEC Article 376-398
Equipment for General Use 6 Q · 9%
NEC Article 400-411NEC Article 422-427NEC Article 430-450NEC Article 455-490
Special Occupancies 4 Q · 6%
NEC Article 500-525NEC Article 530-547NEC Article 550-590
Special Equipment 2 Q · 3%
NEC Article 600-675NEC Article 680-695
Special Communications 6 Q · 9%
NEC Article 700-708NEC Article 720-830

Key Distinctions

Ammeter (M1)vsVoltmeter (M2)

An ammeter is connected in series to carry the full circuit current and must have very low internal resistance, while a voltmeter is connected in parallel across a component to read potential difference and has very high internal resistance so it draws negligible current.

Type MC cable bending radiusvsType MI cable bending radius

Type MC with interlocked-type armor or corrugated sheath requires a minimum bend radius of seven times the external diameter of the metallic sheath, while Type MI greater than 19 mm (3/4 in.) but not more than 25 mm (1 in.) in external diameter requires ten times the external diameter.

NEC 2020 Section 330.24(B)
EMT support spacingvsType MC cable securing interval

EMT must be secured at intervals not exceeding 3 m (10 ft) and within 900 mm (3 ft) of each termination, while Type MC cable, unless otherwise provided, must be secured at intervals not exceeding 1.8 m (6 ft).

NEC 2020 Section 358.30(A)
EMT fastening at terminationsvsFMC fastening at terminations

EMT must be securely fastened within 900 mm (3 ft) of each outlet box, junction box, device box, cabinet, conduit body, or other tubing termination, while FMC must be securely fastened within 300 mm (12 in.) of each box, cabinet, conduit body, or other conduit termination.

NEC 2020 Section 358.30(A)
Real power (watts)vsApparent power (kVA)

Real power is the actual power consumed (P = √3 × V × I × cos θ in three phase), while apparent power is the vector sum of real and reactive power found by S = P ÷ PF and it stays unchanged when power factor changes at constant voltage and current.

Inductive reactance formula XL = 2πfLvsIncorrect form XL = 2πfC

Inductive reactance uses inductance L with frequency f (XL = 2πfL); substituting capacitance C makes the formula wrong.

Metal underground water pipe electrode (10 ft)vsConcrete-encased electrode (20 ft)

A metal underground water pipe qualifies as a grounding electrode with 10 ft or more in direct earth contact, while a concrete-encased electrode requires at least 20 ft of bare or zinc galvanized steel rebar not less than 1/2 in. diameter or bare copper not smaller than 4 AWG, encased in at least 2 in. of concrete.

NEC 2020 Section 250.52(A)(1)
Earth as ground-fault pathvsEffective ground-fault current path

The earth shall not be considered an effective ground-fault current path; an effective path must be a low-impedance circuit capable of safely carrying maximum ground-fault current and facilitating operation of the overcurrent device.

NEC 2020 Section 250.4(A)(5)
60°C/75°C/90°C conductor ratingvsTermination temperature limit

Even with 90°C-rated conductors, for circuits over 100 amperes (or marked for conductors larger than 1 AWG) the ampacity must be determined at 75°C unless the equipment is listed and identified for use at a higher rating.

NEC 2020 Section 110.14(C)(1)(b)
Type MC cable in plenumvsType NM, ENT, and PVC in plenum

Type MC cable without an overall nonmetallic covering (and Type MI without a nonmetallic covering) is permitted in other spaces used for environmental air, while Type NM, ENT, and PVC are not permitted unless enclosed in an approved metal raceway.

NEC 2020 Section 300.22(C)(1)
Grounded conductor terminal identificationvsMain/system bonding jumper screw identification

A terminal for the grounded conductor on receptacles, plugs, and connectors is identified by metal or metal coating substantially white or silver, or the word 'white' or letter 'W'; a main or system bonding jumper that is a screw only must be identified with a green finish visible with the screw installed.

NEC 2020 Section 200.10(B)
Bonding over 250 volts to groundvsBonding at services

For circuits over 250 volts to ground, continuity of metal raceways and cables with metal sheaths must use one of the service methods of 250.92(B) except bonding to the grounded service conductor, because that method applies only to service equipment.

NEC 2020 Section 250.97
Good fuse voltage readingvsOpen fuse voltage reading

A voltmeter across a good fuse reads about 0 V because a good fuse drops almost no voltage, whereas a 120 V reading across the fuse indicates the fuse itself is open.

Key Terms

Ampacity NEC 2020 Article 100 — Definition of Ampacity
The maximum current, in amperes, that a conductor can carry continuously under the conditions of use without exceeding its temperature rating.
Continuous Load NEC 2020 Article 100 — Definition of Continuous Load
A load where the maximum current is expected to continue for 3 hours or more.
Effective ground-fault current path NEC 2020 Section 250.4(A)(5)
A low-impedance circuit capable of safely carrying the maximum ground-fault current and facilitating operation of the overcurrent device; the earth shall not be considered such a path.
Grounding electrode — metal underground water pipe NEC 2020 Section 250.52(A)(1)
A metal underground water pipe in direct contact with the earth for 10 ft or more, including any metal well casing bonded to the pipe, is permitted as a grounding electrode.
Concrete-encased electrode NEC 2020 Section 250.52(A)(3)
At least 20 ft of bare or zinc galvanized steel reinforcing bars not less than 1/2 in. in diameter, or bare copper conductor not smaller than 4 AWG, encased by at least 2 in. of concrete.
Supplemental electrode exception NEC 2020 Section 250.53(A)(2) Exception
A supplemental electrode is not required where a single rod, pipe, or plate electrode has a resistance to earth of 25 ohms or less.
Continuity of the grounded conductor NEC 2020 Section 200.2(B)
The grounded conductor must maintain its own continuity and shall not depend on a connection to a metallic enclosure, raceway, or cable armor.
Electrically connected (grounded conductors) NEC 2020 Section 200.3
Making a direct electrical connection capable of carrying current, as distinguished from induced currents; premises grounded conductors must be so connected to the supply system grounded conductor for a common, continuous grounded system.
Conductor to be grounded, single-phase 3-wire system NEC 2020 Section 250.26
On a grounded AC premises single-phase, 3-wire system, the conductor to be grounded is the neutral conductor.
System bonding jumper screw identification NEC 2020 Section 250.28(B)
Where a main or system bonding jumper is a screw only, the screw must be identified with a green finish visible with the screw installed.
Type S fuse adapter NEC 2020 Section 240.54(C)
An adapter designed so that once inserted in a fuseholder it cannot be removed, preventing tampering and maintaining proper overcurrent protection.
Nominal system voltages for load calculations NEC 2020 Section 220.5(A)
For calculating branch-circuit and feeder loads the recognized voltages are 120, 120/240, 208Y/120, 240, 347, 480Y/277, 480, 600Y/347, and 600 volts ('277/480' is not a recognized designation).
Building disconnecting means (feeder supply) NEC 2020 Section 225.33(A)
The disconnecting means for each supply shall consist of not more than six switches or six circuit breakers in a single enclosure, a group of separate enclosures, or in/on a switchboard or switchgear, with no more than six disconnects per supply grouped in any one location.
Crane working space NEC 2020 Section 610.57
The working space in the direction of access to live parts likely to require examination, adjustment, servicing, or maintenance while energized shall be a minimum of 750 mm (2½ ft), and enclosed control cabinet doors must open at least 90 degrees or be removable.
Neon tubing spacing NEC 2020 Section 600.41(C)
Field-installed skeleton tubing must maintain a spacing of not less than 6 mm (1/4 in.) between the neon tubing and the nearest surface other than its support.
Resistance Basic electrical theory — resistance
The property of a circuit that opposes the flow of current, measured in ohms, and which converts electrical energy to heat.
Hertz Basic electrical theory — alternating current
The unit of AC frequency, equal to the number of complete cycles per second; U.S. standard power frequency is 60 Hz.
Watt Basic electrical theory — units of measurement
The unit of electrical power, the rate at which electrical energy is used or produced.

Formulas to Know

Ohm's law (all forms)E = I × R; I = E ÷ R; R = E ÷ I (e.g., 8 A × 15 Ω = 120 V; 240 V ÷ 48 Ω = 5 A; 12 V ÷ 0.5 A = 24 Ω)
Power in a DC/single-phase resistive circuitP = E × I; I = P ÷ E; P = I² × R (e.g., 120 V × 12.5 A = 1,500 W; 1,800 W ÷ 120 V = 15 A; 4² × 25 Ω = 400 W)
Three-phase powerP = √3 × V × I × cos θ, where V is line voltage and cos θ is the power factor
Apparent power from real power and power factorS (kVA) = P (kW) ÷ PF (e.g., 200 kW ÷ 0.8 = 250 kVA)
Inductive reactanceXL = 2πfL (f = frequency, L = inductance)
Series-parallel total resistanceR_total = R_series + R_parallel; for two resistors in parallel R_p = (R_a × R_b) ÷ (R_a + R_b); for three or more 1/R_p = 1/R1 + 1/R2 + 1/R3; for n equal resistors R_p = R ÷ n
Branch current in a parallel bankFind total R, then I_total = E ÷ R_total; voltage across the bank = I_total × R_parallel; branch current = V_bank ÷ R_branch
Unknown parallel resistance from totalR_parallel = R_total − R_series; then 1/R_unknown = 1/R_parallel − 1/R_known (e.g., 12 Ω − 4 Ω = 8 Ω; 1/8 − 1/24 = 1/12 → R3 = 12 Ω)
Room air conditioner on a shared branch circuitMax marked rating = 50% of branch-circuit rating where lighting outlets, other appliances, or general-use receptacles are on the same circuit (50% × 20 A = 10 A)
Single continuous-duty motor conductor sizingConductor ampacity ≥ 125% of motor full-load current rating
Cable bend radiusType MC interlocked armor/corrugated sheath: radius = 7 × external diameter (7 × 1 in. = 7 in.); Type MI over 19 mm to 25 mm diameter: radius = 10 × external diameter
Unit conversions1 hp = 746 W; kilo = 1,000 (2,400 W = 2.4 kW; 1 kVA = 1,000 VA); milli = 1/1,000 (350 mA = 0.35 A)