Exam Cheat Sheet · Quick Reference

Texas Maintenance Electrician

Texas  ·  PSI Services Contractor

Verified, not estimated. Every figure below is drawn from the official exam structure we maintain — question counts, passing standard and topic weighting. Practice questions are grounded in the source law with statute citations. We omit any figure we can't verify rather than guess at it.
Total questions
60
Passing score
70%
Exam time
180 min
Administered by
PSI Services Contractor
Format
Reference materials allowed

Texas State Portion 60 questions

Definitions, Calculations, Theory, and Plans 5 Q · 8%
Branch-circuit, feeder, and service load calculations using demand factors and unit loadsGrounding and bonding requirements including electrode systems, conductor sizing, and bonding jumpersOvercurrent protection device ratings, locations, and conductor protection rulesNEC code arrangement, mandatory vs. permissive language, and authority having jurisdiction enforcementGFCI and AFCI protection requirements by location and occupancy typeDwelling unit and non-dwelling receptacle and lighting outlet placement requirementsService entrance conductor sizing, clearances, disconnecting means ratings, and overcurrent protectionUnits of measurement, voltage standards, and rounding rules for electrical calculations
Electrical Services, Service Equipment, and Separately Derived Systems 8 Q · 13%
Service conductor types, sizing, and ampacity requirements (overhead and underground)Service disconnecting means: location, rating, number, and groupingOvercurrent protection for service conductors and equipment (including ground-fault protection)Grounding and bonding of service-supplied AC systems (grounding electrode system, main bonding jumper, grounding electrode conductor sizing)Separately derived systems: grounding, bonding, and system bonding jumper requirementsService entrance conductor wiring methods, clearances, and physical protectionSwitchboards, switchgear, and panelboards used as service equipment (ratings, overcurrent protection, grounding, markings)Surge-protective devices and emergency disconnects for services
Electrical Feeders 3 Q · 5%
Minimum feeder conductor ampacity for continuous and noncontinuous loads (125% rule)Feeder overcurrent protection requirements and ratingsFeeder load calculations including demand factors for dwelling units, multifamily, and commercial occupanciesFeeder conductor size and ampacity correction/adjustment factorsGround-fault protection of equipment for feeders rated 1000 amperes or moreFeeder equipment grounding conductor and grounded conductor requirementsSurge-protective device (SPD) requirements for feeders supplying dwelling and sleeping unitsFeeder conductor identification for grounded, ungrounded, and equipment grounding conductors
Branch Circuit Calculations and Conductors 10 Q · 17%
Minimum conductor ampacity and sizing for branch circuits (continuous vs. noncontinuous loads, 125% rule)Overcurrent protection ratings and sizing for branch circuits (Articles 210.20, 240.4, 240.6)Conductor ampacity tables and correction/adjustment factors (Tables 310.16, 310.17, ambient temperature and bundling derating)GFCI protection requirements by location for dwelling and non-dwelling occupancies (Article 210.8)AFCI protection requirements by occupancy and location (Article 210.12)Branch circuit load calculations for dwelling and non-dwelling units (Articles 220.41, 220.42, demand factors)Multiwire branch circuit requirements including disconnecting means and line-to-neutral loads (Article 210.4)Branch circuit ratings, permissible loads, and receptacle ratings by circuit size (Articles 210.18–210.24)
Electrical Wiring Methods and Electrical Materials 9 Q · 15%
Conductor ampacity tables and temperature rating correction factorsPhysical protection of cables and raceways through and parallel to framing membersUnderground installation requirements and minimum burial depthsPermitted and prohibited uses of cable types (NM, NMC, AC, MC, MI, SE, USE, UF)Securing and supporting intervals for cables and racewaysConductor insulation types, markings, and application requirementsWiring in ducts, plenums, and air-handling spacesProtection against corrosion and dissimilar metals in raceways and fittings
Electrical Equipment and Devices 10 Q · 17%
Switch types, ratings, and permitted uses (Articles 404.14, 404.11)Receptacle installation requirements, grounding, and replacement rules (Article 406)Panelboard, switchboard, and switchgear installation and overcurrent protection (Article 408)Motor circuit conductors, overload protection, and disconnecting means (Article 430)Luminaire installation locations, support, grounding, and wiring requirements (Article 410)Air-conditioning and refrigerating equipment branch circuits, disconnecting means, and overload protection (Article 440)Transformer installation, overcurrent protection, and vault requirements (Article 450)Generator installation, overcurrent protection, and disconnecting means (Article 445)
Motors and Generators 4 Q · 7%
Motor branch-circuit conductor sizing and ampacity requirements (430.22, 430.24)Motor branch-circuit short-circuit and ground-fault protective device ratings and types (430.52, Table 430.52(C)(1))Motor overload protection requirements and trip current percentages (430.32)Motor disconnecting means types, location, and current rating requirements (430.102, 430.109, 430.110)Motor controller ratings, markings, and application requirements (430.83, 430.8)Generator installation requirements including overcurrent protection, conductor ampacity, and disconnecting means (445.12, 445.13, 445.18)Motor nameplate markings and locked-rotor code letters (430.7, Table 430.7(B))Several motors on one branch circuit and feeder protection requirements (430.53, 430.62)
Electrical Control Devices and Disconnecting Means 3 Q · 5%
Switch connection requirements and grounded conductor rules (Article 404.2)Rating and use of switches for specific load types (Article 404.14)Motor disconnecting means location, type, and rating requirements (Article 430, Part IX)Service disconnecting means requirements including location, rating, and number of disconnects (Article 230, Part VI)Circuit breaker and switch enclosure requirements for damp/wet locations and accessibility (Articles 404.3, 404.4, 404.8)Motor controller types, ratings, and disconnecting means (Articles 430.83, 430.109, 430.111)Panelboard and switchboard overcurrent protection and disconnecting requirements (Article 408)Industrial control panel disconnecting means and overcurrent protection (Article 409)
Special Occupancies, Equipment, and Conditions 8 Q · 13%
Classification of hazardous locations by Class (I, II, III) and Division (1 and 2)Protection techniques for hazardous classified locations (explosionproof, dust-ignitionproof, intrinsic safety, purged/pressurized, etc.)Wiring methods permitted in Class I, II, and III Division 1 and 2 locationsSealing and drainage requirements for conduit and cable systems in hazardous locationsEquipment marking requirements including class, division, material group, and temperature class (T codes)Grounding and bonding requirements in hazardous classified locationsSpecial occupancy requirements for commercial garages, aircraft hangars, motor fuel dispensing facilities, and bulk storage plantsIntrinsically safe systems installation, separation, and identification requirements

Key Distinctions

Type SHD portable power feeder cablevsType G portable power feeder cable

Type SHD is rated 2001–25,000 volts with three power conductors individually covered with insulation, tape and shielding plus grounding conductors, while Type G is rated 2001–5000 volts without individual conductor shielding (Type SH uses an overall shield instead of individual shields).

NEC 2026 Table 400.50
Class I, Division 1 locationvsClass II, Division 1 location

Class I, Division 1 is hazardous because ignitible concentrations of flammable gases or flammable/combustible liquid-produced vapors can exist under normal operating conditions, while Class II, Division 1 is hazardous because combustible dust is in the air under normal operating conditions in quantities sufficient to produce explosive or ignitible mixtures.

NEC 2026 Section 500.5
Continuous loadvsNoncontinuous load

Continuous load is taken at 125 percent when sizing branch-circuit conductors, feeder conductors/overcurrent devices, and service-entrance conductors, while noncontinuous load is taken at 100 percent.

NEC 2026 Section 210.19
Minimum cover 300 mm (12 in.) for direct burial (residential 120 V or less branch circuits with GFCI protection and max 20 A overcurrent protection)vsMinimum cover 600 mm (24 in.) for direct burial

Per Table 300.5(A), Column 4 — residential branch circuits rated 120 volts or less with GFCI protection and a maximum overcurrent protection of 20 amperes — needs only 300 mm (12 in.) of cover in general locations, whereas direct-buried cables/conductors (Column 1) in locations not otherwise specified require 600 mm (24 in.).

NEC 2026 Table 300.7(A)
Type SPT-1 flexible cordvsType C lamp cord

Type SPT-1 (all-thermoplastic parallel cord for pendant or portable use in damp locations, not hard usage) has a maximum rating of 300 volts, while Type C lamp cord is 300 volts in 18–16 AWG and up to 600 volts in 15–10 AWG.

NEC 2026 Table 400.4
Manufactured wiring system cable conductorsvsLuminaire tap in a manufactured wiring system

Cables must contain nominal 600-volt, 8 AWG to 12 AWG conductors (12 AWG minimum), but a luminaire tap no longer than 1.8 m (6 ft) intended for a single luminaire is permitted to be smaller than 12 AWG down to 18 AWG.

NEC 2026 Section 604.100
NEC Chapters 1 through 7vsNEC Chapter 8 (communications systems)

Chapters 1–4 apply generally and Chapters 5–7 apply to special conditions, but Chapter 8 is not subject to the requirements of Chapters 1 through 7 except where specifically referenced in Chapter 8.

NEC 2026 Section 90.3
Installations covered by the NECvsInstallations excluded from NEC scope

The Code does not cover ships, watercraft other than floating buildings, railway rolling stock, aircraft, or automotive vehicles, but it does cover mobile homes and recreational vehicles.

NEC 2026 Section 90.2
General rule: all conductors of a circuit in the same racewayvsParalleled installations

All conductors of the same circuit, the grounded conductor, and all equipment grounding/bonding conductors must be in the same raceway, conduit body, auxiliary gutter, cable tray, cablebus, trench, cable, or cord, except that conductors run in parallel may be distributed among multiple raceways with the rule applied separately to each portion of the paralleled installation.

NEC 2026 Section 300.5(B)
Wiring methods requiring steel plate protectionvsWiring methods exempt in notched wood members

Where the required 32 mm (1-1/4 in.) distance cannot be maintained, cables and raceways must be protected by a steel plate at least 1.6 mm (1/16 in.) thick, but rigid metal conduit, intermediate metal conduit, PVC, and EMT installed in notches in wood members are exempt from that plate requirement.

NEC 2026 Section 300.6(A)(1)
Conductor sizing for a hermetic motor-compressorvsOvercurrent device sizing for a hermetic motor-compressor

Branch-circuit conductors must be at least 125 percent of the rated-load current (440.32), while the branch-circuit protective device must not exceed 175 percent of the RLA (440.22(A)), with the next higher standard size permitted (Exception No. 1) and a maximum of 225 percent if starting current still cannot be carried (Exception No. 2).

NEC 2026 Section 440.22(A), 440.32
Real power (kW)vsApparent power (kVA)

Real power is P = √3 × V × I × cos θ in a three-phase system, while apparent power S = P ÷ PF; raising power factor at constant voltage and current increases real power but leaves apparent power unchanged.

Key Terms

Mandatory rule NEC 2026 Section 90.5
A rule identifying actions specifically required or prohibited, characterized by use of the terms 'shall' or 'shall not.'
Type SHD cable NEC 2026 Table 400.50
A portable power feeder cable rated 2001–25,000 volts with three round power conductors each individually covered with insulation, tape, and shielding, plus grounding conductors.
Class A GFCI NEC 2026 Section 210.8
The listed ground-fault circuit interrupter type required to provide personnel protection in the locations specified by 210.8.
Multiwire branch circuit load limitation NEC 2026 Section 210.4
Multiwire branch circuits shall supply only line-to-neutral loads unless an exception applies, such as supplying only one utilization equipment or where all ungrounded conductors are opened simultaneously.
Simultaneous disconnect for multiwire branch circuits NEC 2026 Section 210.4
Each multiwire branch circuit must be provided with a means that will simultaneously disconnect all ungrounded conductors at the point where the branch circuit originates.
Free conductor length NEC 2026 Section 300.16
At least 150 mm (6 in.) of free conductor, measured from where it emerges from the raceway or cable sheath in the box, must be left at each outlet, junction, and switch point for splices or connections.
Small-appliance branch circuit NEC 2026 Section 210.11
In dwelling units, two or more 20-ampere circuits that must be provided, in addition to other required branch circuits, for the receptacle outlets specified in 210.52(B).
Standard branch-circuit ratings (other than individual branch circuits) NEC 2026 Section 210.18
The recognized ratings are 10, 15, 20, 30, 40, and 50 amperes (10 amperes is explicitly included in the 2023 NEC); 25 and 60 amperes are not recognized.
Induction heating (grouping requirement) NEC 2026 Section 300.22(A)
Where ac conductors are installed in ferrous metal enclosures or raceways, all phase conductors and the grounded conductor must be grouped together to avoid heating the surrounding ferrous metal by induction.
Main bonding jumper identification NEC 2026 Section 250.28
If a main bonding jumper or system bonding jumper is a screw only, the screw must be identified with a green finish that is visible with the screw installed.
Objectionable current (permitted alterations) NEC 2026 Section 250.6
Where multiple grounding or bonding connections cause objectionable current and 250.4(A)(5) or (B)(4) is met, one or more (but not all) connections may be discontinued or the locations of the connections may be changed, keeping at least one connection.
Reconditioned transfer switch NEC 2026 Section 700.3
Prohibited outright in emergency systems—reconditioned transfer switches shall not be installed, with no exception for testing or certification.
Class I, Division 1 location NEC 2026 Section 500.5
A location in which ignitible concentrations of flammable gases, flammable liquid-produced vapors, or combustible liquid-produced vapors can exist under normal operating conditions.
Class II, Division 1 location NEC 2026 Section 500.5
A location in which combustible dust is in the air under normal operating conditions in quantities sufficient to produce explosive or ignitible mixtures.
Warning ribbon (underground service conductors) NEC 2026 Section 300.7(D)(3)
Underground service conductors not encased in concrete and buried 450 mm (18 in.) or more below grade must have their location identified by a warning ribbon placed in the trench at least 300 mm (12 in.) above the installation.
Receptacle outlet load allowance NEC 2026 Section 120.14(I)
Receptacle outlets are calculated at not less than 180 volt-amperes for each single or each multiple receptacle on one yoke.

Formulas to Know

Minimum ampacity/overcurrent rating for continuous plus noncontinuous loads (branch circuit, feeder, service-entrance)Minimum = noncontinuous load + (1.25 × continuous load); e.g., branch circuit 40 A cont. + 10 A noncont. = (40 × 1.25) + 10 = 60 A; feeder 100 A cont. + 30 A noncont. = (100 × 1.25) + 30 = 155 A; service 80 A cont. + 60 A noncont. = (80 × 1.25) + 60 = 160 A
Next standard overcurrent device size after a continuous/noncontinuous feeder calculation30 A + (50 A × 1.25) = 92.5 A; since 92.5 A is not a standard rating, per 240.6(A) use the next standard size at or above it = 100 A
Minimum ampacity of conductors from generator terminals to first overcurrent deviceAmpacity ≥ 1.15 × generator nameplate current; 180 A × 1.15 = 207 A; 80 A × 1.15 = 92 A; 200 A × 1.15 = 230 A
Hermetic refrigerant motor-compressor conductors and branch-circuit OCPDConductors ≥ 1.25 × RLA (30 A → 37.5 A; 20 A → 25 A); OCPD ≤ 1.75 × RLA (30 A → 52.5 A, next higher standard 60 A permitted; 20 A → 35 A), and only if starting current still cannot be carried may it go to a maximum of 2.25 × RLA
Motor overload protection maximum (430.32(A)(1))Separate overload device ≤ 125% × nameplate FLC for motors with a marked service factor ≥ 1.15 or marked temperature rise ≤ 40°C; ≤ 115% × nameplate FLC for all other motors. These are maximums, not a range: 30 A → 37.5 A max (service factor 1.15) or 34.5 A max (other motors)
Maximum inverse-time circuit breaker rating for a motorSingle-phase motor: 250% of FLC (50 A × 2.5 = 125 A), and if the motor fails to start, go to the next higher standard size (150 A); for FLC of 100 A or less the increase for starting shall not exceed 400% of FLC (60 A × 4 = 240 A maximum)
Minimum feeder conductor ampacity for several motors(1.25 × largest motor FLC) + sum of the other motors' FLC; three 5 HP motors at 15.2 A: (15.2 × 1.25) + 15.2 + 15.2 = 19 + 30.4 = 49.4 A
Dwelling general lighting and circuit load calculation (Article 220; Article 120 in NEC 2026)Total VA = (area in sq ft × 3 VA/sq ft) + (1500 VA × number of small-appliance circuits) + 1500 VA laundry circuit; e.g., 2000 sq ft dwelling = 6000 + 3000 + 1500 = 10,500 VA; 1200 sq ft unit = 3600 + 3000 + 1500 = 8100 VA × 4 units = 32,400 VA. Dwelling units only; a retail store uses the Table 120.42(A) unit load, 1.9 VA/sq ft, plus 180 VA per receptacle outlet (3,500 sq ft → 6,650 VA of general lighting)
Three-phase power and apparent powerP = √3 × V × I × cos θ; S (kVA) = P (kW) ÷ PF, e.g., 200 kW ÷ 0.8 = 250 kVA
Inductive reactanceXL = 2πfL (f = frequency, L = inductance); XL = 2πfC is incorrect