Exam Cheat Sheet · Quick Reference

Texas Residential Appliance Installer

Texas  ·  PSI Services Contractor

Verified, not estimated. Every figure below is drawn from the official exam structure we maintain — question counts, passing standard and topic weighting. Practice questions are grounded in the source law with statute citations. We omit any figure we can't verify rather than guess at it.
Total questions
80
Passing score
70%
Exam time
240 min
Administered by
PSI Services Contractor
Format
Reference materials allowed

Texas State Portion 80 questions

Definitions, Calculations, and Theory 12 Q · 15%
Code DefinitionsGeneral Electrical CalculationsNEC purpose and scope of practical safeguardingBranch-circuit load calculations for dwelling unitsFeeder and service load calculations using demand factorsDemand factors for specific appliances (ranges, dryers, cooking equipment)Optional load calculation methods for dwelling and multifamily unitsNominal voltages and rounding of ampere calculationsMandatory versus permissive rule language (shall vs. shall be permitted)Units of measurement: SI and inch-pound dual system
GFCI Protection and Equipment Grounding and Bonding 15 Q · 19%
GFCI ProtectionEquipment Grounding and BondingEquipotential Bonding
Electrical Wiring Methods and Electrical Materials 10 Q · 12%
RacewaysBoxes and EnclosuresCables, Flexible Cords, and Conductors
Electrical Equipment and Devices 15 Q · 19%
Receptacles, Switches, and DevicesAppliancesWorkspace ClearanceUtilization Equipment
Motors 5 Q · 6%
Electric MotorsMotor branch-circuit conductor sizing and ampacity requirementsMotor overload protection devices and trip current ratingsBranch-circuit short-circuit and ground-fault protective device ratingsMotor disconnecting means types, ratings, and location requirementsMotor controller ratings, markings, and application requirementsMotor nameplate markings and locked-rotor code lettersFeeder conductor sizing and protection for multiple motorsMotor grounding and protection of live parts
Electrical Control Devices and Disconnecting Means 5 Q · 6%
Controllers, Switches, and DisconnectsSwitch types, ratings, and permitted uses (AC/DC snap switches, dimmers, CO/ALR, dimmer/electronic control)Disconnecting means location, type, and rating requirements for motors and motor controllersService disconnecting means requirements including rating, location, and number of disconnectsOvercurrent protection devices including fuses, circuit breakers, and standard ampere ratingsSwitch installation requirements including accessibility, height limitations, enclosures, and wet/damp locationsMotor branch-circuit short-circuit and ground-fault protection ratings and device selectionPanelboard and switchboard overcurrent protection, marking, and grounding requirementsIndustrial control panel disconnecting means, overcurrent protection, and short-circuit current ratings
Swimming Pools, Spas, and Fountain Equipment 18 Q · 22%
Pool Equipment HeaterPool CoverPool LuminairesPumpsVertical ClearanceHorizontal ClearanceHot Tubs and SpasFountain Equipment

Key Distinctions

GFCI in dwelling units — NEC 210.8(A)vsGFCI in other than dwelling units — NEC 210.8(B)

In dwelling units GFCI is required for 125-volt through 250-volt receptacles in listed areas (bathrooms, garages, outdoors, crawl spaces, basements, kitchens, areas with sinks, laundry areas, etc.) on single-phase circuits rated 150 volts or less to ground, while in other than dwelling units it is required for receptacles within 1.8 m (6 ft) of the top inside edge of a sink bowl, on single-phase circuits 150 volts or less to ground and 50 A or less or three-phase circuits 150 volts or less to ground and 100 A or less.

NEC 2026 Section 210.8
Chapters 1 through 4vsChapters 5, 6, 7 and Chapter 8

Per Article 90.3, Chapters 1–4 apply generally to all electrical installations; Chapters 5, 6, and 7 cover special occupancies, equipment, or conditions and may supplement or modify Chapters 1–4, while Chapter 8 (communications systems) is not subject to Chapters 1–7 except where specifically referenced.

NEC 2026 Section 90.3
SI (metric) unitsvsInch-pound units

Per 90.9(A) and (B), SI (metric) is the Code's measurement system of preference and SI units appear first, with inch-pound units immediately following in parentheses.

NEC 2026 Section 90.9
Conduit fill for 2 conductorsvsConduit fill for 3 or more conductors (and nipples)

Chapter 9, Table 1 permits 31% fill for 2 conductors and 40% for 3 or more (53% for 1 conductor), while Note (4) permits nipples not exceeding 600 mm (24 in.) between boxes to be filled to 60%.

NEC 2026 Chapter 9, Table 1
Grounded (neutral) conductor identificationvsEquipment grounding conductor identification

Grounded conductors 6 AWG or smaller use a continuous white or gray outer finish (white or silver terminals, or 'white'/'W'), while an equipment grounding conductor in a flexible cord must be continuous green or green with one or more yellow stripes and must not be used for other purposes.

NEC 2026 Section 200.7(A)
Wiring methods requiring steel plate protectionvsWiring methods exempt from steel plate protection

Nonmetallic-sheathed cable run parallel to framing members less than 32 mm (1¼ in.) from the edge (or in notches) must be protected by a steel plate at least 1.6 mm (1/16 in.) thick, while rigid metal conduit, intermediate metal conduit, rigid nonmetallic conduit, and electrical metallic tubing are not required to have steel plate protection.

NEC 2026 Section 300.6(D)
6 in. of free conductor at each outletvs3 in. of conductor outside a small opening

NEC 300.14 requires at least 150 mm (6 in.) of free conductor measured from where it emerges from the raceway or cable sheath at each outlet, junction, and switch point; additionally, where the opening is less than 200 mm (8 in.) in any dimension, each conductor must extend at least 75 mm (3 in.) outside the opening.

NEC 2026 Section 300.16
Motor branch-circuit conductor sizingvsMotor feeder conductor sizing

A single-motor branch circuit is sized at 125% of the motor full-load current (430.22), while a feeder to several motors is sized at 125% of the largest motor's FLC plus the sum of the full-load currents of the remaining motors (430.24).

NEC 2026 Section 430.22, Table 430.248
Hermetic motor-compressor conductors (440.32)vsHermetic motor-compressor OCPD (440.22(A))

Branch-circuit conductors must have ampacity of at least 125% of the rated-load current, while the branch-circuit protective device must not exceed 175% of RLA (next higher standard size permitted by Exception No. 1, and up to 225% of RLA under Exception No. 2 if needed to carry starting current).

NEC 2026 Section 440.22(A), 440.32
Standard inverse time breaker settingvsIncreased setting for starting

Table 430.52 permits a maximum of 250% of full-load current for a single-phase motor's inverse time breaker, but where the motor fails to start, the rating may be increased to the next higher standard size and in no case over 400% of FLC for currents of 100 A or less.

NEC Section 430.52(C)(1), Exception No. 2; Table 430.52(C)(1)
Standard motor branch-circuit conductors (125%)vsWye-start, delta-run conductors between controller and motor (72%)

Ordinary motor branch-circuit conductors are 125% of FLC, but per 430.22(C) conductors between the controller and a wye-start, delta-run motor need be only 72% of the motor full-load current (58% of load current × 1.25).

NEC 2026 Section 430.22, Table 430.248
Receptacle outlet load at 180 VA per yokevsMultiple receptacle of four or more at 90 VA each

Per 220.14(I), each single or multiple receptacle on one yoke is calculated at not less than 180 volt-amperes, but a single piece of equipment consisting of a multiple receptacle of four or more receptacles is calculated at not less than 90 volt-amperes per receptacle.

NEC 2026 Section 120.14(I)
Real (true) powervsApparent power

In a three-phase system with voltage and current held constant, raising the power factor increases real power (P = √3 × V × I × cos θ) while apparent power, the vector sum of real and reactive power, remains unchanged.

Key Terms

Mandatory rule (NEC 90.5(A)) NEC 2026 Section 90.5
A Code rule identifying an action that is specifically required or prohibited, characterized by the terms 'shall' or 'shall not'.
GFCI protection (NEC 210.8) NEC 2026 Section 210.8
A listed Class A ground-fault circuit interrupter that provides protection for personnel against ground faults, with distances measured as the shortest path the power supply cord would follow without piercing a floor, wall, ceiling, or fixed barrier.
GFCI for appliance outlets (NEC 210.8(D), 2023) NEC 2026 Section 210.8
Required protection for the branch circuit or outlet supplying listed appliances rated 150 volts or less to ground and 60 amperes or less, single- or 3-phase, including dishwashers, electric ranges, wall-mounted ovens, counter-mounted cooking units, clothes dryers, microwave ovens, and sump pumps.
Snow-melting equipment exception (NEC 210.8(A), Exception No. 1) NEC 2026 Section 210.8, Exception No. 1
Receptacles that are not readily accessible and are supplied by a branch circuit dedicated to electric snow-melting, deicing, or pipeline and vessel heating equipment are permitted without GFCI protection when installed per 426.28 or 427.22.
Ground-fault protection of equipment (NEC 210.13) NEC 2026 Section 210.13
Protection required for each branch-circuit disconnecting means rated 1000 amperes or more on solidly grounded wye systems of more than 150 volts to ground but not exceeding 1000 volts phase-to-phase, provided in accordance with 230.95.
Grounded conductor continuity (NEC 200.2(B)) NEC 2026 Section 200.4(B)
The continuity of a grounded conductor shall not depend on a connection to a metal enclosure, raceway, or cable armor; it must be maintained through direct electrical connections.
Screw shell device terminal (NEC 200.10(C)) NEC 2026 Section 200.10
On devices with screw shells, the terminal connected to the screw shell is the terminal that must be connected to the grounded conductor to ensure proper polarity.
Multiwire branch circuit disconnect (NEC 210.4(B)) NEC 2026 Section 210.4
Each multiwire branch circuit must be provided with a means that simultaneously disconnects all ungrounded conductors at the point where the branch circuit originates.
Small-appliance branch circuits (NEC 210.11(C)(1)) NEC 2026 Section 210.11
Two or more 20-ampere branch circuits that must be provided, in addition to other required circuits, for the receptacle outlets specified in 210.52(B).
AFCI protection in dwellings (NEC 210.12(B)) NEC 2026 Section 210.12
All 120-volt, single-phase, 10-, 15-, and 20-ampere branch circuits supplying outlets in bedrooms and other specified dwelling locations must be protected by any of the six means described in 210.12(A)(1) through (A)(6).
Chapter 3 wiring method voltage limit (NEC 300.2(A)) NEC 2026 Section 300.4(A)
Chapter 3 wiring methods are used for 1000 volts ac / 1500 volts dc nominal or less unless limited elsewhere, and are permitted over those values only where specifically permitted in the Code.
Bored holes in wood members (NEC 300.4(A)(1)) NEC 2026 Section 300.6(A)(1)
Holes for cable- or raceway-type wiring must be bored so the edge of the hole is not less than 32 mm (1¼ in.) from the edge of the wood member, otherwise a steel plate at least 1.6 mm (1/16 in.) thick is required.
Minimum cover, direct burial (NEC Table 300.5(A)) NEC 2026 Table 300.7(A)
For direct-buried cables or conductors in all locations not otherwise specified, the minimum cover is 600 mm (24 in.).
Underground warning ribbon (NEC 300.5(D)(3)) NEC 2026 Section 300.7(D)(3)
Underground service conductors not encased in concrete and buried 450 mm (18 in.) or more below grade must be identified by a warning ribbon placed in the trench at least 300 mm (12 in.) above the installation.
Direct-buried splices (NEC 300.5(E)) NEC 2026 Section 300.7(E)
Direct-buried conductors or cables are permitted to be spliced or tapped without splice boxes, provided the splices or taps are made in accordance with 110.14(B).
Conductor grouping in ferrous raceways (NEC 300.20(A)) NEC 2026 Section 300.22(A)
Where ac conductors are installed in ferrous metal enclosures or raceways, all phase conductors and, where used, the grounded conductor and all equipment grounding conductors must be grouped together to avoid inductive heating of the ferrous metal.
Motor disconnecting means (NEC 430.102(B)) NEC 2026 Section 430.102
Every motor disconnecting means must be capable of being locked in the open position, regardless of horsepower rating.
Cord-connected pool filter pump GFCI (NEC 680.31) NEC 2026 Section 680.31
Cord-connected pool filter pumps must have a GFCI that is integral to the attachment plug or located in the power-supply cord within 300 mm (12 in.) of the attachment plug.
Dwelling floor area for load calculation (NEC 220.5(C)) NEC 2026 Section 120.5(C)
Floor area computed from outside dimensions, excluding open porches and unfinished areas not adaptable for future use as a habitable room.
Inductive reactance
Opposition to ac from inductance, calculated as XL = 2πfL where f is frequency and L is inductance (not capacitance).

Formulas to Know

Single-motor branch-circuit conductor ampacityMinimum ampacity = 125% × motor FLC from Table 430.248; e.g., 10 HP, 230 V single-phase FLC 50 A → 50 × 1.25 = 62.5 A
Motor feeder conductor ampacity (NEC 430.24)(125% × largest motor FLC) + sum of remaining motor FLCs; e.g., three 15.2 A motors → (1.25 × 15.2) + 15.2 + 15.2 = 19 + 30.4 = 49.4 A
Hermetic motor-compressor conductors and OCPDConductors ≥ 125% × RLA (30 A → 37.5 A; 20 A → 25 A); OCPD ≤ 175% × RLA (30 A → 52.5 A, round up to next standard 60 A; 20 A → 35 A), and only if starting current cannot be carried may it go to a maximum 225% of RLA
Inverse time circuit breaker maximum ratingSingle-phase motor: 250% × FLC (50 A → 125 A); if the motor fails to start, go to the next higher standard size (150 A), but in no case over 400% of FLC for currents of 100 A or less (60 A × 400% = 240 A max)
Motor overload protection maximum (430.32(A)(1))Separate overload device ≤ 125% × nameplate FLC for motors with a marked service factor ≥ 1.15 or marked temperature rise ≤ 40°C; ≤ 115% × nameplate FLC for all other motors. These are maximums, not a range: 30 A → 37.5 A max (service factor 1.15) or 34.5 A max (other motors)
Wye-start, delta-run conductors between controller and motorAmpacity ≥ 72% × motor FLC (from 58% of load current × 1.25 = 72%)
Optional dwelling general load (NEC 220.82(B))100% of first 10 kVA + 40% of remainder; 28 kVA → 10 + (18 × 0.40) = 10 + 7.2 = 17.2 kVA
Heat pump with supplemental heat, optional method (NEC 220.82(C)(3))100% of heat pump compressor + 65% of supplemental electric heating; 5 kVA + (0.65 × 10 kVA) = 11.5 kVA
Lighting track load (NEC 220.46(B))150 VA for every 600 mm (2 ft) of track or fraction thereof; 15 ft ÷ 2 = 7.5 → 8 increments × 150 VA = 1,200 VA
Series-parallel resistance and Ohm's lawTwo resistors in parallel: Rp = (R1 × R2)/(R1 + R2); n equal resistors in parallel: R ÷ n; add series resistances: RT = R1 + Rp (+R4); then I = E ÷ RT, and branch voltage = I × Rp with branch current = Vp ÷ Rbranch