Exam Cheat Sheet · Quick Reference
South Carolina Residential Electrical
South Carolina · PSI Services Contractor
South Carolina State Portion 60 questions
Key Distinctions
Overload heater elements are sized from the nameplate amperes, while branch-circuit conductors, switch ratings, and short-circuit protection are sized from NEC full-load current tables.
NEC Handbook, Section 430.32The main bonding jumper is used only at the service, while the system bonding jumper connects the grounded circuit conductor to the EGC at a separately derived system such as a transformer.
NEC Handbook, Article 100 (Definition: Bonding Jumper, System)Single-phase: I = (kW × 1000) ÷ (E × PF); three-phase adds the factor 1.73 (√3) in the denominator: I = (kW × 1000) ÷ (E × PF × 1.73).
NEC Handbook, Section 220.5(A)THHN is rated 90°C for dry and damp locations only, while THW is rated 75°C and is approved for both dry and wet locations.
NEC Handbook, Section 310.104, Table 310.104(A)NM cable is permitted inside one- and two-family dwellings and attached/detached garages, while USE cable is for underground use only and is not permitted for interior wiring.
NEC Handbook, Section 334.10(1)FMC is not permitted in wet locations, whereas LFMC is permitted for direct burial where listed and marked for the purpose.
NEC Handbook, Section 348.12EGC size is based on the rating or setting of the overcurrent device ahead of the equipment, while GEC size is based on the size of the largest ungrounded service conductor.
NEC Handbook, Section 250.122 / Table 250.122PLFA circuits must be separated from electric light and power conductors unless specific exceptions apply, while single- and multiple-station smoke alarms in dwellings are supplied by standard 120-volt branch circuits not subject to Article 760.
NEC Handbook, Section 760.136(A)When the overcurrent device exceeds 800 A, conductor ampacity must equal or exceed the device rating; the next-higher-standard-size allowance of 240.4(B) does not apply above 800 A.
NEC Handbook, Section 240.4(C)In a parallel circuit the total resistance is always less than the resistance of any individual branch because additional paths reduce overall opposition, whereas in a series circuit resistances add together.
NEC Handbook, Section 90.1 (Ohm's Law principles); parallel circuit theory as applied in electrical installationsFor a 3-wire, single-phase dwelling unit service, the 83% allowance permits 2/0 AWG THW copper for a 200 A service, rather than the 3/0 AWG that standard ampacity tables would otherwise require.
NEC Handbook, Section 215.2(A)(3)When temporary branch circuits supplying receptacles are run as open conductors, a separate equipment grounding conductor is required; a complete metallic raceway can itself serve as the EGC.
29 CFR 1926, §1926.405(a)(2)(ii)(B)Key Terms
Formulas to Know
I = (kW × 1000) ÷ (E × PF)I = (kW × 1000) ÷ (E × PF × 1.73)Feeder ampacity = (125% × FLC of largest motor) + sum of FLC of all other motorsAdjusted ampacity = Base ampacity × Adjustment factor (e.g., 0.80 for 4–6 conductors)Watts saved = Old lamp wattage − New lamp wattageCost = (Watts × Hours used × Rate per kWh) ÷ 1000VD = (2 × K × I × L) ÷ CM [K = 12.9 for Cu at 75°C; L = one-way length in feet; CM = conductor area in circular mils]Minimum allowable ampacity = Service rating × 83% (3-wire, single-phase dwelling)