Under the longest length method every section and branch is sized from the table row for the system's single longest run (e.g., a 12-ft branch is still sized on the 70-ft row), while under the branch length method each branch is sized using its own measured length from the meter (main length to the tee plus the branch length).
IFGC Section 402.4.1, Longest Length Method; Table 402.4(2), Schedule 40 Metallic Pipe (natural gas, 0.5 in. w.c. drop)Equation 4-1 applies to gas pressures less than 1½ psi (10.3 kPa); Equation 4-2 applies at 1½ psi and above.
IFGC 2024 Section 402.4The code covers natural gas piping systems operating at 125 psig or less, but LP-gas piping systems only at 20 psig (140 kPa gauge) or less, except as provided in Section 402.7.
IFGC 2024 Section 101.2.3 (2018 ed.: Section 101.2.2)Private garages require a minimum clearance of 6 feet above the floor (unless protected from vehicle impact and installed per 305.3), while public garages, repair garages, motor fuel-dispensing facilities and other areas frequented by motor vehicles require not less than 8 feet above the floor.
IFGC 2024 Section 305.5The appliance itself must be 6 feet above a private garage floor, whereas the source of ignition must be elevated not less than 18 inches above the floor in hazardous locations and public, private, repair, parking garages and motor fuel-dispensing facilities.
IFGC 2024 Section 305.3Horizontal ducts require each opening to have not less than 1 square inch of free area per 2,000 Btu/h of total input, double the 1 square inch per 4,000 Btu/h required for vertical ducts or direct communication.
IFGC 2024 Section 304.6.1The Standard Method sets a minimum room volume of 50 cubic feet per 1,000 Btu/h of appliance input, while combining-space openings are sized at 1 square inch of free area per 1,000 Btu/h of total input but never less than 100 square inches each.
IFGC 2024 Section 304.5.1Both operate at positive vent static pressure, but Category III has a vent gas temperature that avoids excessive condensate production while Category IV produces excessive condensate; Categories I and II operate at nonpositive vent static pressure.
IFGC 2024 Section 202Both are Schedule 40 metallic pipe tables for natural gas at less than 2 psi inlet, but Table 402.4(1) is based on a 0.3 in. w.c. pressure drop and Table 402.4(2) on a 0.5 in. w.c. pressure drop, giving different capacities for the same size and length.
IFGC 2024 Table 402.4(1)A 2A extinguisher is required for each 3,000 square feet of protected building area with travel distance not exceeding 100 feet, whereas a 10B extinguisher must be within 50 feet of wherever more than 5 gallons of flammable/combustible liquid or 5 pounds of flammable gas is in use.
OSHA 1926 CFR 29, §1926.150(c)(1)(i), Page 177Subcontractors share joint responsibility for their own portion of the work, but in no case may the prime contractor be relieved of overall responsibility for compliance for all work performed under the contract.
OSHA 1926 CFR 29, §1926.16, Page 29A written plan is normally required, but employers with 10 or fewer employees may communicate the plan orally and need not maintain a written plan.
OSHA 1926 CFR 29, §1926.35(e)(3), Page 33Key Terms
Formulas to Know
cfh = total Btu/h ÷ 1,000; e.g., 100,000 + 40,000 + 65,000 + 35,000 = 240,000 Btu/h ÷ 1,000 = 240 cfhSection load = sum of the Btu/h of all outlets downstream of that point ÷ 1,000; past the last tee the section carries only the last appliance (e.g., 40,000 ÷ 1,000 = 40 cfh)Spare cfh = table capacity at that size and length − appliance demand; e.g., 247 − 35 = 212 cfh, 322 − 150 = 172 cfh, 452 − 340 = 112 cfhSize every section and branch from the row for the system's longest run measured meter-to-farthest-outlet, not the branch's own length (e.g., a 12-ft branch is read on the 70-ft row)Branch length = main length from meter to its tee + branch length (e.g., 15 + 5 = 20 ft; 30 + 20 + 15 = 65 ft → 70-ft row; 30 + 12 = 42 ft → 50-ft row); read the next table row equal to or greater than that lengthCompare each outlet's length from the meter (e.g., 23 ft, 55 ft, 45 ft); the longest (55 ft) is the most remote and sizes the mains feeding it, read on the next row up (60 ft)At the governing length row, choose the smallest nominal size whose capacity ≥ demand (e.g., 100 ft, 0.5 in. w.c.: 195 and 400 cfh are insufficient for 500 cfh, so 1-1/2 in. at 600 cfh is the minimum)L = 1.3n, where L is additional tubing length in feet and n is the number of fittings or bends beyond the standard four 90-degree bends and two end fittings; e.g., 6 bends − 4 standard = 2, L = 1.3 × 2 = 2.6 ftDuration = ½ hour per 500 cubic feet of pipe volume or fraction thereof; 1,200 ÷ 500 = 2.4 → 3 increments × 0.5 hr = 1.5 hoursStandard Method indoor volume = 50 cu ft per 1,000 Btu/h input; combining-space openings = 1 sq in per 1,000 Btu/h but not less than 100 sq in each; outdoor horizontal ducts = 1 sq in per 2,000 Btu/h; vertical ducts/direct = 1 sq in per 4,000 Btu/h