Exam Cheat Sheet · Quick Reference
North Carolina Limited Electrical Contractor (L)
North Carolina · PSI Services Contractor
North Carolina State Portion 100 questions
Key Distinctions
EMT must be fastened at intervals not exceeding 10 ft generally, but within 900 mm (3 ft) of each box, cabinet, conduit body, or other termination.
NEC, Section 358.30(A)NEC 250.22 absolutely prohibits grounding of certain circuits (e.g., crane circuits over combustible fibers in Class III locations), whereas 250.21(A) lists systems that are allowed to remain ungrounded but are not mandated to be so.
NEC Handbook, Sections 250.22 and 250.21(A)Under standard NEC rules a conductor's ampacity must equal or exceed 100% of the overcurrent device rating, but in supervised industrial installations with devices rated over 800 A and two specific conditions met, ampacity need only be 95% of the device rating.
NEC, Section 240.91(B)When the bonding jumper is at the source it connects the grounded conductor to the supply-side bonding jumper and the non-current-carrying metal enclosure; when it is at the first disconnect, the grounding electrode conductor must also be connected at that same disconnect point.
NEC, Section 250.30(A)(5)Feeder conductors must have ampacity equal to noncontinuous load plus 125% of the continuous load; noncontinuous loads are counted at 100% with no adder.
NEC, Section 215.2(A)(1)(a)A one-family dwelling requires a service disconnect rated at least 100 amperes 3-wire, while an installation with no more than two 2-wire branch circuits requires only 30 amperes.
NEC, Section 230.79(C)Edison-base fuseholders are permitted only as replacements in existing installations with no evidence of overfusing or tampering; once overfusing is found, Type S adapters must be installed so only correctly rated Type S fuses can be used and cannot be removed or shunted.
NEC, Sections 240.51(B), 240.52, 240.53, and 240.54Interrupting Rating is the highest current at rated voltage a device is identified to interrupt under standard test conditions, whereas Fault Current is the actual current delivered at a point on the system during a short-circuit condition.
NEC, Article 100 — Definition of Interrupting RatingWhen connected solely to a rod, pipe, or plate electrode the GEC need not exceed 6 AWG copper; the concrete-encased electrode rule requires at least 20 ft of rebar but does not cap the GEC size under 250.66(A).
NEC, Section 250.66(A)Luminaires in permanently installed fountains must operate on supply circuits of 150 volts or less between conductors, whereas submersible pumps and other submersible equipment may operate at up to 300 volts between conductors.
NEC 2020, Section 680.51(B)Tap conductors not over 25 ft long must have ampacity of at least one-third the feeder overcurrent device rating; the 10-ft tap rule requires a higher fraction (at least one-tenth is not applicable here — NEC 240.21(B)(2) specifies one-third for 25 ft taps).
NEC, Section 240.21(B)(2)Both rules set a floor of 1/0 AWG, but 310.10(G)(1) governs phase, neutral, or grounded circuit conductors connected in parallel, while 250.24(C)(2) specifically governs the grounded (neutral) service-entrance conductor run in parallel in each separate raceway or cable.
NEC 2020, Section 310.10(G)(1)Key Terms
Formulas to Know
Minimum ampacity = Noncontinuous load (A) + (Continuous load (A) × 1.25)Minimum conductor ampacity = OCD rating (A) × 0.95Tap conductor ampacity ≥ Feeder OCD rating (A) ÷ 3Max equipment rating = Branch-circuit rating (A) × 0.80Total load = 100% × first 10 kVA + 40% × (total listed load − 10 kVA)Demand load = Total calculated load (kVA) × Demand factor (from NEC Table 220.84, e.g., 0.41 for 12–13 units)Minimum bend radius = 5 × cable outside diameterRequired interrupting rating ≥ Available fault current at line terminals (A)