Key Distinctions
Per 90.3, Chapter 8 is NOT subject to the requirements of Chapters 1 through 7 except where those requirements are specifically referenced in Chapter 8.
NEC 2020 Section 90.3Per 90.5(C), informational notes are included for informational purposes only and are not enforceable as requirements of the Code.
NEC 2020 Section 90.5(C)AC cable (320.24) and NM/NMC cable (334.24) require the inner edge of any bend to be not less than five times the cable diameter, while interlocked-armor/corrugated-sheath MC cable (330.24(B)) requires not less than seven times the external diameter of the metallic sheath.
NEC 2020 Section 320.24220.82(B) takes 100% of the first 10 kVA plus 40% of the remainder, while 220.83(A) takes 100% of the first 8 kVA of existing and new load plus 40% of the remainder.
NEC 2020 Section 220.82(B)Table 430.52 allows a nontime-delay fuse at a maximum of 300% of motor full-load current, while a dual-element time-delay fuse is a maximum of 175% of full-load current (next higher standard size permitted by 430.52(C)(1) Exception No. 1).
NEC 2020 Table 430.52, NEC 430.52(C)(1), NEC 240.6(A)Branch-circuit conductors for a single continuous-duty motor must be not less than 125% of that motor's full-load current, while feeder conductors must be not less than 125% of the highest-rated motor plus the sum of the full-load currents of the other motors.
NEC 2020 Section 430.22Wye-start/delta-run controller-to-motor conductors must be not less than 72% of motor full-load current (58% × 1.25), whereas ordinary motor branch-circuit conductors must be not less than 125% of full-load current.
NEC 2020 Section 430.22(C)Conductors are sized at not less than 125% of the motor full-load current, while the separate overload device for a motor with a marked service factor of 1.15 or greater is selected to trip at not more than 125% of the motor nameplate full-load current (with incremental increases up to 140% possible under 430.32(C)).
NEC 2020 Section 430.22An instantaneous trip setting is a permitted arc energy reduction method, but temporarily adjusting the instantaneous trip setting to achieve arc energy reduction is not permitted; zone-selective interlocking, differential relaying, and energy-reducing maintenance switching are permitted.
NEC 2020 Section 240.87(B)250.32(A) requires a grounding electrode system and grounding electrode conductor to be installed where none exists, while 250.32(B)(1) requires an equipment grounding conductor run with the supply conductors and prohibits connecting any installed grounded conductor to the EGC or grounding electrode(s) at that structure.
NEC 2020 Section 250.32(A)Per Table 310.15(C)(1), 7 to 9 current-carrying conductors in a raceway or cable use 70 percent of the table ampacity, while 10 to 20 current-carrying conductors use 50 percent.
NEC 2020 Table 310.15(C)(1)Per the NASCLA Summary of Business Legal Structures table, a C corporation allows an unlimited number of shareholders with no personal liability and is taxed at the corporate level with a further tax on dividends (double taxation), while an S corporation is limited to 100 shareholders and uses pass-through taxation.
NASCLA Contractors Guide, North Carolina Electrical (14th ed.), Chapter 2 — Summary of Business Legal Structures tableKey Terms
Formulas to Know
General calculated load = 100% of the first 10 kVA + 40% of the remainder of the listed loads (not less than).Load = 100% of the first 8 kVA of existing and new load + 40% of the remainder.Conductors permitted at not less than 83% of the service rating; example: 200 A × 0.83 = 166 amperes (Table 310.12 gives 2/0 AWG copper for a 200 A dwelling service where no adjustment or correction factors are required).Adjusted ampacity = table ampacity × adjustment factor; 7–9 conductors = 70%, 10–20 conductors = 50%. Example: 12 CCCs of 10 AWG THHN at 90°C (40 A) → 40 × 0.50 = 20 amperes.Ambient = outdoor temperature + 33°C (60°F) adder; example: 40°C + 33°C = 73°C (104°F + 60°F = 164°F).Distance = 6 × trade size of largest raceway + sum of diameters of all other raceway entries on the same wall; example: (6 × 2) + 1 = 13 inches.Ampacity ≥ 125% of motor full-load current; example: 50 HP, 480 V, 3-phase = 65 A (Table 430.250) → 65 × 1.25 = 81.25 amperes.Ampacity ≥ (125% × highest-rated motor FLC) + sum of the full-load currents of the other motors; example: (1.25 × 65 A) + 40 A = 121.25 amperes.Nontime-delay fuse = 300% × FLC (65 A × 3.00 = 195 A → next standard size 200 A); dual-element time-delay fuse = 175% × FLC (65 A × 1.75 = 113.75 A → next higher standard size permitted).Creditable years = total primary experience hours ÷ 2,000 (2,000 hours = one creditable year); example: 11,000 ÷ 2,000 = 5.5 years.