Key Distinctions
Branch-circuit conductors must be at least 125% of the motor's table full-load current, while the disconnect must be rated at least 115% of that same full-load current.
NEC 2023 Table 430.248, Section 430.22Table 430.248 gives full-load currents for single-phase AC motors, while Table 430.250 gives full-load currents for three-phase motors; per 430.6(A)(1) both are used instead of nameplate values for conductor, disconnect and OCPD sizing.
NEC 2023 Section 430.6(A)(1) and Table 430.248Overload protection per 430.32(A)(1) is based on the motor NAMEPLATE current, while conductor, feeder, disconnect and branch-circuit short-circuit/ground-fault sizing use the table FLC per 430.6(A)(1).
NEC 2023 Section 430.32(A)(1)For an AC squirrel cage (Design B) motor the time-delay fuse is rated at 175% of FLC while the inverse-time breaker is rated at a maximum of 250% of FLC; in both cases 430.52(C)(1) permits going to the next higher standard size of 240.6(A).
NEC 2023 Table 430.250, Table 430.52, Section 240.6(A)A 12 AWG THWN copper conductor has a Table 310.16 ampacity of 25 amperes at 30°C (75°C column), whereas the commonly cited 20 amperes is the maximum overcurrent protection allowed for 12 AWG, not its ampacity.
NEC 2023 Table 310.16Branch circuits supplying neon tubing installations shall not be rated in excess of 30 amperes, while all other sign and outline lighting branch circuits are limited to 20 amperes.
NEC 2023 Section 600.5(C)(1)For straight pulls the minimum length is 8 times the trade diameter of the largest raceway, while for angle pulls the minimum distance is 6 times the largest conduit trade diameter plus the sum of the trade diameters of the other conduits on the same wall.
NEC 2023 Section 314.28(A)(1)Flexible cord EGCs may be sized per 400.23/Table 400.4 (as small as 18 AWG copper for certain cord types), and per 250.122(E), where the largest circuit conductor is 10 AWG or smaller, the cord EGC shall not be smaller than 18 AWG copper and not smaller than the circuit conductors, instead of following Table 250.122, which otherwise requires a 14 AWG minimum.
NEC 2023 Section 400.23The general emergency power source duration shall in no case be less than 2 hours, while storage batteries and UPS supplying emergency illumination must maintain the load for a minimum of 1½ hours without voltage falling below 87½ percent of nominal.
NEC 2023 Section 700.12(C)Chapters 1 through 4 apply generally to all electrical installations, Chapters 5-7 apply to special occupancies, equipment or conditions and may supplement or modify Chapters 1 through 7, and Chapter 8 (communications systems) is not subject to Chapters 1-7 unless specifically referenced in Chapter 8.
NEC 2023 Section 90.3Where the main or system bonding jumper is a screw only, the screw must be identified with a GREEN finish visible with the screw installed — not red.
NEC 2023 Section 250.28(B)Interconnection cord between office furnishings shall not exceed 600 mm (2 ft), while a cord-and-plug connection for lighting equipment shall not exceed 2.7 m (9 ft).
NEC 2023 Section 605.5Key Terms
Formulas to Know
Table FLC (430.248 single-phase / 430.250 three-phase) × 125%; e.g., 52A × 1.25 = 65A for a 40 HP, 460V 3-phase motor, and 88A × 1.25 = 110A for a 30 HP, 208V 3-phase motor (select conductor from Table 310.16, 75°C column)125% of the largest motor FLC + 100% of all other motor FLCs; e.g., (34A × 125%) + 21A = 63.5A, and (52A × 1.25) + 34A = 99ATable FLC × 115%; e.g., 65A × 1.15 = 74.8A (50 HP, 460V) and 52A × 1.15 = 59.8A (40 HP, 460V)Nameplate full-load amperes × 125% (not table FLC); e.g., 82A × 1.25 = 102.5A and 26A × 1.25 = 32.5ATime-delay (dual-element) fuse = 175% of table FLC (52A × 1.75 = 91A → next standard 100A; 59.4A × 1.75 = 103.95A → 110A); inverse-time circuit breaker for Design B squirrel cage = 250% of FLC (34A × 2.5 = 85A → 90A; 30.8A × 2.5 = 77A → 80A); next higher standard size permitted per 430.52(C)(1)Branch circuit (210.19(A)(1)): noncontinuous load + 125% of the continuous load; feeder (215.4(A)(1)(a) / 2023: 215.2(A)(1)(a)): continuous load × 125%, e.g., 30A × 1.25 = 37.5A added to the motor portionI = kVA × 1,000 / (E × 1.732); e.g., 75,000 / (208 × 1.732) = 208A, and 150,000 / (480 × 1.732) = 180.4A (next standard OCPD per 240.6(A) = 200A)Ampacity not less than 115% of the generator nameplate current; e.g., 180.4A × 1.15 = 207.5A → 4/0 AWG copper THWN (230A at 75°C), since 3/0 AWG at 200A is insufficientStraight pull: length ≥ 8 × trade diameter of the largest raceway (8 × 3" = 24 in.); Angle pull: distance to opposite wall ≥ 6 × largest conduit trade diameter + sum of trade diameters of other conduits on the same wall (6 × 3" + 2" + 1½" = 21.5 in.)12 AWG = 2.25 cu in. and 14 AWG = 2.00 cu in. each for conductors; up to four equipment grounding conductors = one volume allowance based on the largest EGC; each device yoke = 2 × the volume of the largest conductor connected to it