Texas Journeyman Electrician NEC Knowledge Portion
Texas
· PSI Services Contractor
Verified, not estimated. Every figure below is drawn from the official exam structure we maintain — question counts, passing standard and topic weighting. Practice questions are grounded in the source law with statute citations. We omit any figure we can't verify rather than guess at it.
Total questions
59
Passing score
70%
Exam time
130 min
Administered by
PSI Services Contractor
Format
Reference materials allowed
Texas State Portion
59 questions
Definitions, Theory, and Plans3 Q · 5%
Purpose and scope of the NEC (practical safeguarding of persons and property)Installations covered and not covered by the NECMandatory vs. permissive vs. explanatory language (shall, shall be permitted, informational notes)NEC code arrangement and chapter hierarchy (Chapters 1–9, annexes)Authority having jurisdiction (AHJ): enforcement, interpretations, and special permissionEquipment examination, listing, and approval for safetyWiring planning principles (future expansion, circuit limitations in enclosures)Units of measurement (SI vs. inch-pound, hard vs. soft conversion)
Electrical Services, Service Equipment, and Separately Derived Systems6 Q · 11%
Service conductor clearances and wiring methods (overhead and underground)Service disconnecting means — location, rating, and number of disconnectsService entrance conductor sizing, ampacity, and insulation requirementsGrounding electrode system — types, installation, and conductor sizing (Article 250 Part III)Separately derived systems — grounding, bonding, and system bonding jumper requirementsMain bonding jumper and supply-side bonding jumper sizing and installationService equipment overcurrent protection and ground-fault protection of equipmentService load calculations — feeder and service demand factors for dwelling and non-dwelling occupancies
Electrical Feeders3 Q · 5%
Minimum feeder conductor ampacity for continuous and noncontinuous loads (125% rule)Feeder overcurrent protection ratings and requirementsFeeder load calculations including demand factors for dwelling units and other occupanciesGround-fault protection of equipment for feeders rated 1000 amperes or moreFeeder conductor identification (grounded, equipment grounding, and ungrounded conductors)Surge-protective device requirements for feeders supplying dwelling and sleeping unitsOutside feeder clearances, conductor support, and disconnecting means for separate buildingsFeeder neutral load calculations and permitted reductions
Branch Circuits and Conductors10 Q · 18%
GFCI protection requirements for dwelling and non-dwelling locationsAFCI protection requirements and permitted means of protectionBranch circuit ratings and permissible loads by circuit sizeConductor minimum ampacity and sizing for branch circuitsOvercurrent protection for branch-circuit conductors and equipmentRequired receptacle outlet placement in dwelling unitsMultiwire branch circuit requirements and disconnecting meansBranch circuit load calculations including continuous and noncontinuous loads
Electrical Wiring Methods and Electrical Materials10 Q · 18%
Uses permitted and not permitted for Type AC, MC, NM, and NMC cablesSecuring and supporting requirements for cables and raceways (spacing intervals, fastening distances)Conductor ampacity tables and temperature correction/adjustment factorsProtection against physical damage (bored holes, notches, framing members, steel plate requirements)Bending radius requirements for cables and conduitFlexible cord and flexible cable types, uses permitted, and uses not permittedRigid Metal Conduit (RMC) and Intermediate Metal Conduit (IMC) installation requirementsBoxes, fittings, and conductor continuity requirements for wiring methods
Electrical Equipment and Devices10 Q · 18%
Switch ratings, types, and permitted uses (AC/DC snap switches, dimmers, CO/ALR, motor-circuit)Receptacle installation requirements, ratings, and GFCI/AFCI/tamper-resistant protectionMotor branch-circuit conductor sizing and overload protection requirementsSwitchboard, switchgear, and panelboard installation, overcurrent protection, and groundingLuminaire installation locations, support, grounding, and wiring requirementsDisconnecting means requirements for motors, appliances, and air-conditioning equipmentTransformer overcurrent protection, installation types, and vault construction requirementsGenerator ratings, overcurrent protection, disconnecting means, and GFCI requirements
Motors and Generators5 Q · 9%
Motor branch-circuit conductor sizing (125% rule and special motor types)Branch-circuit short-circuit and ground-fault protective device ratings (Table 430.52)Motor overload protection requirements and trip current percentagesMotor disconnecting means type, location, and current rating requirementsMotor controller ratings, markings, and application requirementsGenerator conductor ampacity, overcurrent protection, and disconnecting meansMotor control circuit overcurrent protection and conductor requirementsMotor and generator grounding, bonding, and nameplate marking requirements
Electrical Control Devices and Disconnecting Means1 Q · 2%
Switch connection requirements and grounded conductor rules (404.2)Rating and use of switches for specific load types (404.14)Motor disconnecting means location, type, and rating requirements (430.102, 430.109, 430.110)Service disconnecting means requirements, location, and rating (230.70, 230.71, 230.79)Accessibility, height, and grouping requirements for switches and circuit breakers (404.8)Circuit breakers used as switches — marking, indicating, and application (404.7, 404.11, 240.81–240.85)Industrial control panel and motor control center disconnecting means and overcurrent protection (409.20–409.22, 430.92–430.99)Switch and enclosure installation requirements for damp/wet locations and enclosure grounding (404.4, 404.12)
Special Occupancies, Equipment, and Conditions6 Q · 11%
Classification of hazardous locations by Class, Division, and Group (Classes I, II, III; Divisions 1 and 2; Groups A–G)Protection techniques for hazardous locations (explosionproof, dust-ignitionproof, intrinsically safe, purged/pressurized, nonincendive, etc.)Wiring methods permitted in Class I, II, and III Division 1 and 2 locations (conduit types, cable types, sealing requirements)Equipment marking requirements for hazardous locations (class, division, group, temperature class/T-code)Sealing and bonding requirements for conduit and cable systems in hazardous locationsSpecial occupancy hazardous location requirements (commercial garages, motor fuel dispensing facilities, aircraft hangars, cannabis oil systems)Intrinsically safe systems installation requirements (Article 504 – wiring methods, separation, grounding, identification)Zone classification systems as alternatives to Division classification (Zone 0/1/2 for gases; Zone 20/21/22 for dusts)
Renewable Energy Technologies2 Q · 4%
PV system DC circuit maximum voltage calculations and temperature correction factorsRapid shutdown requirements for PV systems on buildingsPV system disconnecting means requirements and markingsOvercurrent protection for PV system DC circuitsPV system wiring methods, conductor identification, and labelingGrounding and bonding requirements for PV systemsInterconnection of power production sources to other systems (Article 705)Energy storage system disconnecting means and circuit requirements
Key Distinctions
Hard conversionvsSoft conversion
Hard conversion (the NEC default per 90.9(B), except as provided in 90.9(C)) changes dimensions or properties into new sizes, while soft conversion is a direct mathematical conversion that does not change actual dimensions and is permitted where the actual measured size differs from the nominal size and trade size designators are used.
NEC 2026 Section 90.9
Conductor ampacity from Table 310.16vsMaximum overcurrent protection per 240.4(D)
A 12 AWG THWN copper conductor has a 25-ampere ampacity in the 75°C column at 30°C ambient, whereas the commonly cited 20 amperes is the maximum overcurrent protection allowed for 12 AWG, not its table ampacity.
NEC 2026 Table 310.16
Transformer with primary protection onlyvsTransformer with both primary and secondary protection
For transformers rated 1000 volts or less with primary current of 9 amperes or more, Table 450.3(B) limits primary overcurrent protection to 125% of rated current when only primary protection is used, but permits up to 250% when both primary and secondary protection are provided.
NEC 2026 Table 450.5(B)
Emergency power source general 2-hour minimumvsStorage battery/UPS for emergency illumination 1½-hour minimum
Per 700.12(C) the emergency power source must supply the total load for not less than 2 hours unless used for emergency illumination under 700.12(C)(4) or unit equipment under 700.12(H); the 1½-hour minimum (with voltage not below 87½% of nominal) applies specifically to storage batteries and UPS supplying emergency illumination.
NEC 2026 Section 700.12
Direct-buried cable general cover (600 mm / 24 in.)vsReduced covers for driveways and GFCI-protected dwelling circuits
Table 300.5(A) requires 600 mm (24 in.) cover in all locations not otherwise specified, but allows 450 mm (18 in.) for one- and two-family dwelling driveways and outdoor parking areas used only for dwelling-related purposes, and 300 mm (12 in.) for residential branch circuits rated 120 volts or less with GFCI protection and maximum 20-ampere overcurrent protection.
NEC 2026 Table 300.7(A)
NEC Chapters 1 through 4vsNEC Chapters 5-7, Chapter 8, and Chapter 9
Per 90.3 Chapters 1, 2, 3, and 4 apply generally to all electrical installations; Chapters 5, 6, and 7 apply to special occupancies, equipment, or conditions and may supplement or modify Chapters 1 through 7; Chapter 8 covers communications systems and is not subject to Chapters 1 through 7 except where specifically referenced in Chapter 8; Chapter 9 consists of tables applicable as referenced.
NEC 2026 Section 90.3
Wye-start, delta-run motor conductors (72%)vsPart-winding connected motor conductors (62.5%)
Conductors between controller and motor must be not less than 72% of motor FLC for wye-start/delta-run per 430.22(C) (58% × 1.25), versus not less than 62.5% for part-winding connected motors per 430.22(D) (50% × 1.25).
A single continuous-duty motor's branch-circuit conductors must be at least 125% of that motor's full-load current, while feeder conductors supplying several motors must be at least 125% of the highest rated motor's FLC plus the sum of the full-load currents of all other motors.
NEC 2026 Section 430.22
EGC in flexible cords (400.23)vsEGC sized by Table 250.122
EGCs in flexible cords may be sized the same as the circuit conductors in the cord — as small as 18 AWG copper for certain cord types in Table 400.4 — because 250.122(F) permits sizing per 400.23, whereas Table 250.122 otherwise requires a 14 AWG minimum.
Rigid metal conduit, intermediate metal conduit, rigid nonmetallic conduit, and electrical metallic tubing are exempt from steel plate protection at notches (300.4(A)(2) Ex. 1) and when run parallel to framing members within 32 mm (1-1/4 in.) of the edge (300.4(D) Ex. 1), while nonmetallic-sheathed cable, Type MC cable, and flexible metal conduit are not exempt.
NEC 2026 Section 300.6(A)(2)
310.15(A)(2) Exception length limit (10 ft or 10%)vs310.15(C)(1)(b) short raceway exemption (600 mm / 24 in.)
The higher ampacity may be applied to a whole circuit only if the lower-ampacity portion does not exceed the lesser of 3.0 m (10 ft) or 10 percent of the total circuit, whereas the separate 600 mm (24 in.) rule exempts short raceways from adjustment factors entirely.
NEC 2026 Section 310.15(A)(2) Exception
Motor control center required marking (430.98(A))vsAvailable fault current documentation (430.99(B))
The MCC marking per 110.21 must be plainly visible after installation and include the common power bus current rating and the MCC short-circuit rating, while the available fault current and the date of its calculation are documented and made available rather than required as nameplate marking.
NEC 2026 Section 430.98(A)
180 VA per receptacle yokevs90 VA per receptacle
Per 220.14(I) each single or each multiple receptacle on one yoke is calculated at not less than 180 volt-amperes; the 90 volt-ampere value applies only to a single piece of equipment consisting of a multiple receptacle comprised of four or more receptacles.
NEC 2026 Section 120.14(I)
Key Terms
Hard conversion (90.9(B)) NEC 2026 Section 90.9
The NEC's default method of converting inch-pound units to SI units, involving a change in dimensions or properties into new sizes, required except as provided in 90.9(C).
Soft conversion (90.9(C)(1)) NEC 2026 Section 90.9
A direct mathematical conversion that does not change actual dimensions, permitted where the actual measured size of a product differs from the nominal size and trade size designators are used, and also for extracted material, industry practice, and safety concerns.
SI unit preference (90.9(B)) NEC 2026 Section 90.9
SI (metric) units shall appear first in the NEC with inch-pound units immediately following in parentheses, though 90.9(D) permits compliance with either system.
Free conductor length (300.14) NEC 2026 Section 300.16
At least 150 mm (6 in.) of free conductor, measured from the point in the box where it emerges from its raceway or cable sheath, must be left at each outlet, junction, and switch point.
Grounded conductor identification (200.6(A)) NEC 2026 Section 200.7(A)
Grounded conductors 6 AWG or smaller must be identified by a continuous white outer finish, a continuous gray outer finish, or three continuous white or gray stripes along the conductor's entire length on other than green insulation.
Continuity of the grounded conductor (200.2(B), 300.13(B)) NEC 2026 Section 200.4(B)
The continuity of a grounded conductor shall not depend on connection to a metal enclosure, raceway, or cable armor, nor in multiwire branch circuits on device connections such as lampholders or receptacles whose removal would interrupt continuity.
Service disconnecting means (230.71(B)) NEC 2026 Section 230.71(B)
Each service is limited to one disconnecting means unless 230.71(B) is met, which permits two to six service disconnects for each service permitted by 230.2 or each set of service-entrance conductors permitted by 230.40, Exception No. 1, 3, 4, or 5.
Grounding electrode conductor to rod, pipe, or plate electrode (250.66(A)) NEC 2026 Section 250.66(A)
Where the grounding electrode conductor or bonding jumper connects to a single or multiple rod, pipe, or plate electrode(s) and does not extend on to other electrode types requiring a larger conductor, it need not be larger than 6 AWG copper or 4 AWG aluminum/copper-clad aluminum.
Paired locknuts (342.29) NEC 2026 Section 342.29
Where IMC threads enter a box, cabinet, or similar enclosure through an opening other than a threaded opening, a locknut or fitting must be installed on both the inside and the outside of the enclosure; 342.42(B) also prohibits running threads for connection at couplings.
The Chapter 9 Table 2 column used to determine the minimum centerline bend radius for field bends in flexible metal conduit, which must be made without damaging the conduit or effectively reducing its internal diameter.
Zone 20 (506.5(B)(1)) NEC 2026 Section 506.5(B)(1)
Under the Zone classification system for combustible dusts, a location in which ignitible concentrations of combustible dust or fibers/flyings are present continuously or for long periods of time.
Unclassified refrigerant machinery room (500.5(A)(2)) NEC 2026 Section 500.5(A)(2)
An ammonia refrigeration machinery room is permitted to be classified as unclassified where adequate mechanical ventilation operates continuously or is initiated by a detection system at a concentration not exceeding 150 ppm (parallel rule in 505.5(A)(2)).
A panelboard in other than service equipment protected by two main circuit breakers or two sets of fuses with a combined rating not greater than that of the panelboard shall not contain more than 42 overcurrent devices, counting a 2-pole or 3-pole breaker as two or three devices.
Underground warning ribbon (300.5(D)(3)) NEC 2026 Section 300.7(D)(3)
Underground service conductors that are not encased in concrete and that are buried 450 mm (18 in.) or more below grade must have their location identified by a warning ribbon placed in the trench at least 300 mm (12 in.) above the underground installation.
Motor full-load current source (430.6(A)(1)) NEC 2026 Section 430.6 and Table 430.248
Full-load currents for single-phase AC motors are determined from Table 430.248 rather than from motor nameplate markings (three-phase squirrel cage values come from Table 430.250).
10-ampere multiple-outlet branch circuit (210.23(A)) NEC 2026 Section 210.23(A)
A 10-ampere branch circuit supplying two or more outlets is limited to lighting outlets, or dwelling unit exhaust fans on bathroom and laundry room lighting circuits, and per 210.18 Exception No. 2 and Table 210.24(1) shall not supply receptacle outlets.
Formulas to Know
Minimum conductor ampacity with continuous loads (branch circuits 210.19(A)(1) and service-entrance conductors 230.42(A)(1))Minimum ampacity = noncontinuous load + (125% × continuous load); e.g., 40 A + (60 A × 1.25) = 115 A
Branch-circuit conductor ampacity for a single continuous-duty motor (430.22)Minimum ampacity = 125% × motor FLC from 430.6(A)(1); e.g., 65 A × 1.25 = 81.25 A
Feeder conductor ampacity for several motors (430.24)Minimum ampacity = (125% × highest rated motor FLC) + sum of FLC of all other motors; e.g., (28 × 1.25) + 14 + 10 = 59 A
Separate motor overload device maximum trip setting, service factor 1.15 or greater (430.32(A)(1))Max trip = 125% × nameplate FLC; e.g., 14 A × 1.25 = 17.5 A; 40 A × 1.25 = 50 A
Conductors between controller and motor for wye-start/delta-run and part-winding motors (430.22(C), (D))Wye-start delta-run: ≥ 72% of motor FLC (58% × 1.25); Part-winding: ≥ 62.5% of motor FLC (50% × 1.25)
Corrected maximum PV source-circuit voltage (690.7(A), Table 690.7(A))Corrected voltage = (number of modules in series × rated Voc) × temperature correction factor; e.g., (10 × 40 V) × 1.14 (for -6 to -10°C) = 456 V
120 percent busbar rule for interconnected power sources at opposite ends of a busbar (705.12(B)(2))(125% × inverter continuous output current) + busbar OCPD rating ≤ 120% × busbar rating; e.g., 240 A − 40 A = 200 A maximum main breaker
Track lighting load, other than dwelling units or hotel/motel guest rooms (120.46(B))150 VA for every 600 mm (2 ft) of track or fraction thereof; e.g., 30 ft ÷ 2 ft = 15 × 150 VA = 2,250 VA (multicircuit track load divided equally between circuits; load may instead be based on a current-limiting device rating)
Receptacle outlet branch-circuit load (220.14(I))≥180 VA per single or per multiple receptacle on one yoke; 90 VA applies only to a single piece of equipment that is a multiple receptacle of four or more receptacles
Maximum fastened-in-place utilization equipment on a circuit also supplying lighting (210.23(B)(2))Max rating = 50% × branch-circuit ampere rating; e.g., 50% of 20 A = 10 A