Exam Cheat Sheet · Quick Reference
Mississippi Irrigation Systems
Mississippi · PSI Services Contractor
Mississippi State Portion 40 questions
Key Distinctions
For the same 4-mph wind condition triangular spacing uses 55% of the throw diameter while square spacing uses 50%, so the wider triangular layout needs fewer heads (the reference's rectilinear example required two more heads with square spacing).
Irrigation Design Manual, Chapter 18 — Triangular Spacing in Square and Rectilinear Spaces sectionAn AVB must be installed on each circuit (six circuits = six AVBs), whereas PVB and DCVA devices typically require only one unit per project.
Simplified Irrigation Design, Backflow Prevention, Chapter 16AVBs and PVBs seal tightly only in back-siphonage situations and are not effective against back pressure; a DCVA (non-toxic water) or RPP is used where back pressure may occur, such as from a booster pump.
Simplified Irrigation Design, Chapter 16 (Backflow Prevention)A DCVA may be installed below ground in a valve box provided the assembly has good drainage, while AVBs and PVBs must be installed 12 in above the highest sprinkler head and are not described for below-ground installation.
Simplified Irrigation Design, Backflow Prevention, Chapter 16An HCVB needs a minimum of 6 in (152 mm) above grade, whereas AVBs, PVBs and RPPs carry a 12-in requirement.
Simplified Irrigation Design, Backflow Prevention, Chapter 16Spray heads apply about 1 to 2 in/hr while rotary heads apply 0.07 to 1.46 in/hr, so mixing the two families in one zone underwaters some areas and overwaters others.
Irrigation Reference, Chapter 5 — Matched PrecipitationAt the same nominal size only the outside diameter is identical between the two schedules; inside diameter and wall thickness change.
Simplified Irrigation Design, Using Plastic Pipe, Chapter 17D-2241 governs PVC pressure-rated pipe, while D-1785 covers PVC schedule-rated pipe and D-2239 covers polyethylene (PE) pipe.
Simplified Irrigation Design, Chapter 17 (Using Plastic Pipe)SDR (Standard Dimension Ratio, SDR-PR) is the constant wall-thickness-to-outside-diameter ratio of PVC pressure-rated pipe; SIDR applies to polyethylene pipe, not PVC pressure-rated pipe.
Simplified Irrigation Design, Chapter 17 (Using Plastic Pipe)At 25 gpm the globe configuration loses 6 psi while the angle configuration loses 4.5 psi.
Simplified Irrigation Design, Selecting Valves, Chapter 11Solid-state controllers are accurate to within 1 minute (and hold their program on battery 3 to 9 hours during a power outage), while electromechanical controllers may vary several minutes from the programmed run time.
Simplified Irrigation Design, Controllers, Chapter 15 — Types of Controllers sectionWhere the two conflict, the courts have adjudged the technical specifications to have greater importance than the working drawings.
Irrigation Reference, Chapter 27 — Working Drawings and SpecificationsRectilinear patterns are defined by the dimensions of the area covered (e.g., 3 ft × 12 ft, 9 ft × 18 ft), while circular patterns are defined by radius of throw, arc and trajectory.
Irrigation Design Manual, Chapter 2 — Sprinkler Head Patterns sectionKey Terms
Formulas to Know
PR = (96.3 × total GPM of all heads in the area) ÷ total square feet of area covered; 96.3 is the U.S.-customary conversion constant (60 is the metric constant for L/min and m² to mm/hr)Working pressure = static pressure − friction loss; e.g., 20 gpm in 100 ft of 1¼-in Class 200 PVC loses 1.5 psi/100 ft: 51.66 − 1.5 = 50.16 psi, and 43 − 1.5 = 41.5 psi1 ft of elevation rise or fall = 0.433 psi (0.03 kg/cm²) change, so 5 ft × 0.433 = 2.2 psi loss; conversely 1 psi = 2.31 ft of head (1.00 ÷ 0.433)Total surge pressure = pressure rise from nomograph + working water pressure; e.g., 35 psi + 50 psi = 85 psi (acceptable, since even Class 160 pipe holds 160 psi)Size the entire loop for one-half the flow of the largest valve circuit (40 gpm ÷ 2 = 20 gpm) because flow splits along both legsUse one-half the gpm and one-half the total loop length: 20 gpm/810 ft → 10 gpm through 405 ft; 30 gpm/600 ft → 15 gpm through 300 ft (built-in safety factor ≈ 10%)First section flow = number of downstream heads × gpm per head (13 heads × 2 gpm = 26 gpm; 6 heads × 4 gpm = 24 gpm); pipe size decreases at each successive headSpacing = throw diameter × wind factor (no wind 60%, 4-mph 55%, 8-mph 50%); 0.55 × 30 ft = 16.5 ft; 16-ft radius = 32-ft diameter × 0.50 = 16.0 ftMax minutes per cycle = soil permeability (in/hr) ÷ (PR in/hr ÷ 60): 0.2 ÷ 0.006 ≈ 33.3 → 34 min; cycles per week = total weekly minutes ÷ max cycle minutes: 334 ÷ 34 ≈ 9.8 → 10Do not exceed 75% of the meter's maximum safe flow: 75% × 30 gpm = 22.5 gpm (85.16 L/min) for a ¾-in meter