Exam Cheat Sheet · Quick Reference
Texas Residential Appliance Installer
Texas · PSI Services Contractor
Texas State Portion 80 questions
Key Distinctions
In dwelling units GFCI is required for 125-volt through 250-volt receptacles in listed areas (bathrooms, garages, outdoors, crawl spaces, basements, kitchens, areas with sinks, laundry areas, etc.) on single-phase circuits rated 150 volts or less to ground, while in other than dwelling units it is required for receptacles within 1.8 m (6 ft) of the top inside edge of a sink bowl, on single-phase circuits 150 volts or less to ground and 50 A or less or three-phase circuits 150 volts or less to ground and 100 A or less.
NEC 2026 Section 210.8Per Article 90.3, Chapters 1–4 apply generally to all electrical installations; Chapters 5, 6, and 7 cover special occupancies, equipment, or conditions and may supplement or modify Chapters 1–4, while Chapter 8 (communications systems) is not subject to Chapters 1–7 except where specifically referenced.
NEC 2026 Section 90.3Per 90.9(A) and (B), SI (metric) is the Code's measurement system of preference and SI units appear first, with inch-pound units immediately following in parentheses.
NEC 2026 Section 90.9Chapter 9, Table 1 permits 31% fill for 2 conductors and 40% for 3 or more (53% for 1 conductor), while Note (4) permits nipples not exceeding 600 mm (24 in.) between boxes to be filled to 60%.
NEC 2026 Chapter 9, Table 1Grounded conductors 6 AWG or smaller use a continuous white or gray outer finish (white or silver terminals, or 'white'/'W'), while an equipment grounding conductor in a flexible cord must be continuous green or green with one or more yellow stripes and must not be used for other purposes.
NEC 2026 Section 200.7(A)Nonmetallic-sheathed cable run parallel to framing members less than 32 mm (1¼ in.) from the edge (or in notches) must be protected by a steel plate at least 1.6 mm (1/16 in.) thick, while rigid metal conduit, intermediate metal conduit, rigid nonmetallic conduit, and electrical metallic tubing are not required to have steel plate protection.
NEC 2026 Section 300.6(D)NEC 300.14 requires at least 150 mm (6 in.) of free conductor measured from where it emerges from the raceway or cable sheath at each outlet, junction, and switch point; additionally, where the opening is less than 200 mm (8 in.) in any dimension, each conductor must extend at least 75 mm (3 in.) outside the opening.
NEC 2026 Section 300.16A single-motor branch circuit is sized at 125% of the motor full-load current (430.22), while a feeder to several motors is sized at 125% of the largest motor's FLC plus the sum of the full-load currents of the remaining motors (430.24).
NEC 2026 Section 430.22, Table 430.248Branch-circuit conductors must have ampacity of at least 125% of the rated-load current, while the branch-circuit protective device must not exceed 175% of RLA (next higher standard size permitted by Exception No. 1, and up to 225% of RLA under Exception No. 2 if needed to carry starting current).
NEC 2026 Section 440.22(A), 440.32Table 430.52 permits a maximum of 250% of full-load current for a single-phase motor's inverse time breaker, but where the motor fails to start, the rating may be increased to the next higher standard size and in no case over 400% of FLC for currents of 100 A or less.
NEC Section 430.52(C)(1), Exception No. 2; Table 430.52(C)(1)Ordinary motor branch-circuit conductors are 125% of FLC, but per 430.22(C) conductors between the controller and a wye-start, delta-run motor need be only 72% of the motor full-load current (58% of load current × 1.25).
NEC 2026 Section 430.22, Table 430.248Per 220.14(I), each single or multiple receptacle on one yoke is calculated at not less than 180 volt-amperes, but a single piece of equipment consisting of a multiple receptacle of four or more receptacles is calculated at not less than 90 volt-amperes per receptacle.
NEC 2026 Section 120.14(I)In a three-phase system with voltage and current held constant, raising the power factor increases real power (P = √3 × V × I × cos θ) while apparent power, the vector sum of real and reactive power, remains unchanged.
Key Terms
Formulas to Know
Minimum ampacity = 125% × motor FLC from Table 430.248; e.g., 10 HP, 230 V single-phase FLC 50 A → 50 × 1.25 = 62.5 A(125% × largest motor FLC) + sum of remaining motor FLCs; e.g., three 15.2 A motors → (1.25 × 15.2) + 15.2 + 15.2 = 19 + 30.4 = 49.4 AConductors ≥ 125% × RLA (30 A → 37.5 A; 20 A → 25 A); OCPD ≤ 175% × RLA (30 A → 52.5 A, round up to next standard 60 A; 20 A → 35 A), and only if starting current cannot be carried may it go to a maximum 225% of RLASingle-phase motor: 250% × FLC (50 A → 125 A); if the motor fails to start, go to the next higher standard size (150 A), but in no case over 400% of FLC for currents of 100 A or less (60 A × 400% = 240 A max)Separate overload device ≤ 125% × nameplate FLC for motors with a marked service factor ≥ 1.15 or marked temperature rise ≤ 40°C; ≤ 115% × nameplate FLC for all other motors. These are maximums, not a range: 30 A → 37.5 A max (service factor 1.15) or 34.5 A max (other motors)Ampacity ≥ 72% × motor FLC (from 58% of load current × 1.25 = 72%)100% of first 10 kVA + 40% of remainder; 28 kVA → 10 + (18 × 0.40) = 10 + 7.2 = 17.2 kVA100% of heat pump compressor + 65% of supplemental electric heating; 5 kVA + (0.65 × 10 kVA) = 11.5 kVA150 VA for every 600 mm (2 ft) of track or fraction thereof; 15 ft ÷ 2 = 7.5 → 8 increments × 150 VA = 1,200 VATwo resistors in parallel: Rp = (R1 × R2)/(R1 + R2); n equal resistors in parallel: R ÷ n; add series resistances: RT = R1 + Rp (+R4); then I = E ÷ RT, and branch voltage = I × Rp with branch current = Vp ÷ Rbranch