Exam Cheat Sheet · Quick Reference
Maryland Master Electrician
Maryland · PSI Services Contractor
Maryland State Portion 90 questions
Key Distinctions
An overload is operation of equipment in excess of normal, full-load rating that causes damage or dangerous overheating when it persists, while a fault such as a short circuit or ground fault is expressly not an overload (both are overcurrent conditions, but they require different protective approaches).
NEC 2020 Article 100 — Definitions, OverloadA surge arrester limits surge voltages by discharging or bypassing surge current and prevents continued flow of follow current while remaining capable of repeating the function, whereas an SPD limits transient voltages by diverting or limiting surge current.
NEC 2020 Article 100 — Definitions, Surge ArresterInterrupting rating is the highest current at rated voltage a device is identified to interrupt under standard test conditions; short-circuit current rating is the prospective symmetrical fault current an apparatus can be connected to without damage, and available fault current is the largest current deliverable at a point during a short circuit.
NEC 2020 Article 100 — Definitions, Interrupting RatingPer 430.6(A)(1) the NEC full-load current tables (e.g., Table 430.250 for three-phase) are used to size branch-circuit conductors, while the nameplate current is used only for sizing separate motor overload protection per 430.6(A)(2).
NEC 2020 Section 430.6(A)(1)Continuous-duty motors use 125% of the table full-load current, while motors in other than continuous duty (short-time, intermittent, periodic, varying) use the Table 430.22(E) percentages — 140% of nameplate current for intermittent-duty elevator service with a continuous-rated motor.
NEC 2020 Informative Annex D, Example D9; Table 430.22(E)For primary currents less than 9 amperes, the primary-only method permits a maximum of 167%, while the primary-and-secondary method permits a maximum primary overcurrent protection of 250% per Table 450.3(B).
NEC 2020 Table 450.3(B)The standard tables apply only to concentric stranded conductors, while the companion (A) tables must be used for compact stranded conductors and are based on Chapter 9, Table 5A rather than Table 5.
NEC 2020 Informative Annex C, Table C.1 Note 1EMT must be fastened within 900 mm (3 ft) of each box, cabinet, conduit body or other termination (and at intervals not over 10 ft), while FMC (and AC cable) must be secured within 300 mm (12 in.) of each termination.
NEC 2020 Section 358.30(A)Article 706 governs ESS with a capacity greater than 3.6 MJ (1 kWh); systems of 3.6 MJ (1 kWh) or less are governed by Article 480.
NEC 2020 Section 706.1A covered conductor is encased in material whose composition or thickness is NOT recognized by the Code as electrical insulation, so it cannot be treated as insulated, while an insulated conductor is encased in material that IS recognized as electrical insulation.
NEC 2020 Article 100 — Definitions, Conductor Covered and Conductor InsulatedA switchboard is generally accessible from the rear as well as the front and is not intended for installation in cabinets, while a panelboard is accessible only from the front and is designed for assembly in a cabinet.
NEC 2020 Article 100 — Definitions, Switchboard and PanelboardSwitchgear is completely enclosed on all sides and top with sheet metal (except ventilating openings and inspection windows) and contains primary power circuit switching or interrupting devices with buses and connections, unlike a switchboard (open to the rear) or a motor control center (principally motor control units).
NEC 2020 Article 100 — Definitions, SwitchgearOn grounded circuits it is the voltage between the given conductor and the grounded point or conductor, while on ungrounded circuits it is the greatest voltage between the given conductor and any other conductor of the circuit.
NEC 2020 Article 100 — Definitions, Voltage to GroundAn isolating switch has no interrupting rating and is intended to be operated only after the circuit has been opened by other means, while a general-use switch is rated in amperes and capable of interrupting its rated current (a motor-circuit switch is rated in horsepower).
NEC 2020 Article 100 — Definitions, Switch IsolatingKey Terms
Formulas to Know
(continuous load × 125%) + noncontinuous load; e.g., (100 A × 1.25) + 30 A = 155 A125% of the largest motor FLC + sum of the FLCs of the other motors; e.g., (1.25 × 15.2) + 15.2 + 15.2 = 49.4 Anameplate current × 140%; e.g., 52 A × 1.40 = 72.8 A (continuous duty instead uses 125% per 430.22(A))ampacity ≥ 115% of generator nameplate current; 80 A × 1.15 = 92 A; 200 A × 1.15 = 230 AMax = 250% of motor FLC (single-phase), rounded up to the next standard size if the motor will not start: 50 A × 2.5 = 125 A → next standard size 150 A; absolute ceiling where needed for starting = 400% of FLC for FLC ≤ 100 A: 60 A × 4.00 = 240 ASeparate overload device ≤ 125% × nameplate FLC for motors with a marked service factor ≥ 1.15 or marked temperature rise ≤ 40°C; ≤ 115% × nameplate FLC for all other motors. These are maximums, not a range: 30 A → 37.5 A max (service factor 1.15) or 34.5 A max (other motors)(floor area × 3 VA/sq ft) + (1500 VA × number of 2-wire small-appliance circuits) + (1500 VA × number of laundry circuits); e.g., 2000 sq ft: 6000 + 3000 + 1500 = 10,500 VA; per-unit totals × number of units before demand factors (8100 × 4 = 32,400 VA); dwelling units only: a retail store uses the Table 220.12 unit load, 1.9 VA/sq ft, plus 180 VA per receptacle outletMax fill = 40% for 3 or more conductors; conduit area = π r², conductor area = π r² each; fill % = total conductor area ÷ conduit area (e.g., 0.0368 in² ÷ 0.7854 in² ≈ 4.7% < 40%)R(parallel of two) = (R1 × R2)/(R1 + R2) or 1/Rp = Σ1/R; R_total = series R + Rp; I = E / R_total; branch current = (I × Rp) ÷ R_branch (e.g., 36 V ÷ 12 Ω = 3 A; 12 V ÷ 24 Ω = 0.5 A)Box fill: 2.25 in.³ (36.9 cm³) per 12 AWG conductor; straight pull box length ≥ 8 × the metric designator (trade size) of the largest raceway for conductors 4 AWG or larger