Exam Cheat Sheet · Quick Reference

ICC T16 Master Electrician Exam (2020 NEC)

National  ·  Pearson Vue

Verified, not estimated. Every figure below is drawn from the official exam structure we maintain — question counts, passing standard and topic weighting. Practice questions are grounded in the source law with statute citations. We omit any figure we can't verify rather than guess at it.
Total questions
100
Passing score
75%
Exam time
300 min
Administered by
Pearson Vue
Format
Reference materials allowed

National State Portion 100 questions

General Knowledge 12 Q · 12%
Electrical Theory and General Electrical Load CalculationsCode Definitions and TermsPlan ReadingNEC Code Structure, Scope, and Enforcement (Article 90)General Requirements for Electrical Installations (Article 110)Working Space and Clearance Requirements for Electrical EquipmentEquipment Approval, Listing, Labeling, and Marking RequirementsConductor Types, Sizes, and Electrical ConnectionsCommon Electrical Distribution Systems and Wiring Diagram SymbolsAC/DC Circuit Theory: Series, Parallel, and Combination CircuitsPower Factor, Impedance, Reactance, Inductance, and Capacitance Calculations
Services and Service Equipment 16 Q · 16%
Services and Fault CurrentService Load CalculationsService Equipment & Service ConductorsTransformersSystem Grounding and BondingTemporary Service WiringService Disconnecting Means Requirements and RatingsOverhead and Underground Service Conductor Installation and ClearancesGrounding Electrode System Types and InstallationSurge-Protective Devices (SPDs) and Surge Arresters at ServicesService Equipment Workspace, Guarding, and Labeling RequirementsAvailable Fault Current Field Marking and Short-Circuit Current Ratings
Feeders 4 Q · 4%
Load CalculationsEquipment GroundingFeeder conductor ampacity and minimum sizing requirementsOvercurrent protection for feedersFeeder neutral load calculationsDemand factors for dwelling and non-dwelling feeder loadsOutside feeder clearances and installation requirementsFeeder disconnecting means for separate buildings and structuresCommon neutral conductor provisions for feedersGround-fault protection of equipment for feeder disconnects
Branch Circuits and Conductors 16 Q · 16%
Branch Circuit CalculationOvercurrent ProtectionConductorsRequired Outlets & GFCI/AFCI ProtectionEquipment GroundingConductor Ampacity Tables and Temperature RatingsAmpacity Correction and Adjustment FactorsVoltage Drop CalculationsConductor Identification and Color CodingMultiwire Branch Circuit RequirementsBranch Circuit Voltage LimitationsConduit Fill Calculations
Wiring Methods and Materials 19 Q · 19%
Raceway InstallationsUnderground Wiring MethodsBoxes and EnclosuresCabinets, Panelboards, & SwitchboardsClearance and GuardingFlexible Cords and CablesCable Types and Their Permitted and Prohibited Uses (NM, MC, AC, MI, TC, SE, UF, and specialty types)Conductor Fill Calculations and Conduit Sizing (Chapter 9 Tables, percent fill, nipple fill)Conduit Bending Techniques (90-degree, offset, saddle, back-to-back, developed length, shrink)Securing and Supporting Requirements for Wiring Methods (support intervals for RMC, PVC, EMT, FMC, LFMC, cables)Wireway, Auxiliary Gutter, Busway, and Cable Tray Systems (fill limits, uses permitted, splices and taps)NEMA Enclosure Types and Environmental Ratings +2 more
Equipment and Devices 10 Q · 10%
LuminairesReceptacles, Switches and Other DevicesAppliances and Other EquipmentOther Utilization EquipmentHeating and Cooling EquipmentFixture Wire Types, Ampacities, and Installation RequirementsNEMA Receptacle and Attachment Plug ConfigurationsLuminaire Installation in Specific Locations (wet, damp, closets, bathtubs)Recessed Luminaire Clearances and Thermal Protection RequirementsLighting Track Installation and Load RequirementsLow-Voltage Lighting System Requirements (Article 411)Disconnecting Means for Fixed Electric Heating and A/C Equipment +1 more
Control Devices 3 Q · 3%
Switches, Disconnects and ControllersMotor controller ratings and marking requirements (NEC 430.8, 430.83)Motor control circuit overcurrent protection and wiring methods (NEC 430.71–430.75)Disconnecting means for motors and controllers (NEC 430.101–430.113)Motor overload protection devices and settings (NEC 430.32–430.44)Industrial control panel overcurrent protection and short-circuit current ratings (NEC 409.21–409.22)Class 1 remote-control circuit requirements and overcurrent protection (NEC Article 725)Stop-start station and jogging control circuit configurationsHand-off-automatic (HOA) control circuit wiring
Motors and Generators 8 Q · 8%
MotorsGeneratorsMotor circuit conductor sizing and ampacity requirementsMotor branch-circuit short-circuit and ground-fault protective device ratings (Table 430.52)Motor overload protection requirements and trip current percentagesMotor disconnecting means requirements and ratingsMotor controllers — ratings, marking, and design requirementsFull-load current table values for DC, single-phase, and three-phase AC motorsLocked-rotor code letters and locked-rotor current calculationsPhase converters — installation, conductor sizing, and disconnecting means
Special Occupancies, Equipment, and Conditions 12 Q · 12%
Special OccupanciesSwimming Pools and Similar InstallationsMobile Home and RV ParksData Processing EquipmentMiscellaneous Special EquipmentEmergency SystemsSignaling and Fire Alarm SystemsHazardous Location Classification (Class I, II, III / Division and Zone Systems)Specific Hazardous Location Occupancies (Garages, Hangars, Motor Fuel Dispensing, Bulk Storage, Spray/Dip/Coating)Health Care Facilities Wiring and Isolated Power SystemsStandby and Alternate Power Systems (Emergency, Legally Required, Optional, COPS)Alternative and Distributed Energy Systems (Solar PV, Wind, Fuel Cell, Energy Storage) +3 more

Key Distinctions

Surge arrestervsSPD (surge-protective device)

A surge arrester limits surge voltages by discharging or bypassing surge current and prevents continued flow of follow current while remaining capable of repeating these functions, whereas an SPD limits transient voltages by diverting or limiting surge current.

NEC 2020 Article 100 — Definitions, Surge Arrester
InvertervsRectifier

Per Article 100 an inverter is equipment that changes dc to ac, while a rectifier performs the opposite function (ac to dc); a transformer changes voltage levels within the same current type and a dc-to-dc converter changes dc voltage/current levels.

NEC 2020 Article 100 — Definitions, Inverter
SwitchgearvsSwitchboard / panelboard

Switchgear is completely enclosed on all sides and top with sheet metal (except ventilating openings and inspection windows) containing primary power circuit switching and/or interrupting devices with buses and connections, while a switchboard is generally accessible from the rear and not intended to be installed in cabinets and a panelboard is designed for assembly in a cabinet (a motor control center principally contains motor control units).

NEC 2020 Article 100 — Definitions, Switchgear
Voltage to ground — ungrounded circuitvsVoltage to ground — grounded circuit

For ungrounded circuits, voltage to ground is the greatest voltage between the given conductor and any other conductor of the circuit; for grounded circuits it is the voltage between the given conductor and the grounded point or conductor.

NEC 2020 Article 100 — Definitions, Voltage to Ground
225.39(C) one-family dwelling feeder disconnectvs225.39(D) all other installations

For a one-family dwelling the feeder disconnecting means shall have a rating of not less than 100 amperes, 3-wire, while all installations other than one-circuit, two-circuit, or one-family dwelling feeder disconnects require a rating of not less than 60 amperes (a detached garage supplied by a feeder falls in the 60-ampere 'all others' category unless it serves as the dwelling's main disconnect).

NEC 2020 Section 225.39(C)
225.39(B) two-circuit installationsvs225.39(D) all others

For installations of not more than two 2-wire branch circuits the feeder or branch-circuit disconnecting means shall be rated not less than 30 amperes, versus not less than 60 amperes for all other installations.

NEC 2020 Section 225.39(B)
220.82(B) optional dwelling calculationvs220.83(A) existing dwelling (no added A/C or electric space heating)

Under 220.82(B) the general calculated load is not less than 100% of the first 10 kVA plus 40% of the remainder, while under 220.83(A), where no additional air-conditioning or electric space-heating equipment is installed, the first 8 kVA of existing and new load is calculated at 100% with the remainder at 40%.

NEC 2020 Section 220.82(B)
Nontime-delay fuse (Table 430.52)vsDual-element (time-delay) fuse (Table 430.52)

For AC polyphase motors other than wound-rotor, the nontime-delay fuse maximum is 300% of motor full-load current while the dual-element (time-delay) fuse maximum is 175% of full-load current.

NEC 2020 Table 430.52, NEC 430.52(C)(1), NEC 240.6(A)
430.52(C)(1) Exception No. 1vs430.52(C)(1) Exception No. 2

Exception No. 1 permits the next higher standard rating (per 240.6(A)) when the Table 430.52 calculation does not correspond to a standard size, while Exception No. 2 permits an increase only where the motor fails to start, and in no case may the inverse time breaker exceed 400% of full-load current for motors of 100 A or less (300% for motors over 100 A) — the cap is the limit, not simply the next standard size.

NEC 2020 Table 430.52, NEC 430.52(C)(1), NEC 240.6(A)
Table 310.15(C)(1): 7 to 9 current-carrying conductorsvsTable 310.15(C)(1): 10 to 20 current-carrying conductors

With 7 to 9 current-carrying conductors in a raceway or cable the ampacity adjustment factor is 70 percent of the table values, while with 10 to 20 current-carrying conductors the factor is 50 percent.

NEC 2020 Table 310.15(C)(1)
Dwelling unit kitchen countertop receptaclesvsOther-than-dwelling (commercial) kitchen receptacles

Dwelling kitchen receptacles serving countertop surfaces require both GFCI protection (210.8(A)(6)) and AFCI protection for 120-volt, single-phase, 15- and 20-ampere branch circuits supplying outlets in dwelling unit kitchens (210.12(A)); in other than dwelling units, 125-volt through 250-volt receptacles on single-phase branch circuits rated 150 volts or less to ground and 50 amperes or less in kitchens or areas with a sink and permanent food-preparation or cooking provisions require GFCI protection (210.8(B)(2)).

NEC 2020 Section 210.8(A)(6) and 210.12(A)
225.18(1) clearance over finished grade, pedestrians onlyvs225.18(4) clearance over public streets and truck-traffic areas

Overhead spans of open conductors not over 1000 volts require a clearance of not less than 3.0 m (10 ft) above finished grade where the voltage does not exceed 150 volts to ground and the area is accessible to pedestrians only, versus not less than 5.5 m (18 ft) over public streets, alleys, roads, parking areas subject to truck traffic, driveways on other than residential property, and other land traversed by vehicles.

NEC 2020 Section 225.18(1)

Key Terms

Surge arrester NEC 2020 Article 100 — Definitions, Surge Arrester
Per NEC Article 100, a protective device for limiting surge voltages by discharging or bypassing surge current that also prevents continued flow of follow current while remaining capable of repeating these functions.
Inverter NEC 2020 Article 100 — Definitions, Inverter
Per NEC Article 100, equipment that changes dc to ac.
Switchgear NEC 2020 Article 100 — Definitions, Switchgear
Per NEC Article 100, an assembly completely enclosed on all sides and top with sheet metal (except for ventilating openings and inspection windows) containing primary power circuit switching devices, interrupting devices, or both, with buses and connections, accessed through doors or removable covers.
Continuous load NEC 2020 Article 100
Per NEC Article 100, a load where the maximum current is expected to continue for 3 hours or more; continuous loads typically require conductors and devices rated at 125% of the continuous load current.
Voltage to ground NEC 2020 Article 100 — Definitions, Voltage to Ground
Per NEC Article 100, for grounded circuits the voltage between the given conductor and the grounded point or conductor, and for ungrounded circuits the greatest voltage between the given conductor and any other conductor of the circuit.
Authority having jurisdiction (AHJ) NEC 2020 Section 90.4
Per NEC 90.4, the authority having jurisdiction for enforcement has the responsibility for making interpretations of the rules, deciding on the approval of equipment and materials, and granting special permission contemplated in a number of the rules.
Installations not covered by the NEC NEC 2020 Section 90.2(B)(1)
Per Article 90.2, the Code does not cover installations in ships, watercraft other than floating buildings, railway rolling stock, aircraft, or automotive vehicles other than mobile homes and recreational vehicles.
High-impedance grounded neutral system NEC 2020 Section 250.36
Per NEC 250.36, a system in which a grounding impedance limits the ground-fault current to a low value, permitted for 3-phase AC systems of 480 volts to 1000 volts provided all specified conditions are met.
Supply-side bonding jumper (separately derived system) NEC 2020 Section 250.30(A)(2)
Per NEC 250.30(A)(2), where the source of a separately derived system and the first disconnecting means are in separate enclosures, a supply-side bonding jumper shall be installed with the circuit conductors from the source enclosure to the first disconnecting means enclosure.
System bonding jumper of the screw type NEC 2020 Section 250.28(B)
Per NEC 250.28(B), where a main bonding jumper or system bonding jumper is a screw only, the screw shall be identified with a green finish that is visible with the screw installed.
Type S flexible cord NEC 2020 Table 400.4
Per NEC Table 400.4, a hard service cord rated 600V with thermoset insulation and thermoset outer covering, suitable for pendant or portable use in damp locations with an extra-hard usage rating.
Article 337 / Type P cable Ugly's Electrical References 2020, Page 119
Per the 2020 NEC Summary, Article 337 is a new article covering use, installation, and construction specifications for up through 2000-volt Type P cable — a factory assembly of one or more insulated flexible tinned copper conductors commonly used in drilling rig applications for offshore and onshore environments.
Grounded conductor at a separate building or structure NEC 2020 Section 250.32(B)(1)
Per NEC 250.32(B)(1), an equipment grounding conductor shall be run with the supply conductors and connected to the building disconnecting means and grounding electrode(s), and any installed grounded conductor shall not be connected to the equipment grounding conductor or to the grounding electrode(s) at the separate building or structure.
Parallel conductors NEC 2020 Section 310.10(G)(1)
Per NEC 310.10(G)(1), conductors for each phase, polarity, neutral, or grounded circuit are permitted to be connected in parallel (electrically joined at both ends) only in sizes 1/0 AWG and larger where installed per the applicable provisions.
High-leg (higher phase voltage to ground) marking NEC 2020 Section 110.15
Per NEC 110.15, on a 4-wire delta-connected system where the midpoint of one phase winding is grounded, the conductor or busbar having the higher phase voltage to ground shall be durably and permanently marked by an outer finish orange in color or by other effective means (the B phase of the 120/240-volt, three-phase, four-wire delta high-leg system).
Termination temperature rating over 100 amperes NEC 2020 Section 110.14(C)(1)(b)
Per NEC 110.14(C)(1)(b), termination provisions of equipment for circuits rated over 100 amperes, or marked for conductors larger than 1 AWG, shall be used only for conductors rated 75°C (167°F) unless the equipment is listed and identified for use with higher-rated conductors.

Formulas to Know

Ohm's Law and power formulasI = W ÷ E (e.g., 1500 W ÷ 120 V = 12.5 A); R = E ÷ I (e.g., 240 V ÷ 8 A = 30 ohms); E = I × R (e.g., 10 A × 12 ohms = 120 V); P = E × I; P = E² ÷ R (e.g., 240² ÷ 20 = 2880 W); R = E² ÷ P (e.g., 14,400 ÷ 1200 W = 12 ohms)
Three-phase calculations (1.73 multiplier = √3)Three-phase kW = (E × I × PF × 1.73) ÷ 1000 — example: (460 × 52 × 0.80 × 1.73) ÷ 1000 ≈ 33 kW; three-phase amperes when HP is known: I = (HP × 746) ÷ (E × %EFF × PF × 1.73)
Minimum service-entrance / feeder conductor ampacity with continuous and noncontinuous loadsAmpacity not less than noncontinuous load + 125% of continuous load — service-entrance example (230.42(A)(1)): 150 A + (80 A × 1.25) = 250 A; feeder example (215.2(A)(1) in NEC 2023; 215.4(A)(1) in NEC 2026): (100 A × 125%) + 30 A = 155 A
Motor branch-circuit conductor sizingBranch-circuit conductors = 125% of motor full-load current (430.22(A)) — example: 50 HP, 480 V, 3-phase at 65 A FLC × 125% = 81.25 A; for a wye-start, delta-run motor the conductors between controller and motor shall be not less than 72% of the motor full-load current rating (430.22(C)) (58% × 1.25 = 72%)
Feeder ampacity for two or more motors (430.24)Not less than 125% of the highest-rated motor FLC + sum of the full-load currents of the other motors — example: (125% × 65 A) + 40 A = 121.25 A
Motor overload device maximum trip (430.32(A)(1))For continuous-duty motors with a marked service factor of 1.15 or greater, the separate overload device shall trip at or be rated no more than 125% of the motor nameplate full-load current — example: 14 A × 125% = 17.5 A
Motor branch-circuit short-circuit and ground-fault protection (Table 430.52)AC polyphase motors other than wound-rotor: nontime-delay fuse maximum 300% of FLC (example: 65 A × 300% = 195 A; 52 A × 300% = 156 A); dual-element time-delay fuse maximum 175% of FLC (example: 65 A × 175% = 113.75 A). Inverse time circuit breaker up to 250% of FLC — SOURCE example is a single-phase motor: 50 A × 2.5 = 125 A. Exception No. 1 permits the next higher standard size from 240.6(A) (195 A → 200 A). Exception No. 2: where the motor fails to start, the rating may be increased but shall not exceed 400% of FLC for motors of 100 A or less (300% for motors over 100 A) — example: 50 A × 4 = 200 A maximum
Junction box minimum dimension for angle pulls (314.28(A)(2))Distance from raceway entry to opposite wall shall be not less than 6 × trade size of largest raceway + sum of the diameters of all other raceway entries on the same wall — example: (6 × 2) + 1 = 13 in.
One-family dwelling service conductor 83% rule (310.12(A))For a service rated 100 through 400 amperes supplying the entire load of a one-family dwelling on a single-phase, 120/240-volt system, service conductors are permitted to have an ampacity not less than 83% of the service rating — example: 200 A × 0.83 = 166 A
Rooftop ambient temperature adder (310.15(B)(2))For raceways or cables exposed to direct sunlight on or above rooftops with less than 23 mm (7/8 in.) clearance above the roof, add 33°C (60°F) to the outdoor temperature before applying correction factors — example: 40°C + 33°C = 73°C (104°F + 60°F = 164°F)