Verified, not estimated. Every figure below is drawn from the official exam structure we maintain — question counts, passing standard and topic weighting. Practice questions are grounded in the source law with statute citations. We omit any figure we can't verify rather than guess at it.
Total questions
100
Passing score
70%
Exam time
360 min
Administered by
PSI Services Contractor
Format
Reference materials allowed

North Carolina State Portion 100 questions

Bonding and Grounding 10 Q · 10%
Systems and equipment requiring grounding and ground-fault protectionLocation of connection and required interconnectionsConductor identification and color codingBonding jumpersGrounding electrode conductorsEquipment grounding conductorsGrounding electrodesLow-voltage specificationsBonding conductor connectionsBonding/bonding gridTermination
Overcurrent Protection 9 Q · 9%
Location in circuitSizing requirementsCircuit breakersPlug and cartridge fusesEnclosures and locations
Wiring Methods and Terminations 10 Q · 10%
Permitted applications and usagesCharacteristicsConduit and wireway fillPermitted applications and usagesCharacteristicsProtection from damagePermitted usages and ampacity ratingsCharacteristicsMiscellaneousOutdoorsSwitchboards, panelboards, switches, and cabinetsSpecial conditions
Boxes and Fittings 8 Q · 8%
General informationSizing requirements
Service Entrance and Equipment 11 Q · 11%
Installation requirementsService equipmentGeneral sizing requirements
Motors and Control Wiring 7 Q · 7%
General informationBranch circuit and feeder ampacityOverload protectionShort-circuit and ground-fault protectionDisconnects/controllersSizeTypeLocationSeparation of conductors
Special Occupancies and Hazardous Locations 6 Q · 6%
Mobile homes and mobile home parksSwimming poolsUnderwater lighting fixtures
Load Calculations 11 Q · 11%
Branch circuitsTotal computed loadConductor ampacity requirementsLow-voltage
Appliances, Equipment, and Lighting 7 Q · 7%
Air conditionersResidential, commercial, and industrial equipmentLighting fixturesSpace heating equipment and boilersTransformers
General 3 Q · 3%
DefinitionsInstallation requirements
Laws, Rules, Basic Business Practices, and Practical Applications 18 Q · 18%
Electrical Contractors Licensing Law (General Statutes Chapter 87, Article 4)Board’s Rules for the Implementation of the Electrical Contractors Licensing Law (Title 21, North Carolina Administrative Code, Chapter 18B)NASCLA Contractors’ Guide to Business, Law and Project Management - North Carolina Electrical EditionLighting and Power Plans; Estimating and General KnowledgeNational Fire Alarm Code

Key Distinctions

EMT securing distance (NEC 358.30(A))vsFMC and AC cable securing distance

EMT must be secured within 900 mm (3 ft) of each box, cabinet, conduit body, or other termination (and at intervals not over 10 ft), whereas FMC and AC cable must be secured within 12 in. of a termination.

NEC 2020 Section 358.30(A)
Circuits that shall NOT be grounded (250.22)vsSystems permitted but not required to be grounded (250.21(A))

Grounding is prohibited for electric crane circuits operating over combustible fibers in Class III locations, while the systems listed in 250.21(A) are merely permitted — not required — to be grounded; by contrast a 3-phase, 4-wire wye system whose neutral is used as a circuit conductor must be grounded per 250.20(B)(2).

NEC 2020 Sections 250.22 and 250.21(A)
Supervised industrial installation feeders (240.91(B))vsGeneral conductor protection (240.4(C))

In supervised industrial installations with a device rated over 800 A, conductors may have an ampacity of not less than 95 percent of the device rating when the listed conditions are met, while outside Part VIII the conductor ampacity must be at least 100 percent of the device rating.

NEC 2020 Section 240.91(B)
Fountain luminairesvsFountain submersible pumps and other submersible equipment

Luminaires in a fountain shall not operate on supply circuits over 150 volts between conductors, while submersible pumps and other submersible equipment are permitted at 300 volts or less between conductors.

NEC 2020 Section 680.51(B)
Guest rooms/suites WITHOUT permanent cooking provisionsvsGuest units WITH permanent cooking provisions

Where service and maintenance are furnished by building management under continuous supervision, branch-circuit overcurrent devices for guest rooms without permanent cooking provisions may be accessible only to authorized management personnel, but units with permanent cooking provisions are not included in that allowance and the occupant must have ready access.

NEC 2020 Section 240.24(B)(2)
Edison-base fuses (240.51(B))vsType S fuses with adapters (240.52, 240.53, 240.54)

Edison-base fuses are permitted only as replacements in existing installations with no evidence of overfusing or tampering, whereas Edison-base fuseholders showing overfusing must be fitted with non-removable Type S adapters so only the correct Type S ampere classification (0–15 A, 16–20 A, 21–30 A) can be installed.

NEC 2020 Sections 240.51(B), 240.52, 240.53, and 240.54
Branch-circuit inverse time circuit breaker as motor controllervsInstantaneous-trip circuit breaker as motor controller

A branch-circuit inverse time circuit breaker rated in amperes is permitted as the controller for all motors (as is a molded case switch rated in amperes), while an instantaneous-trip breaker may be used only if adjustable and part of a listed combination motor controller.

NEC 2020 Section 430.83(A)(2)
Master alarm box (NFPA 72, 3.3.12.4)vsAuxiliary alarm box / publicly accessible alarm box

A master alarm box is publicly accessible AND can also be operated by remote initiating devices or an auxiliary alarm system, while an auxiliary alarm box can only be operated from remote devices or an auxiliary system and a publicly accessible alarm box houses only a manually operated transmitter.

NFPA 72 National Fire Alarm and Signaling Code, Chapter 3 — 3.3.12 Alarm Box (3.3.12.1, 3.3.12.4, 3.3.12.5)
Girder with top within 4 in. of ceilingvsGirder with top more than 4 in. from ceiling

If the top of the girder is within 4 in. (100 mm) of the ceiling it is treated as a beam and is a factor in the number and location of detectors; if more than 4 in. from the ceiling it is not a factor.

NFPA 72 National Fire Alarm and Signaling Code, Chapter 3 — 3.3.37.2 Girder
MediationvsCollaborative law

In mediation an independent third-party mediator facilitates dialogue while the parties themselves set the terms of any agreement; in collaborative law the parties negotiate through their own advocates (usually lawyers) with no neutral mediator or arbitrator involved.

NASCLA Contractors Guide, Contract Management chapter — Alternative Dispute Resolution section
Minimum conductor size generally (310.3(A))vsMinimum size permitted in parallel (310.10(G)(1))

For voltage ratings up to and including 2000 volts the minimum conductor size is 14 AWG copper or 12 AWG aluminum/copper-clad aluminum, but conductors may be connected in parallel only in sizes 1/0 AWG and larger.

NEC 2020 Section 310.3(A)
16 AWG copper control-circuit conductorsvs18 AWG copper conductors

16 AWG copper is limited to a 10-ampere device with continuous load not over 8 amperes (with listed/marked branch-circuit-rated protection or Class CC, J, or T fuses), while 5.6 amperes is the continuous-load limit that applies to 18 AWG copper.

NEC 2020 Section 240.4(D)(2)

Key Terms

Overcurrent NEC 2020 Article 100 — Definition of Overcurrent
Any current in excess of the rated current of equipment or the ampacity of a conductor, which may result from overload, short circuit, or ground fault.
Fault Current NEC 2020 Article 100 — Definition of Fault Current
The current delivered at a point on the system during a short-circuit condition.
Interrupting Rating NEC 2020 Article 100 — Definition of Interrupting Rating
The highest current at rated voltage that a device is identified to interrupt under standard test conditions; equipment intended to interrupt current at fault levels must have an interrupting rating at least equal to the current available at its line terminals, and 5,000 amperes is the assumed rating for an unmarked circuit breaker.
Series rating (240.86(C)) NEC 2020 Section 240.86(C)
A combination of a higher-rated upstream device with a lower-rated breaker that may not be used where motor circuits are connected between the two devices and the sum of motor full-load currents exceeds 1 percent of the interrupting rating of the lower-rated circuit breaker.
Available fault-current field marking (110.24(A)) NEC 2020 Section 110.24(A)
Service equipment other than dwelling units must be legibly field-marked with the available fault current and the date the calculation was performed, durable for the environment; the calculator's name is not required.
Main bonding jumper (250.24(C)) NEC 2020 Section 250.24(C)
The conductor that connects the grounded conductor(s) to each service disconnecting means enclosure, where the grounded conductor is routed with the ungrounded conductors to each service disconnecting means and connected to its grounded conductor terminal or bus.
System bonding jumper (250.30(A)(1)(a)) NEC 2020 Section 250.30(A)(1)(a)
For a separately derived system, the jumper that—when installed at the source—connects the grounded conductor to the supply-side bonding jumper and the normally non-current-carrying metal enclosure; the grounding electrode conductor must connect at the same point where the system bonding jumper connects.
Metal underground water pipe electrode (250.52(A)(1)) NEC 2020 Section 250.52(A)(1)
A metal underground water pipe qualifies as a grounding electrode only if in direct contact with the earth for 10 ft (3.0 m) or more.
Concrete-encased electrode (250.52(A)(3)) NEC 2020 Section 250.52(A)(3)
At least 20 ft (6.0 m) of bare or zinc galvanized steel reinforcing bars or rods not less than 1/2 in. in diameter, encased by at least 2 in. of concrete in direct contact with the earth.
Supplemental electrode exception (250.53(A)(2)) NEC 2020 Section 250.53(A)(2), Exception
A supplemental electrode is not required where a single rod, pipe, or plate electrode has a resistance to earth of 25 ohms or less.
6 AWG limit for rod/pipe/plate connections (250.66(A), 250.53(E)) NEC 2020 Section 250.66(A)
A grounding electrode conductor or bonding jumper connected solely to rod, pipe, or plate electrode(s) need not be larger than 6 AWG copper (or 4 AWG aluminum), including the portion of a bonding jumper that is the sole connection to a supplemental rod.
Grounding electrode conductor raceway bonding (250.64(E)(1)) NEC 2020 Section 250.64(E)(1)
Ferrous metal raceways, enclosures, and cable armor enclosing a grounding electrode conductor must be electrically continuous from the cabinet/equipment to the electrode and bonded at EACH end to the electrode or GEC, creating an electrically parallel path.
Prohibited grounding/bonding connection (250.8(B)) NEC 2020 Section 250.8(A) and (B)
Connection devices or fittings that depend solely on solder shall not be used for equipment grounding conductors, grounding electrode conductors, or bonding jumpers.
Working space width (110.26(A)(2)) NEC 2020 Section 110.26(A)(2)
For equipment at 1000 volts nominal or less, the working space width in front must be the width of the equipment or 30 in. (762 mm), whichever is greater, and must allow at least a 90-degree opening of doors or hinged panels.
Working space entrances (110.26(C)(2)) NEC 2020 Section 110.26(C)(2)
Equipment rated 1200 amperes or more and over 6 ft wide containing overcurrent, switching, or control devices requires an entrance/egress at each end of the working space, each not less than 24 in. wide and 6½ ft high.
Laundry branch circuit (210.11(C)(2)) NEC 2020 Section 210.11(C)(2)
At least one additional 20-ampere branch circuit must supply the required laundry receptacle outlet(s), and that circuit shall have no other outlets.
25-ft feeder tap rule (240.21(B)(2)) NEC 2020 Section 240.21(B)(2)
Feeder tap conductors not over 25 ft long must have an ampacity not less than one-third of the rating of the overcurrent device protecting the feeder conductors.
360-degree bend limit (358.26 / 358.24(B)) NEC 2020 Section 358.26
EMT bends are limited to 360 degrees between pull points; because a conduit body is a pull point, each section between pull points may contain up to 360 degrees of bends. Section number varies by edition: 358.26 in NEC 2017 and 2020, 358.24(B) in NEC 2023 and 2026.

Formulas to Know

Minimum feeder/branch conductor ampacity with continuous loadAmpacity ≥ noncontinuous load + (125% × continuous load); e.g., (100 A × 1.25) + 30 A = 155 A
Minimum feeder ampacity for several motors (430.24)125% × FLC of largest motor + sum of FLCs of remaining motors; e.g., (1.25 × 15.2) + 15.2 + 15.2 = 49.4 A
Motor overload protection maximum (430.32(A)(1))Separate overload device ≤ 125% × nameplate FLC for motors with a marked service factor ≥ 1.15 or marked temperature rise ≤ 40°C; ≤ 115% × nameplate FLC for all other motors. These are maximums, not a range: 30 A → 37.5 A max (service factor 1.15) or 34.5 A max (other motors)
Maximum inverse time circuit breaker for a motorTable 430.52: 250% × FLC (single-phase); if the motor will not start, next higher standard size, but never over 400% of FLC for FLC ≤100 A (50 A × 2.5 = 125 A → 150 A; 60 A × 4.0 = 240 A max)
Hermetic motor-compressor conductors and OCPDConductors ≥ 125% × RLA (28 A → 35 A; 30 A → 37.5 A; 20 A → 25 A); branch-circuit OCPD ≤ 175% × RLA (30 A → 52.5 A → 50 A standard size, no rounding up in the 2020 NEC; 20 A → 35 A), increased only if needed to start, to a maximum 225% of RLA
Generator output conductor ampacity (445.13)Ampacity ≥ 115% × generator nameplate current; 80 A × 1.15 = 92 A; 200 A × 1.15 = 230 A
Dwelling general load (Article 220)(Area in sq ft × 3 VA/sq ft) + (1,500 VA × number of small-appliance circuits) + (1,500 VA × number of laundry circuits); e.g., 2,000 sq ft → 6,000 + 3,000 + 1,500 = 10,500 VA; per-unit totals × number of units for multifamily before demand factors; dwelling units only: a retail store uses the Table 220.12 unit load, 1.9 VA/sq ft, plus 180 VA per receptacle outlet
Optional calculation methods for dwellingsOne dwelling unit (220.82(B)): general calculated load = 100% of first 10 kVA + 40% of the remainder; multifamily (Table 220.84): apply demand factor by number of units, e.g., 41% for 12–13 units meeting 220.84(A)
Transformer primary-only overcurrent protection (Table 450.3(B))For rated primary current of 9 A or more: device ≤ 125% × rated primary current (12 A × 1.25 = 15 A); next higher standard size allowed only when 125% does not land on a standard rating
Parallel conductor ampacity and grounded-conductor sizingTotal ampacity = ampacity per set × number of sets (350 kcmil Cu at 90°C = 350 A; 2 sets = 700 A); for grounded conductor sizing add parallel areas (2 × 350 = 700 kcmil → Table 250.102(C)(1) over 600 through 1,100 kcmil = 2/0 AWG Cu), and each parallel grounded conductor shall not be smaller than 1/0 AWG per 250.24(C)(2)