Maryland State Portion 40 questions
Key Distinctions
A same-room shutoff must be within 6 feet of the appliance and upstream of the union, connector or quick-disconnect it serves, while a manifold-mounted shutoff may be up to 50 feet from the appliance served but must be readily accessible and permanently identified.
IFGC 2018 Section 409.5.1Pipe is a rigid conduit of iron, steel, copper, copper-alloy or plastic, whereas tubing is a semirigid conduit of copper, copper-alloy, aluminum, plastic or steel (aluminum appears only under tubing).
IFGC 2018 Section 202 (Piping definition)A flared joint is a metal-to-metal compression joint where a conical spread on the tube end is compressed by a flare nut against a mating flare, while a flanged joint is made by bolting together a pair of flanged ends.
IFGC 2018 Section 202 (Joint, Flared definition)A mechanical joint is a gas-tight joint made by a positive-holding mechanical construction (press-connect, flanged, threaded, flared or compression), while a plastic heat fusion joint is made in thermoplastic piping by heating the parts enough to fuse them when pressed together.
IFGC 2018 Section 202 (Joint, Mechanical definition)Per IFGC 101.2.2 the code covers natural gas piping operating at 125 psig or less, but LP-gas piping only at 20 psig or less, except as provided in Section 402.7.
IFGC 2018 Section 101.2.2Combustion air is the air necessary for complete combustion of a fuel, including theoretical air and excess air, while dilution air is air introduced into a draft hood and mixed with the flue gases.
IFGC 2018 Chapter 2 DefinitionsUnderground piping systems must be at least 12 inches below grade generally, but individual outdoor appliance lines may be installed at 8 inches.
IFGC 2018 Section 404.12All four types share the same outside diameter for a given nominal size and differ only in wall thickness (and therefore inside diameter); Type K, available in hard and soft temper, is the type recommended for underground water supply service.
Mathematics for Plumbers and Pipefitters (8th ed.), Page 42 (Copper Tubing)Butt-weld fittings require an extra ⅛ inch weld-gap separation added to the fitting allowance (subtracted from end-to-end pipe length), while socket-weld fittings require withdrawing the pipe 1/16 inch from full socket depth to allow for expansion during welding.
Mathematics for Plumbers and Pipefitters (8th ed.), Page 54Long-radius 90° elbow allowance is 1½ × pipe size, short-radius 90° elbow is 1 × pipe size (same as a butt-weld tee), and a 45° elbow is ⅝ × pipe size.
Mathematics for Plumbers and Pipefitters (8th ed.), Page 54Multiply the offset by the cosecant to find the diagonal (travel), but multiply the offset by the cotangent to find the run/setback; the tangent is used to find the offset from the run.
Mathematics for Plumbers and Pipefitters (8th ed.), Pages 94-96, Unit 25A No-Hub joint uses a gasket enclosed by a stainless steel shield secured with a stainless steel retaining clamp, while hubbed connections use lead and oakum or compression gaskets.
Mathematics for Plumbers and Pipefitters (8th ed.), Page 105 (Unit 27, Cast Iron Pipe)End-to-end is always shorter than center-to-center because the pipe threads into the fitting rather than reaching its center; end-to-end equals center-to-center minus the total fitting allowance.
Mathematics for Plumbers and Pipefitters (8th ed.), Pages 39-41 (Allowance for Threaded Fittings)Key Terms
Formulas to Know
cfh = total BTU/h input ÷ average BTU heating value per cubic foot (e.g., 150,000 ÷ 1,000 = 150 cfh)Spare cfh = table capacity for that size and length [Table 402.4(2), <2 psi, 0.5 in. w.c. drop, SG 0.60] − appliance demand cfh (e.g., 170 − 60 = 110; 137 − 80 = 57; 44 − 40 = 4)Test pressure = 1½ × proposed maximum working pressure, but never less than 3 psig; test duration ≥ 10 minutes for systems under 10 cubic feet or in a single-family dwellingL = 1.3n, where L is additional feet of tubing and n is the number of fittings/bends beyond the four 90° bends and two end fittings already in the tableEnd-to-end = center-to-center − total fitting allowance, where each fitting allowance = center-to-face − thread-in (e.g., 24 − [2(1⅛) − 2(½)] = 24 − 1¼ = 22¾ in.)Long-radius 90° butt-weld ell = 1½ × pipe size; short-radius 90° ell and butt-weld tee = 1 × pipe size; 45° butt-weld ell = ⅝ × pipe size; add ⅛ in. per butt weld for penetration/gap (e.g., 4-in. 45° ell: 4 × ⅝ = 2½ + ⅛ = 2⅝ in.); socket-weld: withdraw pipe 1/16 in. from full socket depth45°: diagonal = 1.414 × offset, offset = 0.707 × diagonal; 30°: diagonal = 2.000 × offset, run = 1.732 × offset; 60°: diagonal = 1.155 × offset, run = 0.5774 × offset, rise = 0.577 × offsetTrue offset = √(offset² + rise²) (e.g., √(12² + 9²) = 15 in.), then diagonal = true offset × the fitting-angle constant; for 45° parallel offsets, difference in length between the two diagonals = 0.414 × spreadStandard method: required volume = (total Btu/h ÷ 1,000) × 50 cu ft (e.g., 180,000 Btu/h → 9,000 cu ft); combination method: outdoor opening reduction factor = 1 − (available indoor volume ÷ required volume), openings sized at that fraction of the full Section 304.6 sizeDrop = grade × run (¼ in./ft × 40 ft = 10 in. = 0.833 ft, so high end = 95.00 + 0.833 = 95.83 ft); percent grade: drop = (percent × run) ÷ 100 (1% × 60 ft = 0.60 ft); grade = drop ÷ run (5 in. ÷ 22 ft = 0.227 in./ft ≈ 7/32 in./ft)