Oklahoma State Portion 80 questions

General Knowledge 4 Q · 5%
Purpose and scope of the NEC (practical safeguarding of persons and property)NEC code arrangement and chapter organizationMandatory versus permissive rules and explanatory material (shall/shall not vs. shall be permitted)Authority having jurisdiction (AHJ) enforcement and special permissionCommon field terms versus official NEC terminologyElectrical schematic and wiring diagram symbolsOhm's Law formulas relating voltage, current, resistance, and power (E, I, R, P)
General Electrical Knowledge 12 Q · 15%
Ohm's Law and power formulas (P, E, I, R relationships)Series, parallel, and combination circuit calculationsVoltage drop calculations for single-phase and three-phase circuitsConductor ampacity tables and temperature rating selectionAmpacity correction and adjustment factors (ambient temperature and conductor bundling)Electrical formulas for AC/DC amperes, kilowatts, kVA, and horsepowerTransformer calculations (primary/secondary amperes, kVA sizing, turns ratio)NEC branch-circuit and feeder load calculations including demand factors
Electrical Installation Requirements 10 Q · 12%
Conductor types, insulation ratings, and ampacity tables (NM, MC, AC, MI, SE, USE, UF)Cable installation methods: securing, supporting, and bending radius requirementsProtection of cables and raceways against physical damage through framing membersUnderground installation requirements and minimum burial cover depthsOutlet, device, pull, and junction box sizing and fill calculationsReceptacle installation, grounding, and wet/damp location requirementsPanelboard, switchboard, and switchgear installation and working clearancesLuminaire and appliance installation requirements including disconnecting means and GFCI protection
Services, Feeders, and Branch Circuits 10 Q · 12%
Branch circuit ratings, conductor sizing, and overcurrent protection requirements (Articles 210, 215)Service entrance requirements: overhead and underground conductors, clearances, wiring methods, and service equipment (Article 230)Load calculations for dwelling units and non-dwelling occupancies using standard and optional methods (Article 220)Demand factors for lighting, appliances, cooking equipment, dryers, and receptacle loadsGFCI and AFCI protection requirements for branch circuits in dwelling and non-dwelling locationsVoltage drop calculations for single-phase and three-phase circuitsConductor ampacity tables, temperature correction factors, and adjustment factors for multiple conductorsService disconnecting means: location, rating, number, and emergency disconnect requirements
Overcurrent Protection 8 Q · 10%
Conductor overcurrent protection and standard ampere ratings (NEC 240.4 and 240.6)Location of overcurrent protective devices in circuits (tap rules: 10 ft, 25 ft, outside taps)Types and requirements for fuses: plug fuses, Type S, Edison-base, and cartridge fusesCircuit breaker requirements: marking, ratings, indicating, and application (voltage ratings, series ratings)Motor branch-circuit overcurrent protection: maximum rating or setting by device type (NEC 430.52)Ground-fault protection of equipment (NEC 240.13) and supplementary overcurrent protectionArc energy reduction requirements for high-ampere overcurrent devices (240.67 and 240.87)Short-circuit current calculations and panelboard short-circuit current ratings (NEC 408.6)
Grounding and Bonding 8 Q · 10%
Grounding electrode types, installation requirements, and the grounding electrode system (NEC 250.50–250.54)Grounding electrode conductor sizing, material, and installation (NEC 250.62–250.66, Table 250.66)Equipment grounding conductor types, sizing, and identification (NEC 250.118–250.122, Table 250.122)Main bonding jumper and system bonding jumper requirements and sizing (NEC 250.28, Table 250.102(C)(1))Bonding of piping systems, structural metal, and service equipment (NEC 250.92–250.104)Grounding of service-supplied AC systems and separately derived systems (NEC 250.24–250.30)Equipment grounding conductor connections at boxes, receptacles, and fixed equipment (NEC 250.130–250.148)Surge-protective device (SPD) and surge arrester grounding and bonding connections (NEC Article 242)
Conductors and Cables 8 Q · 10%
Conductor insulation type designations and application provisions (e.g., THHN, THWN, RHW, XHHW) including maximum operating temperatures and permitted locations (dry, damp, wet)Ampacity tables for conductors in raceways, cables, and free air (Tables 310.16 and 310.17) for copper and aluminum conductorsAmbient temperature correction factors and adjustment factors for more than three current-carrying conductorsMinimum conductor size, material requirements, and stranding rules for conductors rated up to 2000 voltsConductors in parallel: size restrictions, matching requirements, and installation conditionsSingle-phase dwelling service and feeder conductor sizing (NEC 310.12)Flexible cord and cable types, permitted and prohibited uses, ampacity, and marking requirementsFixture wire types, ampacities, minimum size, permitted uses, and grounding conductor identification
Raceways and Boxes 6 Q · 8%
Box fill calculations (conductor volume allowances per AWG size)Conduit fill percentage limits and conductor count tables (EMT, RMC, IMC, FMC, PVC, LFMC, ENT)Securing and supporting requirements for conduit and tubing typesPull and junction box sizing for straight and angle pulls (Article 314.28)Uses permitted and not permitted for each raceway typeOutlet box sizing and support for luminaires, paddle fans, and equipmentConduit bending requirements (bend radius, degrees per run, offset calculations)Wireway and auxiliary gutter fill limits and installation requirements
Special Occupancies and Equipment (Including Swimming Pools) 4 Q · 5%
Hazardous location classification (Class I, II, III; Divisions 1 and 2; Groups A-G)Wiring methods and sealing requirements in hazardous classified locationsSwimming pools, spas, and fountains — GFCI protection, bonding, and equipotential planesHealth care facilities — essential electrical systems, patient care spaces, and groundingMotor branch-circuit conductors, overload protection, and short-circuit/ground-fault protectionAir-conditioning and refrigerating equipment — disconnecting means, branch-circuit protection, and markingsMobile homes, manufactured homes, recreational vehicles, and marinas — power supply and wiring requirementsTransformers, generators, and temporary installations — overcurrent protection and installation requirements
Low Voltage, Alarms, Signaling Systems, and Communications 2 Q · 2%
Fire alarm circuit types: NPLFA vs. PLFA power sources, branch circuit requirements, and disconnecting means identificationFire alarm cable types, ratings, and permitted applications by location (plenum, riser, general-purpose: FPLP, FPLR, FPL, NPLFP, NPLFR, NPLF)Separation requirements between fire alarm circuits and electric light/power conductorsCommunications cable types and permitted applications by location (CMP, CMR, CMG, CM, CMX) and cable substitution hierarchyBonding and grounding of communications systems, antenna systems, and CATV coaxial cable shieldsAntenna system installation requirements: conductor sizing, clearances, discharge units, and grounding electrode conductors (Article 810)CATV and network-powered broadband communications systems: power limitations, cable types, and grounding of coaxial cable shieldsLow-voltage lighting system requirements: voltage limitations, isolating power supply, secondary circuit grounding, and branch circuit ratings
Lighting and Signs 4 Q · 5%
Luminaire location requirements (wet, damp, corrosive, bathtub/shower zones, clothes closets)Support and mounting of luminaires (outlet boxes, suspended ceilings, poles, trees)Grounding and bonding of luminaires and lighting equipmentRecessed luminaire installation (clearances, thermal protection, insulation contact, Type IC)Lighting track installation, construction, and restrictionsElectric signs and outline lighting disconnecting means and branch circuit requirementsNeon secondary-circuit wiring (1000V or less and over 1000V) and transformer/power supply requirementsLow-voltage lighting systems (voltage limitations, secondary circuit isolation, branch circuit requirements)
Safety 4 Q · 5%
Lockout/tagout procedures and establishing an electrically safe work conditionArc-flash hazard assessment and PPE categories (arc ratings by cal/cm²)Shock protection boundaries (limited and restricted approach boundaries)Electrical protective equipment inspection, care, and use (rubber insulating gloves, blankets, sleeves)Ground-fault circuit interrupter (GFCI) and assured equipment grounding conductor program requirementsPersonal protective equipment criteria, selection, and employer payment obligationsFirst aid, medical services, and emergency action plan requirements on construction sitesEmployer and employee responsibilities for electrical safety (OSHA and NFPA 70E)

Key Distinctions

Mandatory rules ("shall"/"shall not")vsInformational Notes

Mandatory rules identify actions specifically required or prohibited and are characterized by "shall" or "shall not," while Informational Notes are informational only and are not enforceable as Code requirements.

NEC 2023 Section 90.5(A)
NEC Chapters 1, 2, 3, and 4vsNEC Chapters 5, 6, and 7

Chapters 1 through 4 apply generally to all electrical installations, whereas Chapters 5, 6, and 7 apply to special occupancies, special equipment, or other special conditions and may supplement or modify Chapters 1 through 4.

NEC 2023 Section 90.3
NEC Chapter 8 (communications systems)vsNEC Chapters 1 through 7

Chapter 8 is not subject to the requirements of Chapters 1 through 7 except where those requirements are specifically referenced in Chapter 8.

NEC 2023 Section 90.3
SI (metric) unitsvsInch-pound units

SI units are the Code's measurement system of preference and shall appear first, with inch-pound units immediately following in parentheses.

NEC 2023 Section 90.9(A), 90.9(B)
Grounded conductor 6 AWG or smallervsInsulated grounded conductor 4 AWG or larger

Both sizes may be identified by a continuous white or gray outer finish or by three continuous white or gray stripes on other than green insulation; the key difference is that 4 AWG or larger may instead be identified at the time of installation by a distinctive white or gray marking encircling the insulation at its terminations.

NEC 2023 Section 200.6(A)
Grounded (neutral) conductor identificationvsEquipment grounding conductor identification

Grounded conductors and their terminals are identified white, gray, or silver (or "white"/"W"), while green or green with one or more yellow stripes is reserved for equipment grounding conductors and shall not be used for anything else.

NEC 2023 Section 200.9
White/gray conductor used as grounded conductorvsWhite/gray conductor re-identified as ungrounded

A white or gray conductor may serve as an ungrounded conductor in circuits of 50 volts or more only where it is part of a cable assembly and is permanently reidentified (tape, paint, or other effective means in a color other than white, gray, or green) at its termination and at each location where the conductor is visible and accessible; without that marking it is not permitted.

NEC 2023 Section 200.7(C)
Continuous loadvsNoncontinuous load

The 125 percent multiplier applies only to the continuous load portion, which is added to the noncontinuous load at 100 percent when sizing branch-circuit conductors and overcurrent devices.

NEC 2023 Section 210.19(A)(1)
Branch-circuit overcurrent device sizing (210.20(A))vsFeeder overcurrent device sizing (215.3)

Both use noncontinuous load plus 125 percent of continuous load, but 210.20(A) applies to branch circuits and 215.3 applies to feeders, with the result rounded to a standard rating from 240.6(A).

NEC 2023 Section 210.20(A), 240.6(A)
GEC to rod, pipe, or plate electrode onlyvsGEC to concrete-encased electrode only

Where it does not extend to other electrode types requiring a larger conductor, the GEC to a rod/pipe/plate electrode need not be larger than 6 AWG copper (4 AWG aluminum), while to a concrete-encased electrode it need not be larger than 4 AWG copper.

NEC 2023 Section 250.66(A)
Copper conductor (K = 12.9)vsAluminum conductor (K = 21.2)

Aluminum has roughly 1.6 times the resistance of copper, so its higher K value produces a larger calculated voltage drop for the same size, current, and length.

Series resistancesvsParallel resistances

Series resistances add directly, while parallel resistance is found by product-over-sum (or reciprocals) and is always less than the smallest branch resistance.

NEC 2023 Chapter 9 (circuit theory); Ugly's Electrical References, Parallel Circuits section
Medium-base (or smaller) screw shell lampholdersvsMogul-base screw shell lampholders

On circuits exceeding 120 volts between conductors but not exceeding 277 volts to ground, incandescent luminaires are permitted only with medium-base or smaller lampholders supplied at 120 volts or less through an integral auto/stepdown transformer; mogul-base lampholders supplied at 240 volts are not permitted.

NEC 2023 Section 210.6(C)(3)
Rigid metal conduit / intermediate metal conduit in notched woodvsCables in notched wood members

RMC, IMC, rigid nonmetallic conduit, and EMT are exempt from the steel plate protection requirement in notches, while other wiring methods such as cables require the steel plate.

NEC 2023 Section 300.4(A)(2) Exception No. 1

Key Terms

Mandatory rule (90.5(A)) NEC 2023 Section 90.5(A)
A Code rule identifying an action specifically required or prohibited, characterized by the terms "shall" or "shall not."
Informational Note (90.5(C)) NEC 2023 Section 90.5(C)
Explanatory material that is informational only and is not enforceable as a requirement of the Code.
NEC arrangement (90.3) NEC 2023 Section 90.3
The Code consists of an introduction plus nine chapters, with Chapters 1–4 applying generally, Chapters 5–7 covering special occupancies/equipment/conditions, Chapter 8 for communications systems, and Chapter 9 consisting of tables.
Mandatory application (90.4(A)) NEC 2023 Section 90.4(A)
The Code is intended to be suitable for mandatory application by governmental bodies exercising legal jurisdiction over electrical installations, including signaling and communications systems, and for use by insurance inspectors.
Grounded conductor continuity (200.2(B)) NEC 2023 Section 200.2(B)
Continuity of a grounded conductor shall not depend on a connection to a metal enclosure, raceway, or cable armor.
Neutral conductor use (200.4(A)) NEC 2023 Section 200.4(A)
A neutral conductor shall not be used for more than one branch circuit, more than one multiwire branch circuit, or more than one set of ungrounded feeder conductors unless specifically permitted elsewhere in the Code.
Multiconductor cable grounded conductor identification (200.6(E)) NEC 2023 Section 200.6(E)
The insulated grounded conductor in a multiconductor cable shall be identified by a continuous white or gray outer finish, or by three continuous white or gray stripes on other than green insulation, along its entire length.
Screw shell device terminal (200.10(C)) NEC 2023 Section 200.10(C)
On devices with screw shells, the terminal for the grounded conductor is the one connected to the screw shell, ensuring proper polarity.
Grounded conductor on load side of service disconnect (250.24(B)) NEC 2023 Section 250.24(B)
A grounded conductor shall not be connected to normally non-current-carrying metal parts, to equipment grounding conductors, or be reconnected to ground on the load side of the service disconnecting means, except as otherwise permitted.
Supplemental electrode bonding jumper (250.53(E)) NEC 2023 Section 250.53(E)
Where a rod, pipe, or plate supplemental electrode is used, the portion of the bonding jumper that is the sole connection to it is not required to be larger than 6 AWG copper (or 4 AWG aluminum/copper-clad aluminum).
Multiple electrode spacing (250.53(A)(3)) NEC 2023 Section 250.53(A)(3)
Multiple rod, pipe, or plate electrodes installed to meet supplemental electrode requirements shall not be less than 1.8 m (6 ft) apart.
Standard branch-circuit ratings (210.18) NEC 2023 Section 210.18
For other than individual branch circuits the ratings are 10, 15, 20, 30, 40, and 50 amperes; individual branch circuits may have other ratings, and 10-ampere circuits shall not supply receptacle outlets.
AFCI protection in dwellings (210.12(B)) NEC 2023 Section 210.12(B)
All 120-volt, single-phase, 10-, 15-, and 20-ampere branch circuits supplying outlets or devices in listed locations, including bedrooms, must be AFCI protected by one of the means in 210.12(A)(1) through (A)(6).
Laundry branch circuit (210.11(C)(2)) NEC 2023 Section 210.11(C)(2)
At least one additional 20-ampere branch circuit shall be provided to supply the laundry receptacle outlet(s) required by 210.52(F).
Dwelling unit voltage limitation (210.6(A)) NEC 2023 Section 210.6(A)
In dwelling units, voltage shall not exceed 120 volts nominal between conductors supplying cord-and-plug-connected loads of 1440 volt-amperes or less.
Household range branch circuit (210.19(C)) NEC 2023 Section 210.19(C)
Branch-circuit conductors for household ranges, wall ovens, counter-mounted cooking units, and other cooking appliances rated 8¾ kW or more require a minimum branch-circuit rating of 40 amperes, and the 3-wire neutral must be at least 70 percent of the branch-circuit rating and not smaller than 10 AWG.
Free conductor at boxes (300.14) NEC 2023 Section 300.14
At least 150 mm (6 in.) of free conductor, measured from where it emerges from the raceway or cable sheath, shall be left at each outlet, junction, and switch point.
Bored holes in wood members (300.4(A)(1)) NEC 2023 Section 300.4(A)(1)
Holes for cables or raceways through joists, rafters, or wood members shall be bored so the edge of the hole is not less than 32 mm (1¼ in.) from the edge of the wood member.
Chapter 3 voltage limit (300.2(A)) NEC 2023 Section 300.2(A)
Wiring methods in Chapter 3 shall be used for 1000 volts AC, 1500 volts DC, nominal, or less, where not specifically limited elsewhere in Chapter 3.
Plug fuse identification (240.50(C)) NEC 2023 Section 240.50(C)
Plug fuses rated 15 amperes and lower must be identified by a hexagonal configuration of the window, cap, or other prominent part to distinguish them from higher-rated fuses.
Type SO flexible cord (Table 400.4) NEC 2023 Table 400.4
A 600-volt flexible cord suitable for pendant or portable use in damp locations and rated for extra-hard usage.
Minimum cover, direct burial (Table 300.5(A)) NEC 2026 Table 300.7(A) (NEC 2023: 300.5(A))
Direct-buried cables or conductors in locations not otherwise specified require a minimum cover of 600 mm (24 in.).

Formulas to Know

Minimum branch-circuit/feeder conductor ampacity and overcurrent device rating with continuous loadsRating ≥ noncontinuous load + (1.25 × continuous load); then select the next standard rating from 240.6(A). Ex: 12 A continuous × 1.25 = 15 A; 40 A + (60 A × 1.25) = 115 A → 125 A device.
Minimum circular mils to hold voltage drop within a limit (single-phase)Allowable VD = source voltage × 0.03 (3% recommended at farthest outlet); CM = (2 × K × I × L) / VD, then choose the next larger conductor. Ex: (2 × 12.9 × 20 × 80) / 3.6 = 11,466 cmil → 8 AWG (16,510 cmil).
Voltage drop and percent voltage drop (single-phase)VD = (2 × K × I × L) / CM, with K = 12.9 copper, K = 21.2 aluminum; %VD = VD ÷ source voltage. Ex: (2 × 21.2 × 30 × 100) / 26,240 = 4.85 V; 8.4 V ÷ 240 V = 3.5%.
Total resistance of parallel resistorsTwo branches: RT = (R1 × R2) / (R1 + R2). Equal branches: RT = R ÷ n. Three or more: 1/RT = 1/R1 + 1/R2 + 1/R3. Ex: (60 × 120)/180 = 40 Ω; 18 Ω ÷ 3 = 6 Ω; 1/12 + 1/12 + 1/6 = 1/3 → 3 Ω.
Series-parallel total resistance and total currentR_total = series resistances + parallel-equivalent resistance(s); I_total = E / R_total. Ex: 3 + (8∥24 = 6) + 5 = 14 Ω; 28 V / 14 Ω = 2 A.
Current in one branch of a parallel sectionV_parallel = I_total × R_parallel; I_branch = V_parallel / R_branch. Ex: 2 A × 6 Ω = 12 V; 12 V / 24 Ω = 0.5 A. Series branch: add its resistors first (7 + 5 = 12 Ω → 12 V/12 Ω = 1 A).
Power dissipated in a resistanceP = I² × R. Ex: (4 A)² × 25 Ω = 16 × 25 = 400 W.
Dwelling general lighting plus small-appliance and laundry load (Article 220)Total VA = (area in sq ft × 3 VA/sq ft) + (1500 VA × number of small-appliance circuits) + 1500 VA per laundry circuit. Ex: 2000 × 3 = 6000 + 3000 + 1500 = 10,500 VA. Dwelling units only; a retail store uses the Table 220.42(A) unit load, 1.9 VA/sq ft, plus 180 VA per receptacle outlet.
Ampacity of conductors installed in parallel setsTotal ampacity = table ampacity of one conductor × number of parallel sets. Ex: 350 kcmil THHN copper at 90°C = 350 A; 350 A × 2 sets = 700 A.
Maximum rating of one cord-and-plug-connected utilization equipment not fastened in place on a multi-outlet circuit (210.23(A)(1))Max equipment rating = 0.80 × branch-circuit ampere rating. Ex: 15 A × 0.80 = 12 A.