Exam Cheat Sheet · Quick Reference
South Carolina Residential Electrical
South Carolina · PSI Services Contractor
South Carolina State Portion 60 questions
Key Distinctions
The main bonding jumper is the connection between the grounded circuit conductor and the equipment grounding conductor at the service, while the system bonding jumper makes that same type of connection at a separately derived system such as a transformer.
NEC 2017 Article 100 — Bonding Jumper, Main definitionThe GEC is sized from Table 250.66 based on the size of the largest ungrounded (service) conductor, while the EGC is sized from Table 250.122 based on the rating or setting of the automatic overcurrent device ahead of the equipment.
NEC 2017 Section 250.66 / Table 250.66Per 430.32 overload heaters are sized on the motor nameplate amperes, whereas branch-circuit conductors and overcurrent devices are sized from the full-load current tables.
NEC 2017 Section 430.32Three-phase calculations include the 1.73 (√3) multiplier — in the denominator for amperes, as the multiplier for kW/kVA, and in place of the factor 2 in voltage drop — while single-phase formulas do not use 1.73 (the factor 2 is used for two-phase, four-wire).
Ugly's Electrical References 2020, Formulas for Calculating Amperes, Horsepower, Kilowatts, and kVAAC formulas include power factor (and 1.73 for three phase), while DC formulas use neither power factor nor the 2 or 1.73 multipliers (e.g., DC amperes I = (kW × 1000) ÷ E; DC HP = (E × I × %EFF) ÷ 746).
Ugly's Electrical References 2020, Formulas for Calculating Amperes, Horsepower, Kilowatts, and kVATHHN is rated 90°C and is suitable for dry and damp locations only, while THW is rated 75°C and is suitable for dry and wet locations (TW is 60°C, RHW is 75°C dry and wet).
NEC 2017 Section 310.104, Table 310.104(A)Type USE shall not be used for interior wiring (identified for underground use only), while Type UF is permitted underground including direct burial and also for interior wiring when installed per applicable requirements.
NEC 2017 Section 338.12(B)(1)Voltage of a circuit is the greatest rms difference of potential between any two conductors of the circuit (240 V on a 120/240 V circuit), while voltage to ground is the separately defined measurement from an ungrounded conductor to ground (120 V).
NEC 2017 Article 100 (Definition of Voltage of a Circuit)Annex C tables apply only when all conductors are the same size and type (and decimals of 0.8 or larger may be rounded up), while conductors of different sizes or insulation types require summing individual cross-sectional areas and comparing to the allowable fill area.
NEC 2017 Chapter 9, Table 1 and Notes to TablesThe next-higher-standard-size rounding permitted by 240.4(B) does not apply above 800 amperes; where the overcurrent device exceeds 800 A the conductor ampacity must equal or exceed the device rating.
NEC 2017 Section 240.4(C)At 120/208 V the conventional colors are A = black, B = red, C = blue with white/gray neutral, while at 277/480 V they are A = brown, B = orange, C = yellow with a gray neutral.
Ugly's Electrical References 2020, Common Electrical Distribution SystemsPer Table 300.5, RMC requires only 6 inches of cover in most locations, compared with 24 inches for direct burial cables and 18 inches for rigid nonmetallic conduit without concrete encasement.
NEC 2017 Section 300.5Peak let-through current corresponds to the mechanical forces exerted on conductors and equipment during a fault, while the apparent prospective RMS symmetrical let-through value corresponds to the heating effect (clearing time being less than ½ cycle in the current-limiting range).
Ugly's Electrical References 2020, Component Protection (Fuse Let-Through Charts)Key Terms
Formulas to Know
I = E ÷ R (e.g., 120 V ÷ 12 Ω = 10 A); P = E² ÷ R (e.g., 120² ÷ 12 = 1,200 W)Single-phase: I = (kW × 1000) ÷ (E × PF); Three-phase: I = (kW × 1000) ÷ (E × PF × 1.73); DC: I = (kW × 1000) ÷ EI = (HP × 746) ÷ (E × %EFF × PF); e.g., (0.5 × 746) ÷ (115 × 0.92 × 0.80) = 4.4 ASingle-phase AC: HP = (E × I × %EFF × PF) ÷ 746; DC: HP = (E × I × %EFF) ÷ 746 (no PF, no 1.73)1φ kW = (E × I × PF) ÷ 1000; 3φ kW = (E × I × PF × 1.73) ÷ 1000; 3φ kVA = (E × I × 1.73) ÷ 1000 (PF is not used for kVA)Single-phase: Vd = (2 × K × L × I) ÷ Cm; Three-phase: Vd = (1.73 × K × L × I) ÷ Cm, with K = 12.9 for copper and 21.2 for aluminum at 75°C; %Vd = Vd ÷ source voltage × 100 (e.g., 7 V ÷ 240 V = 2.9%); NEC recommends not exceeding 5% total, 3% eachCorrected ampacity = base ampacity × ambient temperature correction factor × conductor-count adjustment factor; base tables assume 30°C ambient (e.g., 100 A × 0.88 at 40°C/75°C × 0.80 for 4–6 current-carrying conductors = 70.4 A)Cost = Watts × Hours Used × Rate per kWh ÷ 1000 (e.g., 5000 W × 360 h × $0.15 ÷ 1000 = $270)Minimum ampacity = (125% × FLC of largest motor) + sum of FLCs of all other motors (e.g., 1.25 × 65 A + 40 A = 121.25 A)Transformer %Z = applied primary voltage ÷ rated primary voltage (9.6 ÷ 480 = 2%Z); motor short-circuit contribution ≈ total motor current × 4; at a single-phase center-tapped transformer, I(L-N) = 1.5 × I(L-L)