Key Distinctions
Soft conversion is a direct mathematical conversion that does not change the actual dimension and shall be used where a negative impact on safety would result; hard conversion changes dimensions or properties into new sizes.
NEC 2017 Section 90.9(C)(4)675.7(A) adds the remaining motors' nameplate full-load currents multiplied by their maximum percent duty cycle to 125% of the largest motor, while 675.22(A) adds 60% of the sum of the remaining motors to 125% of the largest motor.
NEC 2017 Section 675.7(A)675.7(B) uses the numerical sum of the locked-rotor currents of the two largest motors plus 100% of the nameplate full-load currents of all remaining motors; 675.22(B) uses two times the locked-rotor current of the largest motor plus 80% of the sum of the full-load currents of the remaining motors.
NEC 2017 Section 675.7(B)Both are rated at not less than 125% of the full-load current of the largest device served plus the full-load current of all other devices — (A) applies to power-transmitting rings and (B) applies to control and signal rings; the grounding collector ring under 675.11(C) is rated not less than the value sized by 675.11(A).
NEC 2017 Section 675.11(A)The main bonding jumper is the connection between the grounded circuit conductor and the equipment grounding conductor at the service; the system bonding jumper serves a similar function at a separately derived system.
NEC 2017 Article 100 (Definition: Bonding Jumper, Main)An insulated conductor is encased within material of composition and thickness recognized by the Code as electrical insulation; a covered conductor is encased in material not recognized as electrical insulation.
NEC 2017 Article 100 (Conductor, Insulated)Per 310.10(C) the listed types are permitted in wet locations, while THHN is a 90°C dry-and-damp-location insulation only (Table 310.104(A)) and is not permitted in wet locations such as an underground raceway.
NEC 2017 Section 310.10(C)240.4(B) permits the next higher standard rating above conductor ampacity only when that selected rating does not exceed 800 amperes; where the device is rated over 800 amperes, 240.4(C) requires conductor ampacity to be equal to or greater than the device rating.
NEC 2017 Section 240.4(B)Per 240.10, supplementary overcurrent protection shall not be used as a substitute for required branch-circuit overcurrent devices or in place of the required branch-circuit protection.
NEC 2017 Section 240.10Per 90.3, Chapters 1 through 4 apply generally to all electrical installations, Chapters 5, 6, and 7 apply to special occupancies, special equipment, or other special conditions and may supplement or modify Chapters 1 through 7, and Chapter 8 (communications systems) is independent except where specifically referenced.
NEC 2017 Section 90.3Per 90.5(C), informational notes are included for informational purposes only and are not enforceable as requirements of the Code.
NEC 2017 Section 90.5(C)Per 220.14(I), each single or multiple receptacle on one yoke is calculated at not less than 180 volt-amperes, but a single piece of equipment consisting of a multiple receptacle comprised of four or more receptacles is calculated at not less than 90 volt-amperes per receptacle.
NEC 2017 Section 220.14(I)Where lighting units or cord-and-plug-connected equipment not fastened in place are also supplied, fastened-in-place utilization equipment (other than luminaires) shall not exceed 50% of the branch-circuit rating, whereas a single cord-and-plug-connected appliance not fastened in place is limited to 80% of the branch-circuit rating.
NEC 2017 Section 210.23(A)(2)Per 240.4(F), 2-wire single-phase and delta-delta 3-wire secondary conductors are permitted to be protected by the primary-side device, while single-phase (other than 2-wire) and multiphase (other than delta-delta, 3-wire) secondary conductors shall not be considered protected by the primary overcurrent protective device.
NEC 2017 Section 240.4(F)Key Terms
Formulas to Know
(1.25 × largest motor nameplate FLC) + (sum of remaining motors' nameplate FLC × maximum percent duty cycle). Examples: (1.25×10)+(16×0.50)=20.5 A; (1.25×10)+(20×0.50)=22.5 A; (1.25×16)+(20×0.50)=30 A; (1.25×20)+(18×0.50)=34 A(1.25 × largest motor nameplate FLC) + (0.60 × sum of remaining motors' nameplate FLC). Examples: (1.25×12)+(0.60×30)=33 A; (1.25×16)+(0.60×25)=35 A; (1.25×14)+(0.60×31.5)=36.4 A; (1.25×15)+(0.60×12)=25.95 ALRC of largest motor + LRC of second-largest motor + 100% of the sum of the nameplate FULL-LOAD currents of all remaining motors (not their locked-rotor currents). Examples: 60+48+(3×6)=126 A; 90+72+(3×8)=186 A(2 × locked-rotor current of largest motor) + (0.80 × sum of full-load currents of remaining motors). Example: (2×60)+(0.80×40)=152 A(1.25 × full-load current of largest device served) + (full-load current of all other devices served). Examples: (1.25×16)+(3×8)=44 A; (1.25×16)+(4×7)=48 A(1.25 × full-load current of largest device served) + (full-load current of all other devices). Example: (1.25×8)+3+2+2=17 ATotal rating shall not exceed 50% of branch-circuit ampere rating. Example: 50% × 20 A = 10 ASum of (number of conductors × area per conductor from Table 5). Example: 7×0.0211 + 3×0.0133 + 1×0.0133 = 0.201 sq inTotal conductor area must fit within 31% of raceway area. Examples: two 10 AWG THHN = 2×0.0211 = 0.042 sq in → smallest EMT whose 31% area (0.094 sq in) is at least that is ½ in; two 4/0 AWG THHN = 2×0.3237 = 0.647 sq in → 2 in EMT (31% = 1.040 sq in)Number = 40% raceway area ÷ area per conductor; a resulting decimal of 0.8 or larger rounds up, below 0.8 is dropped. Example: 1 in EMT 40% = 0.346 sq in ÷ 0.0366 sq in (8 AWG THHN) = 9.45 → 9 conductors