Exam Cheat Sheet · Quick Reference

ICC G21 Low-Voltage Electrician Exam (2017 NEC)

National  ·  Pearson Vue

Verified, not estimated. Every figure below is drawn from the official exam structure we maintain — question counts, passing standard and topic weighting. Practice questions are grounded in the source law with statute citations. We omit any figure we can't verify rather than guess at it.
Total questions
50
Passing score
70%
Exam time
180 min
Administered by
Pearson Vue
Format
Reference materials allowed

National State Portion 50 questions

General Knowledge 12 Q · 24%
Ohm's Law and power formulas (P, E, I, R relationships)Series, parallel, and combination circuit calculationsAC circuit concepts: impedance, reactance, inductance, and capacitanceElectrical formulas for amperes, kilowatts, kVA, and horsepower (single-phase and three-phase)Grounding and bonding principles and terminology (NEC Article 250)NEC code structure, scope, definitions, and general installation requirementsPower factor, power factor correction, and efficiency calculationsElectrical symbols, field terms vs. NEC terms, and units of measurement/conversion
LV Remote Control & Alarm Systems 11 Q · 22%
Class 1 vs. Class 2 vs. Class 3 circuit classifications and definitionsPower source requirements for Class 2 and Class 3 circuitsClass 1 circuit overcurrent protection and conductor sizingSeparation of Class 2/Class 3 circuits from power and Class 1 conductorsCable types and substitution hierarchy for Class 2, Class 3, and PLTC cablesFire alarm circuit classifications: NPLFA vs. PLFAPower source and branch circuit requirements for fire alarm systemsFire alarm cable types, listing requirements, and installation by building location
LV Communications & Sound 18 Q · 36%
Communications cable types and listing requirements (CMP, CMR, CMG, CM, CMX, CMUC)Cable installation locations — plenums, risers, and general-purpose spaces (Article 800)Grounding and bonding of communications cables and primary protectors (Article 800)Primary and secondary protectors — application, location, and typesCATV coaxial cable types, installation, and grounding of outer conductive shield (Article 820)Network-powered broadband communications systems — power classifications, cable types, and installation (Article 830)Audio signal processing and reproduction equipment — wiring methods, grounding, and loudspeaker installation (Article 640)Radio and television antenna systems — materials, clearances, discharge units, and bonding conductors (Article 810)
LV Control Circuits 7 Q · 14%
Motor control circuit overcurrent protection and conductor sizing (NEC 430.72)Electrical arrangement and grounding of control circuits (NEC 430.74)Disconnection of motor control circuits from all power sources (NEC 430.75)Class 1 vs. Class 2 vs. Class 3 remote-control circuit classifications and power source requirementsThree-wire stop-start station wiring and seal-in contact operationMultiple stop-start stations and hand-off-automatic (HOA) control circuit configurationsJogging circuits and control relay wiring for inching operationsControl circuit transformer protection and reduced-voltage control wiring methods
Fiber Optical 2 Q · 4%
Optical fiber cable types and listing requirements (OFNP, OFCP, OFNR, OFCR, OFNG, OFCG, OFN, OFC)Installation locations within buildings (plenums, risers, general spaces, cable trays)Grounding and bonding of metallic members of optical fiber cablesSeparation requirements when installed with electrical conductorsOverhead and underground optical fiber cables entering buildingsCable substitution hierarchy for optical fiber cable typesAbandoned optical fiber cable requirements and fire spread preventionUnlisted optical fiber cables entering buildings (50 ft rule, raceway requirements)

Key Distinctions

Main bonding jumpervsSystem bonding jumper

Per Article 100, the main bonding jumper is the connection between the grounded circuit conductor and the equipment grounding conductor at the service, while the system bonding jumper makes that same type of connection (to the supply-side bonding jumper, the equipment grounding conductor, or both) at a separately derived system.

NEC 2017 Article 100 (Definition: Bonding Jumper, Main)
Class 1 power-limited circuitvsClass 1 remote-control and signaling circuit

Per NEC 725.41, Class 1 circuits are classified as either power-limited circuits meeting the power limitations of 725.41(A) or remote-control/signaling circuits used for those functions and meeting 725.41(B); 'inherently limited/not inherently limited' instead describes Chapter 9 Table 11 power source constructions.

NEC 2017 Section 725.41
Non-power-limited fire alarm (NPLFA) circuitvsPower-limited fire alarm (PLFA) circuit

Article 760 classifies every fire alarm circuit as either non–power-limited or power-limited, and that classification determines the applicable installation requirements (e.g., NPLFA raceway fill must comply with 300.17 per 760.3(J), while PLFA cable per 760.179(I) shall not be marked with a voltage rating except where multiple listings require it).

NEC 2017 Section 760.2 (Fire Alarm Circuit)
820.100(D) bonding jumper between separate electrodesvs820.100(A)(3) bonding conductor/grounding electrode conductor for the shield

Where a CATV system uses its own grounding electrode, the jumper to the power grounding electrode system shall be not smaller than 6 AWG copper (or equivalent), whereas 14 AWG is the minimum size for the shield bonding/grounding electrode conductor itself.

NEC 2017 Section 820.100(D)
Class 1 control conductors supplied from a separate sourcevsControl conductors tapped from the motor branch-circuit short-circuit/ground-fault device

A control circuit fed from a separate panelboard is protected as a Class 1 circuit under 725.43 (10 A max for 16 AWG, 7 A max for 18 AWG, ampacity for 14 AWG and larger), while tapped control conductors larger than 10 AWG use the 400 percent and 300 percent multipliers of Table 430.72(B) Notes 2 and 3 (Columns B and C).

NEC 2017 Section 725.43
Table 430.72(B) Column A — separate protection providedvsTable 430.72(B) Columns B and C — protected by the motor branch-circuit device

With separate overcurrent protection for 14 AWG and larger control conductors (e.g., 12 AWG copper), Note 1 directs the maximum rating to the conductor ampacity value from 310.15, while the 400/300 percent multipliers apply only where the motor branch-circuit short-circuit and ground-fault device protects control conductors larger than 10 AWG; the 500 percent figure belongs to 430.72(C)(4) for control transformer primaries rated less than 2 amperes.

NEC 2017 Table 430.72(B), Note 1
Metal gas piping bonding (250.104(B))vsMetal water piping bonding (250.104(A))

Other metal piping systems such as gas piping that are likely to become energized must be bonded to the equipment grounding conductor of the circuit likely to energize the piping, which differs from the metal water piping bonding requirements of 250.104(A).

NEC 2017 Section 250.104(B)
810.18(A) outdoor lead-in clearancesvs810.18(B) indoor lead-in separation

Lead-in conductors attached to buildings shall not swing closer than 600 mm (2 ft) to power conductors of circuits of 250 volts or less between conductors and shall be not less than 1.8 m (6 ft) from any lightning protection system conductor, while indoor antennas and indoor lead-ins shall not be run nearer than 50 mm (2 in.) to conductors of other wiring systems unless those conductors are in metal raceway or cable armor or permanently separated by a continuous, firmly fixed nonconductor.

NEC 2017 Section 810.18(A)
Clearance at the polevsClearance along the span/drop

For coaxial lead-in/overhead drops where proximity to light, power, Class 1, or NPLFA conductors cannot be avoided, 820.44(A)(4) requires 1.0 m (40 in.) at the pole and a minimum of 300 mm (12 in.) at all other points; similarly 800.44(A)(4) requires 300 mm (12 in.) minimum separation at any point in the span for 0–750 volt supply drops above and parallel to communications drops, provided ungrounded conductors are insulated and not less than 1.0 m (40 in.) is maintained at the pole.

NEC 2017 Section 820.44(A)(4)
Coaxial cable powering RF distribution equipment (820.15)vsMedium-power network-powered broadband source (Table 830.15)

Coaxial cable is permitted to deliver power to equipment directly associated with the radio frequency distribution system only if the voltage is not over 60 volts, whereas a medium-power network-powered broadband source has a circuit voltage Vmax of 0–150 volts and its entrance cables must be in a listed raceway or fittings suitable for the purpose.

NEC 2017 Section 820.15
Series circuit currentvsParallel branch resistance

In a series circuit the total current equals the current in any other part of the circuit (IT = I1 = I2 = I3), while parallel resistors combine as product-over-sum for two resistors or as the reciprocal sum for more, producing a total resistance lower than any branch.

Ugly's Electrical References, 2023 ed., Series Circuits, Page 3 (2020 ed.: Series Circuits)
Phase-to-neutral voltagevsPhase-to-phase voltage

In a 120/208-volt three-phase four-wire wye system, any phase conductor to the grounded neutral measures 120 volts while any two phase conductors measure 208 volts.

Ugly's Electrical References, 2023 ed., Common Electrical Distribution Systems, Page 13 (2020 ed.: Common Electrical Distribution Systems)
AWG sizingvsCircular mils (kcmil)

Per NEC 110.6, conductor sizes are expressed in American Wire Gage for conductors up to 4/0 AWG and in circular mils (kcmil) for conductors larger than 4/0 AWG.

NEC 2017 Section 110.6

Key Terms

Authority Having Jurisdiction (AHJ) NEC 2017 Article 100 (Definitions)
Per NEC Article 100, an organization, office, or individual responsible for enforcing the requirements of a code or standard, or for approving equipment, materials, an installation, or a procedure.
Main bonding jumper NEC 2017 Article 100 (Definition: Bonding Jumper, Main)
Per NEC Article 100, the connection between the grounded circuit conductor and the equipment grounding conductor at the service; per 250.28(D) it shall not be smaller than the sizes shown in Table 250.102(C)(1).
System bonding jumper NEC 2017 Article 100 (Definition: Bonding Jumper, System)
Per NEC Article 100, the connection between the grounded circuit conductor and the supply-side bonding jumper, the equipment grounding conductor, or both, at a separately derived system.
Fire alarm circuit NEC 2017 Section 760.2 (Fire Alarm Circuit)
Per Article 760, a circuit classified as either non–power-limited or power-limited, and that classification determines the applicable installation requirements.
Premises-powered broadband communications system NEC 2017 Section 840.1
Per Article 840.1 Informational Note No. 1, a system typically consisting of an optical fiber, twisted pair, or coaxial cable to the premises supplying a broadband signal to a network terminal that converts it into component electrical signals, with powering typically accomplished through a premises power supply.
Communications primary protector (listed) NEC 2017 Section 800.170(A)
Per NEC 800.170(A), it shall consist of an arrester connected between each line conductor and ground in an appropriate mounting, with terminals marked to indicate line and ground; a fuse in series with each line conductor is instead a feature of the fused-type primary protector of 800.90(A)(2).
Antenna discharge unit NEC 2017 Section 810.20(A)
Per NEC 810.20(A), a listed antenna discharge unit is required on each conductor of a lead-in from an outdoor antenna, except where the lead-in conductors are enclosed in a continuous metallic shield that is grounded or protected by an antenna discharge unit.
Type CATVP plenum coaxial cable NEC 2017 Section 820.179(A)
Coaxial cable listed as having adequate fire-resistant and low-smoke-producing characteristics; the Informational Note to 820.179(A) describes one method as a maximum peak optical density of 0.50 or less, average optical density of 0.15 or less, and maximum flame spread distance of 1.52 m (5 ft) or less when tested per NFPA 262.
Medium-power network-powered broadband communications circuit NEC 2017 Table 830.15
Per Table 830.15 its circuit voltage Vmax is 0–150 volts, and per 830.40(A) entrance cables within buildings shall be in a listed raceway or fittings suitable for the purpose, complying with Chapter 3, with metallic members grounded in accordance with Article 250.
Conductor material (NEC 110.5) NEC 2017 Section 110.5
Conductors normally used to carry current shall be copper or aluminum unless otherwise provided; where the material is not specified, the sizes given in the Code apply to copper conductors and must be changed accordingly for other materials.
Conductor size expression (NEC 110.6) NEC 2017 Section 110.6
Conductor sizes are expressed in American Wire Gage (AWG) or in circular mils.
NEC scope (90.2(A)) NEC 2017 Section 90.2(A)
The Code covers the installation and removal of electrical conductors, equipment, and raceways; signaling and communications conductors, equipment, and raceways; and optical fiber cables and raceways.
Limited Approach Boundary (Movable) Ugly's Electrical References 2020, Page 180
Per NFPA 70E Table 130.4(D)(a) as reproduced in Ugly's, the movable-conductor limited approach boundary is 10 ft for phase-to-phase voltages of 151–750 volts (e.g., a 480-volt system).
Physical protection of Class 1 circuits (725.31) NEC 2017 Section 725.31(B)
Where damage to a Class 1 remote-control or signaling circuit would introduce a hazard as covered in 725.31, the circuit is required to have physical protection.
Grounded neutral conductor identification Ugly's Electrical References, 2023 ed., Common Electrical Distribution Systems, Page 13 (2020 ed.: Common Electrical Distribution Systems)
In a 120/240-volt single-phase three-wire system the grounded neutral conductor is white or gray as required by NEC 200.6(A), while the ungrounded conductors are black (line one) and red (line two).
Metric prefixes (milli, kilo) Metric prefixes (milli = 1/1,000)
Milli means one-thousandth, so milliamperes are divided by 1,000 to get amperes (350 mA = 0.35 A), and kilo means 1,000, so 1 kVA = 1,000 volt-amperes.

Formulas to Know

Current from power and voltage (Ohm's Law)Amperes = Watts ÷ Volts; example: 1500 W ÷ 120 V = 12.5 A
Resistance from voltage and current (Ohm's Law)Ohms = Volts ÷ Amperes; example: 240 V ÷ 8 A = 30 Ω
Voltage from current and resistance (Ohm's Law)E = I × R; example: 10 A × 12 Ω = 120 V
Power when voltage and current are knownP = E × I (volts × amperes = watts)
Power/resistance when voltage is knownP = E² ÷ R and R = E² ÷ P; examples: (240 V)² ÷ 20 Ω = 2,880 W; (120 V)² ÷ 1200 W = 12 Ω
Three-phase amperes when kilowatts are knownI = (kW × 1000) ÷ (E × PF × 1.73), where 1.73 (√3) is the three-phase multiplier accounting for the 120-degree phase relationship
Apparent power from real power and power factorS (kVA) = P (kW) ÷ PF; example: 200 kW ÷ 0.8 = 250 kVA
Total resistance and current of series-parallel networksTwo resistors in parallel: Rp = (R1 × R2) ÷ (R1 + R2); three or more: 1/Rp = 1/R1 + 1/R2 + 1/R3; equal parallel resistors: Rp = R ÷ n; series elements add: RT = R1 + Rp + R4; then IT = E ÷ RT (e.g., 28 V ÷ 14 Ω = 2 A)
Grounded conductor / bonding jumper for very large supply conductorsIf ungrounded supply conductors exceed 1100 kcmil copper or 1750 kcmil aluminum, the grounded conductor or bonding jumper shall have an area not less than 12½ percent of the area of the largest ungrounded supply conductor (or equivalent area for parallel conductors) — Table 250.102(C)(1), Note 1
Overcurrent rating for a Class 1 power-limited source other than a transformerOCPD rating shall be not more than 167 percent of (volt-ampere rating of the source ÷ rated voltage); the device may be integral to the power supply but shall not be interchangeable with higher-rated devices — 725.41(A)(2)