Verified, not estimated. Every figure below is drawn from the official exam structure we maintain — question counts, passing standard and topic weighting. Practice questions are grounded in the source law with statute citations. We omit any figure we can't verify rather than guess at it.
Total questions
26
Passing score
70%
Exam time
110 min
Administered by
PSI Services Contractor
Format
Reference materials allowed
Texas State Portion
26 questions
Calculations and Theory2 Q · 8%
Dwelling unit load calculations using standard and optional methods (Articles 220 Parts III and IV)Branch-circuit load calculations including minimum unit loads, receptacle loads, and outlet loads (Article 220 Part II)Conductor ampacity selection and correction/adjustment factors for temperature and number of conductors (Article 310)Motor branch-circuit conductor sizing and feeder calculations including 125% rule and multiple motor loads (Article 430 Parts II and V)Feeder and service neutral load calculations and permitted reductions (Section 220.61)Demand factors for household electric ranges, cooking appliances, and clothes dryers (Sections 220.54 and 220.55)Overcurrent protective device ratings and standard ampere ratings for branch circuits and feeders (Article 240)Multifamily dwelling, school, and commercial occupancy optional load calculation methods (Sections 220.84 through 220.88)
Electrical Services, Service Equipment, and Separately Derived Systems4 Q · 17%
Service conductor ampacity sizing and minimum size requirements (Articles 230.23, 230.31, 230.42)Service disconnecting means rating and number of disconnects (Articles 230.71, 230.79, 230.80)Grounding electrode conductor sizing using Table 250.66Main bonding jumper and system bonding jumper sizing using Table 250.102(C)(1)Service entrance conductor sizing for continuous and noncontinuous loads (Article 230.42)Ground-fault protection of equipment requirements for solidly grounded wye services (Article 230.95)Separately derived system grounding and bonding calculations (Article 250.30)Transformer overcurrent protection calculations using Tables 450.3(A) and 450.3(B)
Electrical Feeders3 Q · 12%
Minimum feeder conductor ampacity for continuous and noncontinuous loads (125% rule)Feeder load calculations using demand factors for dwelling units and multifamily buildingsFeeder overcurrent protection rating requirementsFeeder neutral load calculations and permitted reductionsOptional feeder load calculation methods for dwelling units and schoolsAmpacity correction and adjustment factors applied to feeder conductorsGround-fault protection requirements for feeder disconnects rated 1000 amperes or moreFeeder tap conductor rules (10-foot, 25-foot, and outside tap provisions)
Branch Circuit Calculations and Conductors4 Q · 17%
Minimum conductor ampacity and sizing for continuous and noncontinuous loads (210.19, 220.11)Branch circuit ratings and permissible loads by circuit size (210.18, 210.23, 210.24)Overcurrent protection sizing for branch circuits including 125% continuous load rule (210.20, 240.4, 240.6)Ampacity tables and correction/adjustment factors for temperature and number of conductors (310.15, 310.16, Table 310.15(C)(1))Dwelling unit branch circuit load calculations including general lighting, small appliance, and laundry loads (220.41, 220.52)GFCI and AFCI protection requirements by location and occupancy type (210.8, 210.12)Receptacle outlet ratings and placement requirements for dwelling and non-dwelling occupancies (210.21, 210.52)Conductor identification requirements for grounded, ungrounded, and equipment grounding conductors (200.6, 210.5, 310.6)
Electrical Wiring Methods and Electrical Materials2 Q · 8%
Conductor ampacity tables and temperature ratings (Table 310.16, 310.17)Ambient temperature correction factors for conductor ampacity (Table 310.15(B)(1)(1))Adjustment factors for more than three current-carrying conductors in a raceway (Table 310.15(C)(1))Minimum underground burial depth requirements by wiring method and location (Table 300.5(A))Conductor sizing for single-phase dwelling services and feeders (Table 310.12(A))Conductor support spacing in vertical raceways (Table 300.19(A))Physical protection requirements for cables and raceways through wood members and framing (300.4)Permitted wiring methods in ducts and plenums used for environmental air (300.22)
Electrical Equipment and Devices2 Q · 8%
Motor branch-circuit conductor sizing and ampacity calculations (Article 430)Motor branch-circuit short-circuit and ground-fault protective device ratings using Table 430.52(C)(1)Overload protection sizing for continuous-duty motors (430.32)Conductors supplying multiple motors or combined motor and non-motor loads (430.24)Hermetic refrigerant motor-compressor branch-circuit sizing and protection (Article 440)Transformer overcurrent protection ratings using Tables 450.3(A) and 450.3(B)Generator conductor ampacity and overcurrent protection requirements (Article 445)Industrial control panel supply conductor ampacity and overcurrent protection rating (Article 409)
Motors and Generators2 Q · 8%
Motor branch-circuit conductor sizing (125% rule, Table 430.247–430.250)Branch-circuit short-circuit and ground-fault protective device rating or setting (Table 430.52)Motor overload protection sizing and selection (430.32, service factor and temperature rise percentages)Feeder conductor sizing for multiple motors (430.24 summation method)Disconnecting means rating and location requirements for motors (430.102, 430.109, 430.110)Generator output conductor ampacity and overcurrent protection (445.12, 445.13)Hermetic refrigerant motor-compressor branch-circuit protection and conductor sizing (440.22, 440.32)Locked-rotor current code letters and kVA/hp calculations (Table 430.7(B))
Electrical Control Devices and Disconnecting Means1 Q · 4%
Motor disconnecting means rating, type, and location requirements (Article 430 Part IX)Motor branch-circuit short-circuit and ground-fault protective device rating calculations using Table 430.52(C)(1)Motor overload protection sizing for continuous-duty motors (430.32 percentage thresholds)Conductor ampacity calculations for single and multiple motors (430.22 and 430.24)Service disconnecting means rating, location, and number of disconnects (Article 230 Part VI)Switch ratings and permitted uses by load type (Article 404.14 AC/DC snap switch classifications)Industrial control panel conductor ampacity and overcurrent protection rating calculations (Article 409)Air-conditioning and refrigerating equipment disconnecting means rating and branch-circuit protection (Article 440)
Special Occupancies, Equipment, and Conditions3 Q · 12%
Classification of hazardous locations by Class, Division, and Group (Classes I, II, III; Divisions 1 and 2; Groups A–G)Protection techniques for hazardous locations (explosionproof, dust-ignitionproof, intrinsic safety, purged/pressurized, nonincendive, dusttight, etc.)Wiring methods permitted in Class I, II, and III Division 1 and 2 locations (conduit types, cable types, sealing requirements)Equipment marking requirements including temperature classification (T-codes) and approval for class, division, and groupSealing and drainage requirements for conduit and cable systems in hazardous locationsGrounding and bonding requirements specific to hazardous classified locationsArea classification and wiring/equipment requirements for specific occupancies (commercial garages, motor fuel dispensing facilities, aircraft hangars, cannabis oil facilities)Intrinsically safe systems installation requirements including conductor separation, sealing, and identification (Article 504)
Renewable Energy Technologies1 Q · 4%
PV source circuit maximum voltage calculation using temperature correction factors (Table 690.7(A))Maximum circuit current calculation for PV systems (690.8(A)) and 125% conductor ampacity sizingOvercurrent protection device ratings for PV system dc circuits (690.9(B))Busbar and feeder sizing for load-side power source connections (705.12(A) and 705.12(B))Wind electric system circuit sizing and overcurrent device ratings at 125% of maximum current (694.12(B))Energy storage system circuit sizing and overcurrent device ratings at 125% of maximum current (706.30 and 706.31)Conductor ampacity sizing for interconnected power source output circuits (705.28(B))Equipment grounding conductor sizing for PV systems using Table 250.122 (690.45)
Continuous loads require conductor ampacity of at least 125% of the load current, while non-continuous loads are calculated at 100%.
NEC 215.2(A)(1)(a)
Feeder Ampacity (Motor Only)vsFeeder Ampacity (Motor + Other Loads)
Motor-only feeders use 125% of largest motor FLC + 100% of all other motor FLCs, while mixed feeders also add 125% of any continuous non-motor loads.
NEC Table 430.250, Section 430.24
Branch Circuit Conductor Sizing (Motor, NEC 430.22)vsFeeder Conductor Sizing (Motors, NEC 430.24)
A single-motor branch circuit conductor must be ≥125% of that motor's FLC, while a motor feeder must be ≥125% of the largest motor FLC plus 100% of all remaining motor FLCs.
NEC Table 430.248, Section 430.22
Temperature Correction FactorvsConduit Fill Adjustment Factor
Temperature correction compensates for ambient heat above the conductor's rated temperature, while conduit fill adjustment derates for heat buildup from multiple current-carrying conductors in the same raceway; both factors are multiplied together against base ampacity.
NEC Table 310.16, Table 310.15(B)(2)(a), Table 310.15(B)(3)(a)
Straight pull box minimum length = 8× the largest conduit trade size; angle pull box minimum distance = 6× the largest conduit trade size plus the sum of all other conduit trade sizes on the same wall.
NEC 314.28(A)(1)
Single-Phase Voltage Drop FormulavsThree-Phase Current Formula
Single-phase VD uses a factor of 2 in the numerator (VD = 2×K×I×D / CM), while three-phase current uses √3 (1.732) as the divisor (I = VA / (E × 1.732)).
NEC Chapter 9, Table 8
Motor Overload Protection (NEC 430.32(A)(1)) — Service Factor ≥1.15vsMotor Branch-Circuit OCPD (NEC 430.52, Inverse-Time CB)
Overload protection is set at 125% of the motor nameplate current (for SF ≥1.15), while branch-circuit short-circuit/ground-fault protection via inverse-time CB is set at 250% of the Table FLC (next standard size up if needed).
The disconnect must be rated at least 115% of motor FLC, while branch circuit conductors must have an ampacity of at least 125% of motor FLC.
NEC Table 430.250, Section 430.110(A)
Time-Delay (Dual-Element) Fuse for Motor Protection (NEC Table 430.52)vsInverse-Time Circuit Breaker for Motor Protection (NEC Table 430.52)
Time-delay dual-element fuses are sized at 175% of motor FLC (next standard size up if needed), while inverse-time circuit breakers are sized at 250% of motor FLC (next standard size up if needed).
NEC 600.5(A) prohibits other loads on a sign branch circuit (dedicated use only), while NEC 600.5(C) classifies sign loads as continuous, requiring conductor ampacity ≥125% of the sign load.
NEC 600.5(A), 600.5(C)
3-Phase Transformer Secondary Currentvs3-Phase System Load Current
Both use I = VA / (E × √3), but transformer secondary current is calculated from kVA rating to size protective equipment, while system load current is calculated from total calculated VA to size feeder conductors.
NEC Article 700.4, transformer secondary current formula
Per NEC 215.2(A)(1)(a), feeder conductors must have ampacity not less than the non-continuous load plus 125% of the continuous load.
Motor Branch Circuit Conductor Sizing NEC Table 430.250, Section 430.22
Per NEC 430.22, branch circuit conductors supplying a single motor must have an ampacity of not less than 125% of the motor's full-load current from NEC Table 430.248 or 430.250.
Motor Feeder Conductor Sizing NEC Table 430.250, Section 430.24
Per NEC 430.24, feeder conductors supplying multiple motors must have an ampacity of not less than 125% of the largest motor FLC plus 100% of all other motor FLCs.
Overload Protection — Motor with Service Factor ≥1.15 NEC Section 430.32(A)(1)
Per NEC 430.32(A)(1), a motor with a service factor of 1.15 or greater shall have overload protection not exceeding 125% of the motor's nameplate full-load ampere rating.
Motor Disconnect Minimum Rating NEC Table 430.250, Section 430.110(A)
Per NEC 430.110(A), the motor disconnect must be rated at not less than 115% of the motor's full-load current from the applicable NEC table.
Straight Pull Box Minimum Length NEC 314.28(A)(1)
Per NEC 314.28(A)(1), the minimum length of a straight pull box is 8 times the trade size diameter of the largest conduit entering the box.
Angle Pull Box Minimum Distance NEC 314.28(A)(2)
Per NEC 314.28(A)(2), the minimum distance for an angle pull is 6 times the largest conduit trade size on that wall plus the sum of all other conduit trade sizes on the same wall.
Emergency System Battery Minimum Voltage NEC 700.12(C)(4)
Per NEC 700.12(C)(4), storage batteries supplying emergency illumination must maintain voltage at no less than 87½% of nominal voltage for 1½ hours.
Emergency System Ground-Fault Signal Device Maximum Setting NEC 700.6(D)
Per NEC 700.6(D), on solidly grounded wye systems over 150V to ground with protective devices rated 1000A or more, the ground-fault signal device shall be set for a maximum of 1200 amperes.
Sign Branch Circuit — Dedicated Use NEC 600.5(A), 600.5(C)
Per NEC 600.5(A), the branch circuit supplying an electric sign shall supply no other load — it must be a dedicated circuit.
Per NEC 600.5(C), electric sign loads are considered continuous loads, requiring branch circuit conductor ampacity of not less than 125% of the sign's rated current.
Neon Sign Switch Rating — Non-Inductive NEC 600.6(B)
Per NEC 600.6(B), a control switch not rated for inductive loads must have a current rating not less than twice the total current rating of the transformers it controls.
Conduit Fill — 40% Rule (Multiple Conductors) NEC Chapter 9, Table 4; Chapter 9, Table 5
Per NEC Chapter 9, Table 4, when three or more conductors are installed in a conduit, the total conductor cross-sectional area must not exceed 40% of the conduit's internal cross-sectional area.
Conductor Ampacity Adjustment — Conduit Fill (4–6 CCC) NEC Table 310.16, Table 310.15(B)(2)(a), Table 310.15(B)(3)(a)
Per NEC Table 310.15(B)(3)(a), when 4–6 current-carrying conductors are in a raceway, each conductor's base ampacity must be multiplied by an adjustment factor of 0.80.
Conductor Ampacity Adjustment — Conduit Fill (7–9 CCC) NEC Table 310.16, Table 310.15(B)(2)(a), Table 310.15(B)(3)(a)
Per NEC Table 310.15(B)(3)(a), when 7–9 current-carrying conductors are in a raceway, each conductor's base ampacity must be multiplied by an adjustment factor of 0.70.
Maximum Continuous Load on a Branch Circuit NEC 210.20(A), 210.19(A)(1)
Per NEC 210.20(A), the continuous load on a branch circuit must not exceed 80% of the OCPD rating (equivalently, OCPD rating ÷ 1.25 = maximum continuous load).
Motor Branch-Circuit OCPD — Inverse-Time CB (Max Size)Max CB = Motor FLC × 2.50; if result is not a standard size, round UP to next standard size per NEC 240.6(A)
Motor Branch-Circuit OCPD — Time-Delay (Dual-Element) Fuse (Max Size)Max Fuse = Motor FLC × 1.75; if result is not a standard size, round UP to next standard size per NEC 240.6(A)
Conduit Fill — Minimum Trade Size (Multiple Conductors)Total Fill Area = Σ(Number of each conductor × individual conductor area from Table 5); select smallest conduit from Table 4 where 40% fill area ≥ Total Fill Area