Exam Cheat Sheet · Quick Reference
ICC G27 Master Plumber with Gas Exam (2018 IPC/IFGC)
National · Pearson Vue
National State Portion 100 questions
Key Distinctions
Per the IPC 2018 Section 202 definitions, the water service pipe runs from the water main or other potable source (or from the meter only where the meter is at the public right of way) to the water distribution system of the building, so when the meter is inside the building the service pipe extends all the way to the building's distribution system and the distribution pipe begins only where the meter is at the structure.
IPC 2018 Chapter 2 — Section 202, definitions of Water Pipe (Water service pipe and Water distribution pipe)A horizontal pipe or fitting makes an angle of less than 45 degrees with the horizontal plane (so 40 degrees is horizontal), while a vertical pipe or fitting makes an angle of 45 degrees or more with the horizontal.
IPC 2018 Chapter 2 — Section 202, definitions of Horizontal Pipe and Vertical PipeA stack vent is the extension of a soil or waste stack above the highest horizontal drain connected to that stack, while a vent stack is a vertical vent pipe installed primarily to provide circulation of air to and from the drainage system.
IPC 2018 Chapter 2 — Section 202, definitions of Stack Vent and Vent StackAn appurtenance is an adjunct device that demands no additional water supply and adds no discharge load to a fixture or the drainage system, whereas devices dependent on energized components are plumbing appliances.
IPC 2018 Chapter 2 — Section 202, definitions of Plumbing Appurtenance and Plumbing ApplianceFull-open valves are required at points such as the discharge side of every water meter, the water supply pipe to every water heater, the entrance to the structure and the base of every water riser (in occupancies other than multiple-family residential two stories or less and one- and two-family dwellings), while shutoff valves are the valves required at fixture supplies — with bathtubs and showers in one- and two-family residential occupancies exempt.
IPC 2018 Sections 606.1 and 606.2Both are prohibited traps under IPC 1002.3, but drum traps have an exception permitting their use as solids interceptors and for chemical waste systems, while S-traps are prohibited with no exception.
IPC 2018 Section 1002.3Potable water-supplied trap seal primer valves must conform to ASSE 1018 (Section 1002.4.1.1) and waste water-supplied trap primer devices to ASSE 1044 (Section 1002.4.1.3), while barrier-type floor drain trap seal protection devices must conform to ASSE 1072 (Section 1002.4.1.4).
IPC 2018 Section 1002.4.1.1Per Table 608.1, the double check assembly is rated for low hazard only but protects against both backpressure and backsiphonage, while the pressure vacuum breaker assembly (ASSE 1020, CSA B64.1.2) is rated for backsiphonage only; reduced pressure principle assemblies and spill-resistant vacuum breakers are rated for high or low hazard.
IPC 2018 Section 608.1, Table 608.1Under the longest length method every section and branch is sized from the table row for the system's longest run, while under the branch length method each branch is sized using its own length measured from the meter (e.g., a 120 cfh branch at 50 ft sizes to 3/4 inch on the 50-ft row, where the 90-ft longest-length row would call for 1 inch).
IFGC Section 402.4.1, Longest Length Method; Table 402.4(2), Schedule 40 Metallic Pipe (natural gas, 0.5 in. w.c. drop)In covered and open mall buildings the required facilities shall be not more than one story above or below the space served and the path of travel shall not exceed 300 feet from the main entrance of the store or tenant space (Section 403.3.4), while the 500-foot limit of Section 403.3.3 applies to occupancies other than malls.
IPC 2018 Chapter 4, Section 403.3.4 (Location of Toilet Facilities in Malls)Urinals shall not be substituted for more than 67 percent of the required water closets in assembly and educational occupancies, while in all other occupancies the limit is 50 percent.
IPC 2018 Section 424.2A permit application is deemed abandoned 180 days after filing unless pursued in good faith, but the code official may grant one or more extensions of not more than 180 days each upon written request with justifiable cause, whereas permit extensions under 106.5.4 may be granted only once.
IPC 2018 Chapter 1 Scope and Administration — Section 106.3.3 Time Limitation of ApplicationPot sinks, prerinse sinks and floor drains into which kettles are drained must discharge through a grease interceptor (Section 1003.3.1), while a food waste disposer shall not discharge to a grease interceptor (Section 1003.3.2).
IPC 2018 Section 1003.3.2Key Terms
Formulas to Know
cfh = total Btuh ÷ 1,000; e.g., (50,000 + 40,000 + 100,000) ÷ 1,000 = 190 cfh at the meter; (100,000 + 200,000 + 40,000) ÷ 1,000 = 340 cfh; (40,000 + 65,000 + 30,000) ÷ 1,000 = 135 cfh; (80,000 + 40,000 + 30,000) ÷ 1,000 = 150 cfh; (65,000 + 40,000 + 50,000) ÷ 1,000 = 155 cfhBtuh = table capacity in cfh × 1,000 Btu per cu ft; e.g., 247 cfh = 247,000 Btuh, 44 cfh = 44,000 Btuh, 117 cfh = 117,000 BtuhSpare cfh = table capacity at that length − connected demand; e.g., 170 cfh capacity − 60 cfh demand = 110 cfh spare; 137 cfh − 135 cfh = 2 cfh marginUse the next table length row at or above the actual run: 15 ft → 20-ft row; 35 ft → 40-ft row; 95 ft → 100-ft row; 110 ft → 125-ft row; 140 ft → 150-ft rowSize every section and branch from the system's longest-run row, not the branch's own length; e.g., 40,000 Btuh = 40 cfh branch, 70-ft row, 1/2 inch carries 60 cfh; 65,000 Btuh = 65 cfh branch, 40-ft row, 1/2 inch carries 81 cfhEach branch uses its own length measured from the meter (main length to the tee + branch length); e.g., 15 ft main + 8 ft branch = 23 ft → 30-ft row; 120 cfh branch at its own 50 ft → 50-ft row, 3/4 inch (151 cfh); and the most remote outlet's length sizes the main sections feeding it (55 ft → 60-ft row; 85 ft → 90-ft row; 70 ft → 70-ft row)Section load = sum of the inputs of all outlets it serves ÷ 1,000; e.g., outlets 2–4: 40,000 + 35,000 + 100,000 = 175 cfh → 1 inch on the 70-ft row (237 cfh); outlets 2–3: 35,000 + 40,000 = 75 cfh → 1/2 inch on the 40-ft row (81 cfh); outlets 2–3: 40,000 + 50,000 = 90 cfh → 3/4 inch on the 80-ft rowMaximum distance downstream of the drainage stack = 10 × stack diameter; for a 4-inch stack, 10 × 4 in. = 40 inches1 gpm of flow = 2 drainage fixture units (IPC 709.3)Divide the total occupant load in half (Section 403.1.1), then apply the Table 403.1 ratio; worked example: restaurant with 150 total occupants → 150 ÷ 2 = 75 females ÷ (1 per 75) = 1 water closet