ICC G21 Low-Voltage Electrician Exam (2017 NEC)
National · Pearson Vue
National State Portion 50 questions
Key Distinctions
Per Article 100, the main bonding jumper is the connection between the grounded circuit conductor and the equipment grounding conductor at the service, while the system bonding jumper makes that same type of connection (to the supply-side bonding jumper, the equipment grounding conductor, or both) at a separately derived system.
NEC 2017 Article 100 (Definition: Bonding Jumper, Main)Per NEC 725.41, Class 1 circuits are classified as either power-limited circuits meeting the power limitations of 725.41(A) or remote-control/signaling circuits used for those functions and meeting 725.41(B); 'inherently limited/not inherently limited' instead describes Chapter 9 Table 11 power source constructions.
NEC 2017 Section 725.41Article 760 classifies every fire alarm circuit as either non–power-limited or power-limited, and that classification determines the applicable installation requirements (e.g., NPLFA raceway fill must comply with 300.17 per 760.3(J), while PLFA cable per 760.179(I) shall not be marked with a voltage rating except where multiple listings require it).
NEC 2017 Section 760.2 (Fire Alarm Circuit)Where a CATV system uses its own grounding electrode, the jumper to the power grounding electrode system shall be not smaller than 6 AWG copper (or equivalent), whereas 14 AWG is the minimum size for the shield bonding/grounding electrode conductor itself.
NEC 2017 Section 820.100(D)A control circuit fed from a separate panelboard is protected as a Class 1 circuit under 725.43 (10 A max for 16 AWG, 7 A max for 18 AWG, ampacity for 14 AWG and larger), while tapped control conductors larger than 10 AWG use the 400 percent and 300 percent multipliers of Table 430.72(B) Notes 2 and 3 (Columns B and C).
NEC 2017 Section 725.43With separate overcurrent protection for 14 AWG and larger control conductors (e.g., 12 AWG copper), Note 1 directs the maximum rating to the conductor ampacity value from 310.15, while the 400/300 percent multipliers apply only where the motor branch-circuit short-circuit and ground-fault device protects control conductors larger than 10 AWG; the 500 percent figure belongs to 430.72(C)(4) for control transformer primaries rated less than 2 amperes.
NEC 2017 Table 430.72(B), Note 1Other metal piping systems such as gas piping that are likely to become energized must be bonded to the equipment grounding conductor of the circuit likely to energize the piping, which differs from the metal water piping bonding requirements of 250.104(A).
NEC 2017 Section 250.104(B)Lead-in conductors attached to buildings shall not swing closer than 600 mm (2 ft) to power conductors of circuits of 250 volts or less between conductors and shall be not less than 1.8 m (6 ft) from any lightning protection system conductor, while indoor antennas and indoor lead-ins shall not be run nearer than 50 mm (2 in.) to conductors of other wiring systems unless those conductors are in metal raceway or cable armor or permanently separated by a continuous, firmly fixed nonconductor.
NEC 2017 Section 810.18(A)For coaxial lead-in/overhead drops where proximity to light, power, Class 1, or NPLFA conductors cannot be avoided, 820.44(A)(4) requires 1.0 m (40 in.) at the pole and a minimum of 300 mm (12 in.) at all other points; similarly 800.44(A)(4) requires 300 mm (12 in.) minimum separation at any point in the span for 0–750 volt supply drops above and parallel to communications drops, provided ungrounded conductors are insulated and not less than 1.0 m (40 in.) is maintained at the pole.
NEC 2017 Section 820.44(A)(4)Coaxial cable is permitted to deliver power to equipment directly associated with the radio frequency distribution system only if the voltage is not over 60 volts, whereas a medium-power network-powered broadband source has a circuit voltage Vmax of 0–150 volts and its entrance cables must be in a listed raceway or fittings suitable for the purpose.
NEC 2017 Section 820.15In a series circuit the total current equals the current in any other part of the circuit (IT = I1 = I2 = I3), while parallel resistors combine as product-over-sum for two resistors or as the reciprocal sum for more, producing a total resistance lower than any branch.
Ugly's Electrical References, 2023 ed., Series Circuits, Page 3 (2020 ed.: Series Circuits)In a 120/208-volt three-phase four-wire wye system, any phase conductor to the grounded neutral measures 120 volts while any two phase conductors measure 208 volts.
Ugly's Electrical References, 2023 ed., Common Electrical Distribution Systems, Page 13 (2020 ed.: Common Electrical Distribution Systems)Per NEC 110.6, conductor sizes are expressed in American Wire Gage for conductors up to 4/0 AWG and in circular mils (kcmil) for conductors larger than 4/0 AWG.
NEC 2017 Section 110.6Key Terms
Formulas to Know
Amperes = Watts ÷ Volts; example: 1500 W ÷ 120 V = 12.5 AOhms = Volts ÷ Amperes; example: 240 V ÷ 8 A = 30 ΩE = I × R; example: 10 A × 12 Ω = 120 VP = E × I (volts × amperes = watts)P = E² ÷ R and R = E² ÷ P; examples: (240 V)² ÷ 20 Ω = 2,880 W; (120 V)² ÷ 1200 W = 12 ΩI = (kW × 1000) ÷ (E × PF × 1.73), where 1.73 (√3) is the three-phase multiplier accounting for the 120-degree phase relationshipS (kVA) = P (kW) ÷ PF; example: 200 kW ÷ 0.8 = 250 kVATwo resistors in parallel: Rp = (R1 × R2) ÷ (R1 + R2); three or more: 1/Rp = 1/R1 + 1/R2 + 1/R3; equal parallel resistors: Rp = R ÷ n; series elements add: RT = R1 + Rp + R4; then IT = E ÷ RT (e.g., 28 V ÷ 14 Ω = 2 A)If ungrounded supply conductors exceed 1100 kcmil copper or 1750 kcmil aluminum, the grounded conductor or bonding jumper shall have an area not less than 12½ percent of the area of the largest ungrounded supply conductor (or equivalent area for parallel conductors) — Table 250.102(C)(1), Note 1OCPD rating shall be not more than 167 percent of (volt-ampere rating of the source ÷ rated voltage); the device may be integral to the power supply but shall not be interchangeable with higher-rated devices — 725.41(A)(2)