Total questions
60
Passing score
70%
Exam time
180 min
Administered by
PSI Services Contractor
Format
Reference materials allowed

Texas State Portion 60 questions

Definitions, Theory, and Plans 7 Q · 12%
Purpose and scope of the NEC (practical safeguarding of persons and property)Installations covered vs. not covered by the NECMandatory vs. permissive vs. explanatory rules (shall/shall not vs. shall be permitted)Authority having jurisdiction (AHJ): enforcement, interpretations, and special permissionNEC code arrangement (Chapters 1–9, annexes, and their hierarchy)Equipment examination, listing, and approval for safetyWiring planning principles (future expansion, raceway space, circuit enclosure limits)Units of measurement (SI vs. inch-pound, hard vs. soft conversion)
Electrical Services, Service Equipment, and Separately Derived Systems 4 Q · 7%
Service conductor clearances and installation requirements (overhead and underground)Service disconnecting means location, rating, and maximum number of disconnectsService entrance conductor sizing, ampacity, and permitted wiring methodsService equipment overcurrent protection and ground-fault protection requirementsGrounding and bonding of service equipment, including main bonding jumper and grounding electrode systemSeparately derived system grounding, system bonding jumper, and grounding electrode conductor requirementsTransformer installation requirements, overcurrent protection, and vault constructionGenerator installation, overcurrent protection, disconnecting means, and emergency shutdown requirements
Electrical Feeders 4 Q · 7%
Minimum feeder conductor ampacity for continuous and noncontinuous loads (125% rule)Feeder overcurrent protection requirements and ratingsFeeder load calculations including demand factorsGround-fault protection of equipment for feeder disconnects rated 1000A or moreFeeder equipment grounding conductor requirements and sizingFeeder conductor identification (grounded, ungrounded, and EGC)Feeder taps rules (10-ft, 25-ft, and outside tap provisions)Surge-protective device requirements for feeders and common neutral feeder rules
Branch Circuit Calculations and Conductors 6 Q · 10%
Minimum conductor ampacity for continuous and noncontinuous loads (125% rule)Branch circuit ratings and permissible loads by circuit size (10A through 50A+)Overcurrent protection sizing and small conductor limits (240.4)Ampacity tables and correction/adjustment factors for temperature and conductor fill (Table 310.16, 310.15)GFCI protection requirements by location for dwelling and non-dwelling occupanciesAFCI protection requirements and approved means of protectionConductor identification for grounded, ungrounded, and equipment grounding conductorsMultiwire branch circuit requirements including simultaneous disconnection and line-to-neutral loads
Electrical Wiring Methods and Electrical Materials 10 Q · 17%
Conductor ampacity tables and temperature ratings (Tables 310.16–310.21)Ampacity correction and adjustment factors for ambient temperature and conductor bundlingUnderground installation requirements and minimum cover depths (Table 300.5)Physical protection of cables and raceways through framing members and structural elementsBox and conduit body fill calculations and sizing requirementsSecuring and supporting requirements for raceways, cables, and boxesUses permitted and not permitted for wiring methods (NM, AC, MC, EMT)Protection against corrosion and deterioration for raceways and enclosures
Electrical Equipment and Devices 6 Q · 10%
Switch types, ratings, and installation requirements (Articles 404, 408, 409)Motor circuit conductors, overload protection, and branch-circuit short-circuit protection (Article 430 Parts II, III, IV)Receptacle ratings, grounding, and installation requirements (Article 406)Panelboard and switchboard construction, overcurrent protection, and grounding (Article 408)Motor controllers, disconnecting means, and motor control centers (Article 430 Parts VII, VIII, IX)Luminaire installation, grounding, and location restrictions (Article 410)Air-conditioning and refrigerating equipment disconnecting means, branch-circuit protection, and overload protection (Article 440)Generator overcurrent protection, conductor ampacity, disconnecting means, and emergency shutdown (Article 445)
Motors and Generators 7 Q · 12%
Motor branch-circuit conductor sizing and ampacity requirements (430.22, 430.24)Motor overload protection selection and rating (430.32, 430.37)Branch-circuit short-circuit and ground-fault protection ratings for motors (430.52, Table 430.52(C)(1))Motor controller ratings, types, and disconnecting means requirements (430.83, 430.102, 430.109, 430.110)Motor nameplate markings and locked-rotor code letters (430.7, Table 430.7(B))Motor control centers: overcurrent protection, grounding, busbars, and marking (430.94 through 430.99)Generator installation requirements: marking, overcurrent protection, conductor ampacity, and disconnecting means (445.11 through 445.19)Adjustable-speed drive systems: conductor sizing, overload and overtemperature protection (430.122, 430.124, 430.126)
Electrical Control Devices and Disconnecting Means 3 Q · 5%
Motor disconnecting means location, type, and rating requirements (Article 430 Part IX)Switch ratings, types, and load control limitations (Article 404)Motor controller ratings, design requirements, and use as disconnecting means (Article 430 Parts VII, IX)Overcurrent protection for motor branch circuits and feeders (Article 430 Parts IV, V)Industrial control panel disconnecting means, overcurrent protection, and short-circuit ratings (Article 409)Service disconnecting means location, rating, and number of disconnects (Article 230 Part VI)Switchboard, switchgear, and panelboard overcurrent protection and disconnecting provisions (Article 408)Knife switch ratings, isolating switch restrictions, and position requirements (Article 404)
Special Occupancies, Equipment, and Conditions 6 Q · 10%
Classification of hazardous locations by Class, Division, and Group (Classes I, II, III; Divisions 1 and 2; Groups A-G)Protection techniques for hazardous locations (explosionproof, dust-ignitionproof, intrinsically safe, purged/pressurized, nonincendive, dusttight, hermetically sealed, etc.)Wiring methods for Class I, II, and III Division 1 and 2 locations (permitted conduit types, cable types, flexible connections, boxes and fittings)Sealing and drainage requirements for conduit and cable systems in hazardous locations (seal placement, compound requirements, fill limits)Equipment marking, temperature classification (T-codes), and approval requirements for hazardous locationsGrounding and bonding requirements specific to hazardous classified locations (Classes I, II, III)Health care facility electrical systems (patient care space wiring, essential electrical systems, isolated power systems, GFCI requirements)Swimming pools, fountains, and similar installations (GFCI/SPGFCI protection, grounding and bonding, listing requirements)
Electrical Safety 7 Q · 12%
Classification of hazardous locations (Class I, II, III; Division 1 and 2)Wiring methods and approved cable types for Class I, II, and III hazardous locationsSealing and drainage requirements for conduit and cable systems in hazardous locationsGrounding and bonding requirements in hazardous (classified) locationsEquipment protection techniques (explosionproof, dust-ignitionproof, intrinsic safety, purged/pressurized, nonincendive)Overcurrent protection requirements including conductor protection, fuse and circuit breaker ratings, and arc energy reductionGrounding electrode systems, grounding electrode conductors, and equipment grounding conductorsSurge protection and overvoltage protective devices in classified and general locations

Key Distinctions

Mandatory rules (NEC 90.5(A))vsPermissive rules (NEC 90.5(B))

Mandatory rules use 'shall' or 'shall not' to identify required or prohibited actions, while permissive rules use 'shall be permitted' or 'shall not be required.'

NEC 2026 Section 90.5
Mandatory Code textvsInformational Notes / explanatory material

Mandatory text is enforceable, while informational notes are included for informational purposes only and are not enforceable as requirements of the Code (e.g., the 3% and 5% voltage-drop figures).

NEC 2026 Section 90.5
Chapters 1-4vsChapters 5, 6, and 7

Chapters 1 through 4 apply generally to all installations, while Chapters 5, 6, and 7 apply to special occupancies, special equipment, or other special conditions.

NEC 2026 Section 90.3
Chapters 1 through 7vsChapter 8

Chapter 8 covers communications systems and is not subject to the requirements of Chapters 1 through 7 except where specifically referenced in Chapter 8.

NEC 2026 Section 90.3
Class I locationsvsClass II locations

Class I locations involve flammable gases or vapors (Division 1 = ignitible concentrations can exist under normal operating conditions), while Class II locations involve combustible dusts.

NEC 2026 Section 500.5
Class II (combustible dust)vsClass III, Division 1 (fibers/flyings)

Class II dusts form ignitible suspensions in air, while Class III easily ignitible fibers/flyings are not normally suspended in air in sufficient quantity but can collect on machinery or lighting and be ignited.

NEC 2026 Section 500.5
Branch-circuit/feeder conductor sizing for continuous loadsvsGenerator output conductor sizing

Branch-circuit and feeder conductors must be sized at noncontinuous load plus 125% of continuous load, while conductors from generator output terminals to the first overcurrent device must be at least 115% of the generator nameplate current rating.

NEC 2026 Section 210.19
Motor branch-circuit conductor ampacity (430.22)vsMotor branch-circuit short-circuit/ground-fault breaker sizing (430.52)

Conductors for a single continuous-duty motor are sized at 125% of the table full-load current, while an inverse-time breaker may be set at 250% of FLC for a single-phase motor and increased for starting to a maximum of 400% of FLC for currents of 100 A or less.

NEC 2026 Section 430.6, 430.22
Motor nameplate full-load currentvsTable 430.248 full-load current

For general motor applications, 430.6(A)(1) requires the table values — not the nameplate values — to be used to determine conductor ampacity; nameplate rating is used for overload protection sizing.

NEC 2026 Section 430.6, 430.22
Hermetic motor-compressor conductor sizing (440.32)vsHermetic motor-compressor OCPD sizing (440.22(A))

Conductors must be at least 125% of the rated-load current, while the branch-circuit protective device must not exceed 175% of RLA (next higher standard size permitted by Exception No. 1, up to 225% of RLA under Exception No. 2 if needed to carry starting current).

NEC 2026 Section 440.22(A), 440.32
Table 250.122 EGC sizingvsNEC 250.122(E) flexible cord EGC sizing

Table 250.122 sizes equipment grounding conductors by overcurrent device rating for general equipment, while 250.122(E) governs flexible cords, requiring the EGC to be not smaller than 18 AWG copper and not smaller than the circuit conductors when the largest circuit conductor is 10 AWG or smaller.

NEC 2026 Section 250.122
Feeder voltage drop recommendationvsCombined feeder plus branch-circuit voltage drop recommendation

The informational note recommends feeders be sized to prevent a voltage drop exceeding 3% at the farthest outlet, with maximum total voltage drop on both feeders and branch circuits not exceeding 5%; both are recommendations, not requirements.

NEC 2026 Section 215.4(A)(4) Informational Note
Type SOW flexible cordvsType SPT-2 / SJ / SV cords

Type SOW is a 600-volt extra-hard-usage cord suitable for damp and wet locations ('W' suffix), while SPT-2 is a lightweight parallel thermoplastic cord (not permitted in show windows/showcases), SJ is junior hard-service for damp locations, and SV is a not-hard-usage vacuum cleaner cord.

NEC 2026 Table 400.4
Type SH portable power feeder cablevsType SC / Type G portable power cable

Per Table 400.50, Type SH is a single conductor cable rated 2001–25,000 volts, while Type SC is single conductor rated 2001–5000 volts and Type G is multiconductor rated 2001–5000 volts.

NEC 2026 Table 400.50

Key Terms

Authority Having Jurisdiction (AHJ) NEC 2026 Section 90.4
The enforcement authority responsible for making interpretations of Code rules, deciding on approval of equipment and materials, and granting special permission (NEC 90.4).
Permissive rule NEC 2026 Section 90.5
A Code rule characterized by the terms 'shall be permitted' or 'shall not be required' (NEC 90.5(B)).
Mandatory rule NEC 2026 Section 90.5
A Code rule characterized by the terms 'shall' or 'shall not,' identifying actions specifically required or prohibited (NEC 90.5(A)).
Informational Note NEC 2026 Section 90.5
Explanatory material included for informational purposes only and not enforceable as a requirement of the Code (NEC 90.5(C)).
International System of Units (SI) NEC 2026 Section 90.9
The modernized metric system that is the NEC's measurement system of preference, with SI units appearing first and inch-pound units immediately following in parentheses (NEC 90.9(A) and (B)).
Multiwire branch circuit NEC 2026 Section 210.4
A branch circuit that shall supply only line-to-neutral loads (with exceptions for single utilization equipment or where all ungrounded conductors are opened simultaneously) and must have a means to simultaneously disconnect all ungrounded conductors where it originates (NEC 210.4(B), (C)).
Grounded conductor (premises wiring) NEC 2026 Section 200.5
A conductor that must be electrically connected to the supply system grounded conductor to ensure a common, continuous grounded system, and whose continuity shall not depend on a metal enclosure, raceway, or cable armor (NEC 200.3, 200.2(B)).
Continuous load NEC 2026 Section 210.19
A load for which conductors and overcurrent devices must be sized at the noncontinuous load plus 125 percent of the continuous load (NEC 210.19(A)(1), 215.4(A)(1), 210.20(A), 215.5).
Class I, Division 1 location NEC 2026 Section 500.5
A location where ignitible concentrations of flammable gases, flammable liquid-produced vapors, or combustible liquid-produced vapors can exist under normal operating conditions (NEC 500.5(B)(1)).
Class III, Division 1 location NEC 2026 Section 500.5
An area where easily ignitible fibers or materials producing combustible flyings are handled, manufactured, or used (NEC 500.5(D)(1)).
Autoignition temperature NEC 2026 Section 500.8
The temperature of a specific gas or vapor that no exposed surface of Class I equipment may exceed (NEC 500.8(B)(1)).
Free conductor length NEC 2026 Section 300.16
At least 150 mm (6 in.) of conductor measured from where it emerges from its raceway or cable sheath, left at each outlet, junction, and switch point for splices or connections (NEC 300.14).
Same-raceway rule NEC 2026 Section 300.5(B)
All conductors of the same circuit, including the grounded conductor and all equipment grounding conductors, shall be contained within the same raceway, auxiliary gutter, cable tray, cablebus, trench, cable, or cord unless specifically permitted otherwise, such as for parallel conductors per 310.10(G) (NEC 300.3(B), 300.3(B)(1), 2020 edition).
Inductive heating avoidance (ferrous enclosures) NEC 2026 Section 300.22(A)
All phase conductors and, where used, the grounded conductor and all equipment grounding conductors shall be grouped together to avoid heating surrounding ferrous metal by induction (NEC 300.20(A)).
Supplemental grounding electrode bonding jumper NEC 2026 Section 250.53(E)
The portion of a bonding jumper that is the sole connection to a rod, pipe, or plate supplemental electrode is not required to be larger than 6 AWG copper or 4 AWG aluminum/copper-clad aluminum (NEC 250.53(E)).
Flexible cord prohibited use NEC 2026 Section 400.12
Flexible cords and cables shall not be used as a substitute for the fixed wiring of a structure (NEC 400.12).
Sign equipment working space NEC 2026 Section 600.21
A working space at least 900 mm (3 ft) high × 900 mm (3 ft) wide × 900 mm (3 ft) deep at each ballast, transformer, electronic power supply, and Class 2 power source, or its enclosure, where not installed in a sign (NEC 600.21(D)).

Formulas to Know

Minimum branch-circuit or feeder conductor ampacity with continuous and noncontinuous loadsAmpacity ≥ noncontinuous load + (1.25 × continuous load); e.g., 40 A continuous × 1.25 = 50 A; 100 A cont. × 1.25 + 30 A noncont. = 155 A
Minimum overcurrent device rating for continuous plus noncontinuous load (device not 100% rated)OCPD ≥ noncontinuous + (1.25 × continuous), then round up to next standard size per 240.6(A); e.g., 80 + (60×1.25) = 155 A → 175 A; 10 + (30×1.25) = 47.5 A → 50 A
Generator output conductor minimum ampacityAmpacity ≥ 1.15 × generator nameplate current; 180 A × 1.15 = 207 A; 80 A × 1.15 = 92 A; 200 A × 1.15 = 230 A (exception: 100% permitted where design/operation prevents overloading)
Single continuous-duty motor branch-circuit conductor ampacityAmpacity ≥ 1.25 × full-load current from Table 430.248 (use table value, not nameplate); 65 A × 1.25 = 81.25 A
Feeder ampacity for multiple motorsNEC 430.24: (125% × largest motor FLC) + sum of other motor FLCs; (1.25 × 15.2) + 15.2 + 15.2 = 49.4 A
Motor overload protection maximum (430.32(A)(1))Separate overload device ≤ 125% × nameplate FLC for motors with a marked service factor ≥ 1.15 or marked temperature rise ≤ 40°C; ≤ 115% × nameplate FLC for all other motors. These are maximums, not a range: 30 A → 37.5 A max (service factor 1.15) or 34.5 A max (other motors)
Inverse-time circuit breaker maximum for motor that will not startSingle-phase: 250% of FLC standard (50 A × 2.5 = 125 A, next standard size 150 A if it won't start); absolute maximum 400% of FLC for currents of 100 A or less (60 A × 4 = 240 A)
Hermetic motor-compressor conductors and OCPDConductors ≥ 1.25 × RLA (30 × 1.25 = 37.5 A; 20 × 1.25 = 25 A); OCPD ≤ 1.75 × RLA (30 × 1.75 = 52.5 A → next standard 60 A; 20 × 1.75 = 35 A), max 225% of RLA under Exception No. 2
Conduit fill limits (Chapter 9, Table 1)1 conductor = 53%; 2 conductors = 31%; over 2 conductors = 40% of cross-sectional area; fill % = total conductor area ÷ conduit internal area (e.g., three 0.25 in conductors: 0.147 in² ÷ 0.785 in² ≈ 18.8% < 40%)
Dwelling general load calculation (Article 220)Total VA = (sq ft × 3 VA/sq ft) + (number of small-appliance circuits × 1500 VA) + (number of laundry circuits × 1500 VA); e.g., 2000 sq ft: 6000 + 3000 + 1500 = 10,500 VA; multiply per-unit total by number of units for multifamily before demand factors
Apparent power from real power and power factorS (kVA) = P (kW) ÷ PF; 200 kW ÷ 0.8 = 250 kVA (three-phase power P = √3 × V × I × cos θ)
Off-grid battery bank capacity and DC disconnect sizingBattery kWh = daily energy ÷ (DoD × efficiency) = 5 ÷ (0.5 × 0.85) = 11.76 kWh; DC disconnect ≥ 1.25 × max current = 30 × 1.25 = 37.5 A → 40 A standard size
Grounded conductor size for service conductors run in parallel (one set per raceway)Size per raceway from the ungrounded conductors in that raceway, not from the combined total: 350 kcmil copper → 2 AWG per Table 250.102(C)(1), but NEC 250.24(C)(2) sets a 1/0 AWG minimum in each raceway → 1/0 AWG copper
Total ampacity of parallel conductor setsTotal = per-set ampacity × number of sets; Table 310.16 90°C column, 350 kcmil copper = 350 A × 2 sets = 700 A