Idaho Plumbing Specialty Water Pump Journeyman Exam
Idaho · PSI Services Contractor
Idaho State Portion 50 questions
Key Distinctions
"Accessible" means access may first require removing an access panel, door, or similar obstruction, while "Readily Accessible" means direct access without removing any panel, door, or obstruction.
ISPC 2017 Section 203.0A brazed joint uses alloys melting above 840°F (449°C) but below the melting point of the parts joined; a soldered joint uses metallic mixtures or alloys melting at temperatures up to and including 840°F (449°C).
ISPC 2017 Section 212.0 - Joint, BrazedContamination is an impairment of potable water quality creating an actual health hazard through poisoning or spread of disease (High Hazard), while pollution does not create a health hazard but adversely and unreasonably affects aesthetic qualities (Low Hazard).
ISPC 2017 Section 218.0 (Pollution)A soil pipe conveys the discharge of water closets, urinals, clinical sinks or similar fixtures (with or without other fixture discharge), whereas a waste pipe conveys only liquid waste free of fecal matter.
ISPC 2017 Section 220.0 - Soil PipeA wet vent also serves as a drain, while a dry vent does not receive the discharge of any sewage or waste.
ISPC 2017 Section 222.0 - Wet Vent"Shall" indicates a mandatory requirement; "Should" indicates a recommendation or advice that is not required, and "May" is a permissive term.
ISPC 2017 Section 220.0 - ShallThe tailpiece connects the outlet of a plumbing fixture to the trap, while the trap arm is the portion of the fixture drain between the trap and the vent.
ISPC 2017 Section 221.0 - TailpieceThe building supply carries potable water from the water meter or other source to the building or point of use on the lot; a water distribution pipe conveys water within the building from the building supply to fixtures and outlets, and a fixture supply connects the fixture to the fixture branch.
ISPC 2017 Section 204.0 - Building SupplyA riser is a water supply pipe extending vertically one full story or more to convey water to branches or fixtures; a fixture supply is the water supply pipe connecting an individual fixture to the fixture branch.
ISPC 2017 Section 219.0 - RiserAn application for which no permit is issued expires by limitation 180 days after the application date, while an issued permit becomes null and void if the authorized work is not commenced within 180 days from the date of the permit (requiring a new permit).
ISPC 2017 Section 104.3.3Tests of 10 psi or less require gauges of 0.10 psi incrementation or less, while tests exceeding 10 psi but not more than 100 psi require gauges of 1 psi incrementation or less; in both cases the gauge range must not exceed twice the test pressure applied.
ISPC 2017 Sections 318.3 and 318.5The invert is the lowest portion of the inside of a horizontal pipe, whereas grade is the slope or fall of a line of pipe in reference to a horizontal plane.
ISPC 2017 Section 211.0 - InvertA battery of fixtures is two or more similar, adjacent fixtures discharging into a common horizontal waste or soil branch — not into a common vertical waste or soil stack.
ISPC 2017 Section 204.0Key Terms
Formulas to Know
Static pressure (psi) = height of water above the point (ft) × 0.433 psi/ft; for a gravity system between two elevations use the elevation difference (e.g., 150 ft − 74 ft = 76 ft × 0.433 = 32.91 psi, then subtract friction losses).Height (ft) = pressure (psi) ÷ 0.433 psi/ft, or equivalently pressure (psi) × 2.31 ft/psi (2.31 is the reciprocal of 0.433).Available psi = static pressure at main/meter − (height above meter × 0.433) − meter loss − other device losses (e.g., backflow preventer) − minimum required residual/flow pressure at the fixture.Rate (psi/100 ft) = (available friction pressure ÷ total equivalent length including fittings) × 100.Equivalent length = developed length (service + main + riser + branch) × 1.5 (adding the printed 50% allowance for fittings).For each outlet compute: main static pressure − meter loss − (elevation ft × 0.433) − required flow pressure at that outlet; the outlet with the LEAST remaining pressure governs the design (may not be the highest outlet).Pump discharge psi = (lift height ft × 0.433) + piping friction loss + required residual pressure at the fixture (street main pressure and meter loss affect inlet conditions, not the discharge requirement).Cylinder: V = π × r² × h (use radius, not diameter); half-cylinder trough: V = (π × r² × L) ÷ 2; convert to gallons by multiplying cubic feet × 7.48 gal/ft³ (convert inch dimensions to feet first).Minutes = (L × W × D in cubic feet × 7.48 gal/ft³) ÷ flow rate in gpm.Trench width = 1.25 × outside diameter + 12 in, OR outside diameter + 16 in (for a 4-in OD pipe: 17 in or 20 in; use 20 in to satisfy both).