Exam Cheat Sheet · Quick Reference
Texas - Residential Appliance Installer
Texas · PSI Services Contractor
Texas State Portion 80 questions
Key Distinctions
Mandatory rules use 'shall' or 'shall not' and identify actions specifically required or prohibited, while permissive rules allow but do not require certain actions.
NEC 90.5(A)Grounded (neutral) conductor terminals are identified by white or silver color, while equipment grounding conductors in flexible cords are identified by continuous green or green with one or more yellow stripes.
NEC 200.9Dwelling units require GFCI for 125V–250V receptacles in bathrooms, garages, outdoors, crawl spaces, basements, kitchens, and laundry areas; non-dwelling locations require GFCI for rooftops, outdoors, and other specified areas, with amperage limits of 50A single-phase and 100A three-phase.
NEC 210.8(A)When only 2 conductors are installed in a conduit, maximum fill is 31% of cross-sectional area, whereas 3 or more conductors allows up to 40%.
Table 1, Chapter 9Standard conduit fill is limited to 31–40% depending on conductor count, but conduit nipples not exceeding 600 mm (24 in.) between boxes are permitted to be filled to 60% of total cross-sectional area.
Table 1, Chapter 9Chapters 1–4 apply generally to all electrical installations, while Chapter 8 covers communications systems and is NOT subject to Chapters 1–7 except where specifically referenced in Chapter 8.
Article 90.3Chapters 1–4 apply to all installations broadly, while Chapters 5, 6, and 7 apply to special occupancies, equipment, or conditions and may supplement or modify Chapters 1–4.
Article 90.3A receptacle supplying only a permanently installed premises security system may omit GFCI to prevent nuisance tripping from disabling security; listed WSCRs used with compatible WSAFs may also omit GFCI unless they include an integral general-purpose convenience receptacle.
NEC 210.8(A) Exception No. 2SI units appear first in the NEC as the measurement system of preference per 90.9(A), with inch-pound units immediately following in parentheses, and when a difference exists between the two, the inch-pound measurement governs.
NEC 90.9(A), 90.9(B)The continuity of a grounded conductor must be maintained through direct electrical connections and shall not depend on connection to a metal enclosure, raceway, or cable armor.
NEC 200.2(B)For screw shell devices, the terminal connected to the screw shell is designated for the grounded conductor, ensuring correct polarity.
NEC 200.10(C)NEC 210.8 requires GFCI for receptacles in numerous specified locations, while 210.8(C) separately requires GFCI for lighting outlets not exceeding 120 volts installed in crawl spaces.
NEC 210.8(C)Key Terms
Formulas to Know
Max fill = 53% of conduit internal cross-sectional area (1 conductor)Max fill = 31% of conduit internal cross-sectional area (2 conductors)Max fill = 40% of conduit internal cross-sectional area (3+ conductors)Max fill = 60% of conduit internal cross-sectional area (nipple ≤ 600 mm / 24 in.)Area = π × (diameter / 2)²Total fill area = Sum of cross-sectional areas of all conductors installedFill % = (Total conductor area ÷ Conduit interior area) × 100 — must not exceed allowed %I (amperes) = V (volts) ÷ R (ohms)P (watts) = V (volts) × I (amperes)Load (VA) = Voltage × Amperage; must not exceed 80% of breaker rating for continuous loads