Exam Cheat Sheet · Quick Reference
ICC T16 Master Electrician Exam (2020 NEC)
National · Pearson Vue
National State Portion 100 questions
Key Distinctions
A surge arrester limits surge voltages by discharging or bypassing surge current and prevents continued flow of follow current while remaining capable of repeating these functions, whereas an SPD limits transient voltages by diverting or limiting surge current.
NEC 2020 Article 100 — Definitions, Surge ArresterPer Article 100 an inverter is equipment that changes dc to ac, while a rectifier performs the opposite function (ac to dc); a transformer changes voltage levels within the same current type and a dc-to-dc converter changes dc voltage/current levels.
NEC 2020 Article 100 — Definitions, InverterSwitchgear is completely enclosed on all sides and top with sheet metal (except ventilating openings and inspection windows) containing primary power circuit switching and/or interrupting devices with buses and connections, while a switchboard is generally accessible from the rear and not intended to be installed in cabinets and a panelboard is designed for assembly in a cabinet (a motor control center principally contains motor control units).
NEC 2020 Article 100 — Definitions, SwitchgearFor ungrounded circuits, voltage to ground is the greatest voltage between the given conductor and any other conductor of the circuit; for grounded circuits it is the voltage between the given conductor and the grounded point or conductor.
NEC 2020 Article 100 — Definitions, Voltage to GroundFor a one-family dwelling the feeder disconnecting means shall have a rating of not less than 100 amperes, 3-wire, while all installations other than one-circuit, two-circuit, or one-family dwelling feeder disconnects require a rating of not less than 60 amperes (a detached garage supplied by a feeder falls in the 60-ampere 'all others' category unless it serves as the dwelling's main disconnect).
NEC 2020 Section 225.39(C)For installations of not more than two 2-wire branch circuits the feeder or branch-circuit disconnecting means shall be rated not less than 30 amperes, versus not less than 60 amperes for all other installations.
NEC 2020 Section 225.39(B)Under 220.82(B) the general calculated load is not less than 100% of the first 10 kVA plus 40% of the remainder, while under 220.83(A), where no additional air-conditioning or electric space-heating equipment is installed, the first 8 kVA of existing and new load is calculated at 100% with the remainder at 40%.
NEC 2020 Section 220.82(B)For AC polyphase motors other than wound-rotor, the nontime-delay fuse maximum is 300% of motor full-load current while the dual-element (time-delay) fuse maximum is 175% of full-load current.
NEC 2020 Table 430.52, NEC 430.52(C)(1), NEC 240.6(A)Exception No. 1 permits the next higher standard rating (per 240.6(A)) when the Table 430.52 calculation does not correspond to a standard size, while Exception No. 2 permits an increase only where the motor fails to start, and in no case may the inverse time breaker exceed 400% of full-load current for motors of 100 A or less (300% for motors over 100 A) — the cap is the limit, not simply the next standard size.
NEC 2020 Table 430.52, NEC 430.52(C)(1), NEC 240.6(A)With 7 to 9 current-carrying conductors in a raceway or cable the ampacity adjustment factor is 70 percent of the table values, while with 10 to 20 current-carrying conductors the factor is 50 percent.
NEC 2020 Table 310.15(C)(1)Dwelling kitchen receptacles serving countertop surfaces require both GFCI protection (210.8(A)(6)) and AFCI protection for 120-volt, single-phase, 15- and 20-ampere branch circuits supplying outlets in dwelling unit kitchens (210.12(A)); in other than dwelling units, 125-volt through 250-volt receptacles on single-phase branch circuits rated 150 volts or less to ground and 50 amperes or less in kitchens or areas with a sink and permanent food-preparation or cooking provisions require GFCI protection (210.8(B)(2)).
NEC 2020 Section 210.8(A)(6) and 210.12(A)Overhead spans of open conductors not over 1000 volts require a clearance of not less than 3.0 m (10 ft) above finished grade where the voltage does not exceed 150 volts to ground and the area is accessible to pedestrians only, versus not less than 5.5 m (18 ft) over public streets, alleys, roads, parking areas subject to truck traffic, driveways on other than residential property, and other land traversed by vehicles.
NEC 2020 Section 225.18(1)Key Terms
Formulas to Know
I = W ÷ E (e.g., 1500 W ÷ 120 V = 12.5 A); R = E ÷ I (e.g., 240 V ÷ 8 A = 30 ohms); E = I × R (e.g., 10 A × 12 ohms = 120 V); P = E × I; P = E² ÷ R (e.g., 240² ÷ 20 = 2880 W); R = E² ÷ P (e.g., 14,400 ÷ 1200 W = 12 ohms)Three-phase kW = (E × I × PF × 1.73) ÷ 1000 — example: (460 × 52 × 0.80 × 1.73) ÷ 1000 ≈ 33 kW; three-phase amperes when HP is known: I = (HP × 746) ÷ (E × %EFF × PF × 1.73)Ampacity not less than noncontinuous load + 125% of continuous load — service-entrance example (230.42(A)(1)): 150 A + (80 A × 1.25) = 250 A; feeder example (215.2(A)(1) in NEC 2023; 215.4(A)(1) in NEC 2026): (100 A × 125%) + 30 A = 155 ABranch-circuit conductors = 125% of motor full-load current (430.22(A)) — example: 50 HP, 480 V, 3-phase at 65 A FLC × 125% = 81.25 A; for a wye-start, delta-run motor the conductors between controller and motor shall be not less than 72% of the motor full-load current rating (430.22(C)) (58% × 1.25 = 72%)Not less than 125% of the highest-rated motor FLC + sum of the full-load currents of the other motors — example: (125% × 65 A) + 40 A = 121.25 AFor continuous-duty motors with a marked service factor of 1.15 or greater, the separate overload device shall trip at or be rated no more than 125% of the motor nameplate full-load current — example: 14 A × 125% = 17.5 AAC polyphase motors other than wound-rotor: nontime-delay fuse maximum 300% of FLC (example: 65 A × 300% = 195 A; 52 A × 300% = 156 A); dual-element time-delay fuse maximum 175% of FLC (example: 65 A × 175% = 113.75 A). Inverse time circuit breaker up to 250% of FLC — SOURCE example is a single-phase motor: 50 A × 2.5 = 125 A. Exception No. 1 permits the next higher standard size from 240.6(A) (195 A → 200 A). Exception No. 2: where the motor fails to start, the rating may be increased but shall not exceed 400% of FLC for motors of 100 A or less (300% for motors over 100 A) — example: 50 A × 4 = 200 A maximumDistance from raceway entry to opposite wall shall be not less than 6 × trade size of largest raceway + sum of the diameters of all other raceway entries on the same wall — example: (6 × 2) + 1 = 13 in.For a service rated 100 through 400 amperes supplying the entire load of a one-family dwelling on a single-phase, 120/240-volt system, service conductors are permitted to have an ampacity not less than 83% of the service rating — example: 200 A × 0.83 = 166 AFor raceways or cables exposed to direct sunlight on or above rooftops with less than 23 mm (7/8 in.) clearance above the roof, add 33°C (60°F) to the outdoor temperature before applying correction factors — example: 40°C + 33°C = 73°C (104°F + 60°F = 164°F)