Exam Cheat Sheet · Quick Reference
North Carolina Unlimited Electrical Contractor (U)
North Carolina · PSI Services Contractor
North Carolina State Portion 100 questions
Key Distinctions
Table 430.250 values are used to size branch-circuit conductors and overcurrent protection, while the nameplate current is used only for sizing separate motor overload protection per 430.6(A)(2).
NEC, Section 430.6(A)(1)Straight pull minimum length = 8× the largest raceway trade size; angle pull minimum distance = 6× the largest raceway trade size plus the sum of all other raceway entries on the same wall.
NEC 314.28(A)(1)Per Table 430.52, nontime delay fuses are rated up to 300% of motor FLA, while dual-element time-delay fuses are rated up to 175% of motor FLA for AC polyphase motors.
NEC Table 430.52Motors with a service factor of 1.15 or greater may have overload protection set up to 125% of nameplate FLA; motors without this rating use a lower threshold per 430.32(A)(1).
NEC 430.32(A)(1)In supervised industrial installations with overcurrent devices rated over 800 A, conductors need only be rated at 95% of the device rating; outside Part VIII, conductors must equal or exceed 100% of the device rating.
NEC, Section 240.91(B)EMT must be secured within 900 mm (3 ft) of each termination, while LFNC must be secured within 300 mm (12 in.) of each outlet box, junction box, cabinet, or fitting.
NEC, Section 358.30(A)Circuits listed in 250.21(A) are permitted but not required to be grounded, while circuits under 250.22 (e.g., crane circuits over combustible fibers in Class III locations) are expressly prohibited from being grounded.
NEC Handbook, Sections 250.22 and 250.21(A)Per 240.83(D), both markings permit use as a switch, but SWD applies to 120V and 277V fluorescent lighting circuits, while HID applies to high-intensity discharge lighting circuits.
NEC 240.83(D)Per 300.22(C)(1), Type MC cable without an overall nonmetallic covering is permitted in plenum spaces without a metal raceway, while NM, ENT, and PVC are not permitted unless enclosed in an approved metal raceway.
NEC 2020, Section 300.22(C)(1)Per 240.52, Edison-base fuseholders shall only be installed where they are made to accept Type S fuses via adapters, preventing overfusing by restricting installed fuse ratings.
NEC 240.52'Dead Front' means no live parts are exposed on the operating side, while 'Externally Operable' means the equipment can be operated without exposing the operator to contact with live parts at all.
NEC 2020, Article 100 (Definitions, Part I — Externally Operable)A structure supplied by not more than two 2-wire branch circuits requires a minimum 30-ampere disconnect, while a one-family dwelling requires a minimum 100-ampere, 3-wire disconnect.
NEC 225.39(B)Key Terms
Formulas to Know
Use NEC Table 430.250 FLA value (not nameplate) × 125% for continuous-duty motor branch-circuit conductor minimum ampacityMax fuse size = Motor FLA (from Table 430.250) × 300%Max fuse size = Motor FLA (from Table 430.250) × 175%; if result is not a standard size, round up to next standard size per 430.52(C)(1) Exception No. 1Max overload trip = Nameplate FLA × 125%Min conductor ampacity = Overcurrent device rating × 95%Min length = 8 × (trade size of largest raceway entering box)Min distance = (6 × largest raceway trade size) + (sum of all other raceway entry trade sizes on same wall)First 8 kVA of load × 100% + Remaining load × 40% (when no additional A/C or electric space heating is added)Each 12 AWG conductor = 2.25 in.³; each device yoke = double the volume of the largest conductor connected to it≤2 two-wire branch circuits → min 30 A disconnect; one-family dwelling → min 100 A, 3-wire disconnect; max 6 disconnects per supply grouping