Exam Cheat Sheet · Quick Reference
Maryland Master Electrician
Maryland · PSI Services Contractor
Maryland State Portion 90 questions
Key Distinctions
An overload is excess current beyond normal full-load rating that causes damage only when persistent; a short circuit or ground fault is NOT classified as an overload per NEC Article 100.
NEC, Article 100 — Definition of OverloadTable values from NEC 430.250 are used to size branch-circuit conductors; the nameplate current is used only for sizing separate motor overload protection per 430.6(A)(2).
NEC, Section 430.6(A)(1)EMT must be secured within 900 mm (3 ft) of each termination, while FMC must be secured within 300 mm (12 in.) of each termination.
NEC, Section 358.30(A)Primary-only protection allows a maximum of 167% for primary currents less than 9 amperes, while the primary-and-secondary method allows up to 250% for the same current range.
NEC, Table 450.3(B)Standard Annex C tables apply only to concentric stranded conductors; the (A)-suffix tables must be used for compact stranded conductors.
NEC, Informative Annex C, Table C.1 Note 1Article 706 governs energy storage systems with a capacity greater than 3.6 MJ (1 kWh); systems at or below that threshold fall under Article 480.
NEC Handbook, Section 706.1For a straight pull, the box length must be at least 8 times the trade size of the largest raceway; angle pulls use a different multiplier (6×) plus the sum of other raceways per NEC 314.28(A).
NEC 314.28(A)(1)Conductors 6 AWG or smaller must have a continuous white or gray outer finish; larger conductors may use white or gray markings at terminations rather than a continuous finish.
NEC, Section 200.6(A)A one-family dwelling requires a minimum 100-ampere, 3-wire service disconnect, while an installation with no more than two 2-wire branch circuits requires only a 30-ampere disconnect.
NEC, Section 230.79(C)A continuous load is one where maximum current is expected to persist for 3 hours or more, requiring conductors/devices sized at 125% of that load; noncontinuous loads do not carry this 125% requirement.
NEC Handbook, Article 100 — DefinitionsThe grounding electrode conductor to a rod, pipe, or plate need not exceed 6 AWG copper, while a concrete-encased electrode requires at least 20 ft of reinforcing bar to qualify.
NEC, Section 250.66(A)A Class A GFCI trips at 6 mA or higher to protect persons from electrocution, while equipment ground-fault protection per 230.95 is required on service disconnects rated 1000 A or more on 480Y/277V solidly grounded wye systems to protect equipment.
NEC Handbook, Article 100 — Definitions, Ground-Fault Circuit Interrupter (GFCI)Key Terms
Formulas to Know
Required Ampacity ≥ Noncontinuous Load (A) + 1.25 × Continuous Load (A)General Load = 100% × first 10,000 VA + 40% × (Total Listed Load VA − 10,000 VA)Conductor Ampacity ≥ 1.25 × FLC (from NEC Table 430.250 for 3-phase, or 430.248 for single-phase)Max Device Rating = FLC (table value) × Multiplier from NEC Table 430.52 (e.g., 250% for inverse-time CB, 300% for dual-element fuse)Max Overload Setting = Nameplate FLA × 1.25 (motors with SF ≥ 1.15 or temp rise ≤ 40°C) or × 1.15 (all other motors)Corrected Ampacity = Table Ampacity × Temperature Correction Factor (NEC Table 310.15(B)(1) or 310.15(B)(2))Adjusted Ampacity = Table Ampacity × Bundling Adjustment Factor (NEC Table 310.15(C)(1), e.g., 0.80 for 4–6 conductors)Sum of cable/conductor areas ≤ Fill % × Conduit Internal Area (40% for 3+ conductors, 53% for 2 conductors, 31% for 1 conductor; NEC Chapter 9, Table 1)Max Primary OCPD = 250% × Primary FLA (NEC Table 450.3(B))Box Length ≥ 8 × Trade Size of Largest Raceway (NEC 314.28(A)(1))