Exam Cheat Sheet · Quick Reference
ICC G34 Journeyman Gas Pipe Fitter Exam (2018 IFGC)
National · Pearson Vue
National State Portion 55 questions
Key Distinctions
Longest length sizes every section from the table row for the longest run from the point of delivery to the most remote outlet, while branch length sizes each branch from its own length measured from the meter (e.g., 30 ft of main + 15 ft branch = 45 ft → 50-ft row).
IFGC 2018 Section 402.4.1Pipe is a rigid conduit of iron, steel, copper, copper-alloy or plastic, while tubing is a semirigid conduit of copper, copper-alloy, aluminum, plastic or steel (aluminum appears only under tubing).
IFGC 2018 Section 202 (Piping definition)Combustion air is the air necessary for complete combustion of a fuel, including theoretical air and excess air; dilution air is air introduced into a draft hood and mixed with the flue gases.
IFGC 2018 Chapter 2 DefinitionsPer Section 402.4 (Equations 4-1 and 4-2) and Appendix A A.4, the low-pressure equation applies to systems operating at less than 1-1/2 psi and the high-pressure equation at 1-1/2 psi and above; the 2 psig value is the dividing point for the capacity tables, not for the equations.
IFGC 2018 Section 402.4 (Chapter 4) and Appendix A, Section A.4Per Section 406.7.1, piping systems with a design operating pressure greater than 2 psig must be purged outdoors; indoor purging (such as through an appliance burner) is allowed only for systems at 2 psig or less that also do not meet the size and length criteria of Table 406.7.1.1.
IFGC 2018 Section 406.7.1Under the Section 404.7 exception, black steel and galvanized steel piping are not required to be protected from fasteners; other piping concealed in light-frame construction and located less than 1-1/2 inches from the framing member face to which the membrane attaches must be protected by steel shield plates not less than 0.0575 inch (No. 16 gage) thick (Sections 404.7.1 through 404.7.3).
IFGC 2018 Section 404.7Most appliances get combustion, ventilation and dilution air by the prescribed code methods, but direct-vent appliances, gas appliances of other than natural draft design, vented gas appliances not designated as Category I, and appliances equipped with power burners must follow the appliance manufacturer's instructions.
IFGC 2018 Chapter 3, Section 304.1Single-wall metal pipe through a combustible exterior wall needs a ventilated thimble not less than 4 inches larger in diameter than the pipe for listed draft-hood appliances (2-inch allowance only where there is a run of not less than 6 feet of pipe in the open between draft hood outlet and thimble), but not less than 6 inches larger for unlisted draft-hood appliances.
IFGC 2018 Section 503.7.7A flared joint is a metal-to-metal compression joint where a conical spread on the tube end is compressed by a flare nut against a mating flare; a flanged joint is made by bolting together a pair of flanged ends.
IFGC 2018 Section 202 (Joint, Flared definition)A mechanical joint is a gas-tight joint made by positive-holding mechanical construction (press-connect, flanged, threaded, flared or compression), while a plastic heat fusion joint is made in thermoplastic piping by heating the parts enough to fuse the materials when pressed together.
IFGC 2018 Section 202 (Joint, Mechanical definition)Single-appliance venting tables already include two 90-degree elbows and the listed maximum capacity is reduced 10 percent for each additional elbow greater than 45 up to 90 degrees, whereas corrugated metallic liners in masonry chimneys require the maximum common vent capacities from Tables 504.3(1)/(2) to be reduced by 20 percent.
IFGC 2018 Section 504.2.3Section 309.1 prohibits using gas piping as a grounding electrode, while a bonding jumper is a conductor installed to electrically connect metallic gas piping to the grounding electrode system, and each above-ground portion of a gas piping system other than CSST likely to become energized must be electrically continuous and bonded to an effective ground-fault current path.
IFGC 2018 Section 309.1Per Section 624.1, gas water heaters are tested to ANSI Z21.10.1/CSA 4.1 and ANSI Z21.10.3/CSA 4.3 and installed per the manufacturer's instructions, while water heaters utilizing fuels other than fuel gas are regulated by the International Mechanical Code.
IFGC 2018 Section 624.1 (Chapter 6, Specific Appliances)Key Terms
Formulas to Know
cfh = Btuh ÷ 1,000 (e.g., 40,000 Btuh ÷ 1,000 = 40 cfh); conversely table capacity in cfh × 1,000 = Btuh the pipe can serve (e.g., 247 cfh = 247,000 Btuh)Spare cfh = table capacity at the applicable length row − demand (example: 247 − 35 = 212 cfh; 137 − 80 = 57 cfh; 44 − 40 = 4 cfh; 322 − 150 = 172 cfh)Use the next longer length row in Table 402.4(2) (e.g., a 15-ft run uses the 20-ft row; a 95-ft run uses the 100-ft row; a 140-ft run uses the 150-ft row; branch length 45 ft → 50-ft row; 65 ft → 70-ft row)Required volume = (total appliance input Btu/h ÷ 1,000) × 50 cubic feet (example: 120,000 + 60,000 = 180,000 Btu/h → 180 × 50 = 9,000 cu ft)Ratio of interior spaces = available volume ÷ required volume; reduction factor = 1 − ratio; minimum outdoor opening = full outdoor opening size × reduction factor (example: 1,200 ÷ 2,000 = 0.6, 1 − 0.6 = 0.4, 50 sq in × 0.4 = 20 sq in). Minimum dimension of any air opening is still 3 inches.Each opening free area = not less than 1 square inch per 2,000 Btu/h of total input rating of all appliances in the enclosureL = 1.3n, where L is additional equivalent length in feet and n is the number of fittings or bends beyond the four 90-degree bends and two end fittings already included in the tableMaximum straight duct = 35 ft total equivalent length − sum of fitting equivalent lengths (example: two 4-in radius mitered 90° elbows at 5 ft each + one 4-in radius mitered 45° elbow at 2 ft 6 in = 12 ft 6 in; 35 − 12.5 = 22 ft 6 in)Test pressure = not less than 1½ times the proposed maximum working pressure, but not less than 3 psig irrespective of design pressure; mechanical gauge scale high end not greater than five times the test pressureSingle-appliance venting: reduce listed maximum capacity 10 percent for each 90-degree (or >45° up to 90°) elbow beyond the two already included; corrugated metallic liner in masonry chimney: reduce maximum common vent capacities from Tables 504.3(1)/(2) by 20 percentAggregate input rating of appliances in Items 5 through 11 shall not exceed 20 Btu per hour per cubic foot of room volume; excess appliances must be provided with venting systemsOutside ventilation air = not less than 4 cubic feet per minute per 1,000 Btu/h of rated heater input