Exam Cheat Sheet · Quick Reference

ICC G34 Journeyman Gas Pipe Fitter Exam (2018 IFGC)

National  ·  Pearson Vue

Verified, not estimated. Every figure below is drawn from the official exam structure we maintain — question counts, passing standard and topic weighting. Practice questions are grounded in the source law with statute citations. We omit any figure we can't verify rather than guess at it.
Total questions
55
Passing score
70%
Exam time
120 min
Administered by
Pearson Vue
Format
Reference materials allowed

National State Portion 55 questions

General Requirements 22 Q · 40%
General Installation RequirementsCode Definitions and TermsPlan ReadingTestingMaterialsAppliance Location and Prohibited LocationsClearances to Combustible Construction and Clearance ReductionElectrical Bonding and Grounding of Gas PipingCondensate Disposal RequirementsAccess and Service Space RequirementsPermits, Inspections, and Code AdministrationAppliance Listing, Labeling, and Approval Requirements +2 more
Appliances and Equipment 13 Q · 24%
Requirements for Specific Appliances & EquipmentClothes dryer exhaust duct installation and maximum duct length requirementsUnvented room heater restrictions, oxygen-depletion safety systems, and input rating limitsForced-air warm-air furnace prohibited return-air sources and circulating air requirementsCooking appliance clearances, prohibited locations, and venting requirementsVented and unvented fireplace appliance flame safeguard and ignition device requirementsUnit heater support, clearances, and installation in commercial garages and aircraft hangarsWater heater installation requirements and dual-use space-heating applicationsSauna heater location, heat controls, combustion air, and ventilation requirements
Fuel Supply System Sizing 5 Q · 9%
Service and Distribution Pipe SizingMaximum Gas Demand Calculation and Load DeterminationPipe Sizing Methods (Longest Length, Branch Length, and Hybrid Pressure)Allowable Pressure Drop and Operating Pressure LimitsSizing Table Selection by Pipe Material and Gas TypeEquivalent Length Allowances for Fittings and ValvesSpecific Gravity Correction Factors for Gas Pipe SizingLow-Pressure vs. High-Pressure Sizing EquationsChapter 4 Gas Piping Installations
Combustion Air 7 Q · 13%
Combustion Air Source, Size of Ducts/OpeningsIndoor combustion air requirements (standard method and known air-infiltration-rate method)Combining indoor spaces for combustion air (same story and different stories)Outdoor combustion air methods (two-permanent-openings and one-permanent-opening)Combination indoor and outdoor combustion air calculationsMechanical combustion air supply systems and appliance interlock requirementsLouvers, grilles, and screens: net free area calculations and motorized louver interlocksCombustion air duct installation requirements and restrictionsProtection of combustion air from corrosive or flammable fumes and gases
Chimneys and Vents 8 Q · 15%
Venting, Vent Connector, and ChimneysAppliance venting categories and vent system type selection (Table 503.4)Vent and chimney termination location requirementsDraft hoods and draft controls installation requirementsSizing of Category I appliance venting systems using tables (single and multiple appliances)Vent connector materials, clearances, slope, and installation requirementsAppliances not required to be vented and aggregate input limitsFactory-built chimney requirements and listings (UL 103, UL 959)Corrugated metallic liner sizing and exterior masonry chimney design temperature considerationsChapter 5 Chimneys and Vents

Key Distinctions

Longest length method (Section 402.4.1)vsBranch length method (Section 402.4.2)

Longest length sizes every section from the table row for the longest run from the point of delivery to the most remote outlet, while branch length sizes each branch from its own length measured from the meter (e.g., 30 ft of main + 15 ft branch = 45 ft → 50-ft row).

IFGC 2018 Section 402.4.1
PipevsTubing

Pipe is a rigid conduit of iron, steel, copper, copper-alloy or plastic, while tubing is a semirigid conduit of copper, copper-alloy, aluminum, plastic or steel (aluminum appears only under tubing).

IFGC 2018 Section 202 (Piping definition)
Combustion airvsDilution air

Combustion air is the air necessary for complete combustion of a fuel, including theoretical air and excess air; dilution air is air introduced into a draft hood and mixed with the flue gases.

IFGC 2018 Chapter 2 Definitions
Low-pressure gas sizing equationvsHigh-pressure gas sizing equation

Per Section 402.4 (Equations 4-1 and 4-2) and Appendix A A.4, the low-pressure equation applies to systems operating at less than 1-1/2 psi and the high-pressure equation at 1-1/2 psi and above; the 2 psig value is the dividing point for the capacity tables, not for the equations.

IFGC 2018 Section 402.4 (Chapter 4) and Appendix A, Section A.4
Indoor purgingvsOutdoor purging

Per Section 406.7.1, piping systems with a design operating pressure greater than 2 psig must be purged outdoors; indoor purging (such as through an appliance burner) is allowed only for systems at 2 psig or less that also do not meet the size and length criteria of Table 406.7.1.1.

IFGC 2018 Section 406.7.1
Black steel or galvanized steel concealed pipingvsOther (non-steel) concealed piping

Under the Section 404.7 exception, black steel and galvanized steel piping are not required to be protected from fasteners; other piping concealed in light-frame construction and located less than 1-1/2 inches from the framing member face to which the membrane attaches must be protected by steel shield plates not less than 0.0575 inch (No. 16 gage) thick (Sections 404.7.1 through 404.7.3).

IFGC 2018 Section 404.7
Prescriptive combustion air methods (Sections 304.5 through 304.9)vsManufacturer's instructions method (Section 304.1)

Most appliances get combustion, ventilation and dilution air by the prescribed code methods, but direct-vent appliances, gas appliances of other than natural draft design, vented gas appliances not designated as Category I, and appliances equipped with power burners must follow the appliance manufacturer's instructions.

IFGC 2018 Chapter 3, Section 304.1
Thimble for a listed draft-hood appliance (Section 503.7.7, Item 1)vsThimble for an unlisted draft-hood appliance (Section 503.7.7, Item 2)

Single-wall metal pipe through a combustible exterior wall needs a ventilated thimble not less than 4 inches larger in diameter than the pipe for listed draft-hood appliances (2-inch allowance only where there is a run of not less than 6 feet of pipe in the open between draft hood outlet and thimble), but not less than 6 inches larger for unlisted draft-hood appliances.

IFGC 2018 Section 503.7.7
Flared jointvsFlanged joint

A flared joint is a metal-to-metal compression joint where a conical spread on the tube end is compressed by a flare nut against a mating flare; a flanged joint is made by bolting together a pair of flanged ends.

IFGC 2018 Section 202 (Joint, Flared definition)
Mechanical jointvsPlastic heat fusion joint

A mechanical joint is a gas-tight joint made by positive-holding mechanical construction (press-connect, flanged, threaded, flared or compression), while a plastic heat fusion joint is made in thermoplastic piping by heating the parts enough to fuse the materials when pressed together.

IFGC 2018 Section 202 (Joint, Mechanical definition)
Elbow capacity reduction, single-appliance vent (Section 504.2.3)vsCorrugated metallic liner reduction, common vent (Section 504.3.19)

Single-appliance venting tables already include two 90-degree elbows and the listed maximum capacity is reduced 10 percent for each additional elbow greater than 45 up to 90 degrees, whereas corrugated metallic liners in masonry chimneys require the maximum common vent capacities from Tables 504.3(1)/(2) to be reduced by 20 percent.

IFGC 2018 Section 504.2.3
Gas piping as a grounding electrodevsBonding jumper / bonding of gas piping

Section 309.1 prohibits using gas piping as a grounding electrode, while a bonding jumper is a conductor installed to electrically connect metallic gas piping to the grounding electrode system, and each above-ground portion of a gas piping system other than CSST likely to become energized must be electrically continuous and bonded to an effective ground-fault current path.

IFGC 2018 Section 309.1
Gas-fired water heater installationvsWater heater fired by other than fuel gas

Per Section 624.1, gas water heaters are tested to ANSI Z21.10.1/CSA 4.1 and ANSI Z21.10.3/CSA 4.3 and installed per the manufacturer's instructions, while water heaters utilizing fuels other than fuel gas are regulated by the International Mechanical Code.

IFGC 2018 Section 624.1 (Chapter 6, Specific Appliances)

Key Terms

Piping system IFGC 2018 Section 202 (Piping System definition)
Per Section 202, the fuel piping, valves and fittings from the outlet of the point of delivery to the outlets of the appliance shutoff valves.
Pipe IFGC 2018 Section 202 (Piping definition)
Per Section 202, a rigid conduit of iron, steel, copper, copper-alloy or plastic.
Tubing IFGC 2018 Section 202 (Piping/Tubing definition)
Per Section 202, a semirigid conduit of copper, copper-alloy, aluminum, plastic or steel.
Joint, flared IFGC 2018 Section 202 (Joint, Flared definition)
Per Section 202, a metal-to-metal compression joint in which a conical spread is made on the end of a tube that is compressed by a flare nut against a mating flare.
Joint, flanged IFGC 2018 Section 202 (Joint, Flanged definition)
Per Section 202, a joint made by bolting together a pair of flanged ends.
Joint, mechanical IFGC 2018 Section 202 (Joint, Mechanical definition)
Per Section 202, a general form of gas-tight joint obtained by joining metal parts through a positive-holding mechanical construction, such as a press-connect, flanged, threaded, flared or compression joint.
Joint, plastic heat fusion IFGC 2018 Section 202 (Joint, Plastic Heat Fusion definition)
Per Section 202, a joint made in thermoplastic piping by heating the parts sufficiently to permit fusion of the materials when the parts are pressed together.
Bonding jumper IFGC 2018 Section 202 Definitions
Per Section 202, a conductor installed to electrically connect metallic gas piping to the grounding electrode system.
Combustion air IFGC 2018 Chapter 2 Definitions
Air necessary for complete combustion of a fuel, including theoretical air and excess air.
Dilution air IFGC 2018 Section 202
Per Section 202, air that is introduced into a draft hood and is mixed with the flue gases.
EHD (Equivalent Hydraulic Diameter) IFGC 2018 Table 402.4(15), Note 2
Per the notes to CSST sizing Tables 402.4(15) through 402.4(19), a measure of the relative hydraulic efficiency between tubing sizes — the greater the EHD, the greater the gas capacity of the tubing.
Longest length method IFGC 2018 Section 402.4.1
Per Section 402.4.1, sizing in which the pipe size of each section is determined using the longest length of piping from the point of delivery to the most remote outlet and the load of that section.
Branch length method IFGC Section 402.4.2, Branch Length Method; Table 402.4(2), Schedule 40 Metallic Pipe (natural gas, 0.5 in. w.c. drop)
Per Section 402.4.2, sizing in which each branch is sized using its own length measured from the meter through the mains to that branch outlet.
Shield plate IFGC 2018 Section 404.7.3
Per Section 404.7.3, protection for piping in light-frame construction made of steel not less than 0.0575 inch (No. 16 gage) thick against penetration by fasteners.
Appliance shutoff valve at a manifold IFGC 2018 Section 409.5.3
Per Section 409.5.3, a shutoff valve installed at a manifold instead of in the appliance room, which shall be located within 50 feet of the appliance served and be readily accessible and permanently identified.
Overpressure protection device setting IFGC 2018 Section 416.2.1
Per Section 416.2.1, where gas is delivered above 2 psi to piping serving appliances designed for 14 inches w.c. or less, each device must be adjusted to limit pressure to each connected appliance to 2 psi or less upon failure of the line pressure regulator.
Prohibited shutoff valve location IFGC 2018 Section 409.1.2
Per Section 409.1.2, shutoff valves are prohibited in concealed locations and in furnace plenums.
Combustible gas detector (CGD) evacuation level IFGC 2018 Appendix D, Section D.2(4)
Per Appendix D, Section D.2(4), a CGD reading of 20% LEL or greater requires immediately notifying the occupant to evacuate, evacuating, and calling 911.

Formulas to Know

Gas demand in cfh from appliance input (natural gas, 1,000 Btu per cu ft)cfh = Btuh ÷ 1,000 (e.g., 40,000 Btuh ÷ 1,000 = 40 cfh); conversely table capacity in cfh × 1,000 = Btuh the pipe can serve (e.g., 247 cfh = 247,000 Btuh)
Spare capacity of an installed pipeSpare cfh = table capacity at the applicable length row − demand (example: 247 − 35 = 212 cfh; 137 − 80 = 57 cfh; 44 − 40 = 4 cfh; 322 − 150 = 172 cfh)
Table length row selectionUse the next longer length row in Table 402.4(2) (e.g., a 15-ft run uses the 20-ft row; a 95-ft run uses the 100-ft row; a 140-ft run uses the 150-ft row; branch length 45 ft → 50-ft row; 65 ft → 70-ft row)
Indoor combustion air — standard method volumeRequired volume = (total appliance input Btu/h ÷ 1,000) × 50 cubic feet (example: 120,000 + 60,000 = 180,000 Btu/h → 180 × 50 = 9,000 cu ft)
Combination indoor/outdoor combustion air — reduced outdoor opening (Section 304.7.3)Ratio of interior spaces = available volume ÷ required volume; reduction factor = 1 − ratio; minimum outdoor opening = full outdoor opening size × reduction factor (example: 1,200 ÷ 2,000 = 0.6, 1 − 0.6 = 0.4, 50 sq in × 0.4 = 20 sq in). Minimum dimension of any air opening is still 3 inches.
Outdoor combustion air — two permanent openings through horizontal ducts (Section 304.6.1)Each opening free area = not less than 1 square inch per 2,000 Btu/h of total input rating of all appliances in the enclosure
CSST extra fittings/bends equivalent lengthL = 1.3n, where L is additional equivalent length in feet and n is the number of fittings or bends beyond the four 90-degree bends and two end fittings already included in the table
Domestic dryer exhaust — maximum straight duct lengthMaximum straight duct = 35 ft total equivalent length − sum of fitting equivalent lengths (example: two 4-in radius mitered 90° elbows at 5 ft each + one 4-in radius mitered 45° elbow at 2 ft 6 in = 12 ft 6 in; 35 − 12.5 = 22 ft 6 in)
Gas piping test pressure and gauge rangeTest pressure = not less than 1½ times the proposed maximum working pressure, but not less than 3 psig irrespective of design pressure; mechanical gauge scale high end not greater than five times the test pressure
Vent capacity reductionsSingle-appliance venting: reduce listed maximum capacity 10 percent for each 90-degree (or >45° up to 90°) elbow beyond the two already included; corrugated metallic liner in masonry chimney: reduce maximum common vent capacities from Tables 504.3(1)/(2) by 20 percent
Unvented appliance input limit per room volume (Section 501.8)Aggregate input rating of appliances in Items 5 through 11 shall not exceed 20 Btu per hour per cubic foot of room volume; excess appliances must be provided with venting systems
Direct-fired industrial air heater ventilation airOutside ventilation air = not less than 4 cubic feet per minute per 1,000 Btu/h of rated heater input