Exam Cheat Sheet · Quick Reference

Kansas Journeyman Mechanical Exam (ICC KGG, 2018 IMC/IFGC)

Kansas  ·  Pearson Vue

Verified, not estimated. Every figure below is drawn from the official exam structure we maintain — question counts, passing standard and topic weighting. Practice questions are grounded in the source law with statute citations. We omit any figure we can't verify rather than guess at it.
Total questions
50
Passing score
75%
Exam time
180 min
Administered by
Pearson Vue
Format
Reference materials allowed

Kansas State Portion 50 questions

Administration General Regulations 11 Q · 22%
General Installation RequirementsPlan ReadingPermits and permit applicationsInspections and testing requirementsCode official duties and authorityViolations, stop work orders, and penaltiesMeans of appeal and board of appealsDefinitions of key mechanical code termsApplicability to existing installations and alterationsGeneral Regulations
Appliances & Mechanical Equipment 11 Q · 22%
Heating Equipment & Gen App InstallationWater Heaters and BoilersCooling and Refrigeration SystemsHydronic and Other SystemsRefrigerant Classification & Safety Groups (ASHRAE 34 toxicity/flammability ratings)Machinery Room Requirements (construction, ventilation rates, refrigerant detectors, emergency controls)Refrigerant Piping Materials, Joints & Stop ValvesMaximum Allowable Refrigerant Quantities by OccupancySpecific Gas-Fired Appliance Installation (wall furnaces, floor furnaces, unit heaters, duct furnaces, unvented room heaters)Clothes Dryer Exhaust Systems (duct materials, length limits, termination requirements)Solar Thermal System Design & Installation (freeze protection, pressure relief, heat exchangers, potable water protection)Boiler Safety Controls, Relief Valves & Low-Water Cutoffs +1 more
Exhaust and Ventilation Systems 7 Q · 14%
Exhaust Fan & Product Conveying SystemsCommercial Hoods & Kitchen VentilationClothes Dryer Exhaust SystemsMakeup Air Requirements for Exhaust SystemsHazardous Exhaust SystemsSmoke Control SystemsExhaust Discharge Location & Outlet ClearancesMechanical Ventilation Rates by OccupancyEnclosed Parking Garage VentilationEnergy Recovery Ventilation SystemsExhaust Systems
Duct Systems 8 Q · 16%
Duct Construction, Installation & PlenumsSmoke and Fire DampersReturn Air System Requirements and RestrictionsDuct Insulation, Coverings, and Vapor RetardersAir Filters in Duct SystemsSmoke Detection Systems for Air DistributionFlexible Duct and Flexible Air Connector RequirementsUnderground and Exterior Duct InstallationRegisters, Grilles, and DiffusersDuct Systems
Combustion Air 4 Q · 8%
Venting of Fuel Burning AppliancesIndoor combustion air volume requirements (standard method and known air-infiltration-rate method)Outdoor combustion air opening methods (two-permanent-openings and one-permanent-opening)Combustion air opening sizing for louvers, grilles, and screensCombustion air duct requirements and installation restrictionsCombination indoor and outdoor combustion air methodMechanical combustion air supply systems and appliance interlock requirementsMakeup air provisions for exhaust fans and ventilation interferenceDampered combustion air openings and interlock requirements for oil-fired and solid-fuel appliancesChapter 3 General Regulations
Chimneys and Vents 5 Q · 10%
Venting of Fuel Burning AppliancesChimney and Vent ConnectorsAppliance venting categories and vent type selection (Table 503.4 / Table 802.2)Vent and chimney termination height and location requirementsSizing of Category I appliance venting systems using tables (Section 504)Masonry chimney requirements including flue lining materials and cleanoutsFactory-built chimney listing, installation, and support requirementsDraft hoods, draft controls, and automatically operated vent dampersAppliances not required to be vented and aggregate input rate limitsDirect-vent, mechanical draft, and integral vent system termination requirementsChapter 5 Chimneys and Vents
Gas Piping and Fuel Supply Systems 4 Q · 8%
Fuel Supply Installation, Testing and SizingApproved piping materials and tubing types (steel, copper, CSST, polyethylene, aluminum)Piping joints, fittings, and connection methodsProhibited piping locations and installation restrictionsUnderground piping installation, burial depth, and corrosion protectionShutoff valves and pressure regulatorsOverpressure protection devices and pressure limitationsPiping support intervals and spacing requirementsFuel oil piping materials, joints, valves, and system componentsChapter 4 Gas Piping Installations

Key Distinctions

General requirement (IMC 102.1)vsSpecific requirement (IMC 102.1)

Where a general requirement conflicts with a requirement written specifically for the appliance being installed, the specific requirement governs; the separate 'most restrictive governs' rule applies only where different sections specify different materials, methods or other requirements.

IMC 2018 Section 102.1
Longest length method (IFGC 402.4.1)vsBranch length method (IFGC 402.4.2)

The longest length method sizes every section from the longest length of piping from the point of delivery to the most remote outlet, while the branch length method sizes each branch using that branch's own length from the meter (e.g., a 120 cfh branch at its own 50 ft needs 3/4 inch, whereas the longest length 90-ft row would call for 1 inch).

IFGC 2018 Section 402.4.1
One-permanent-opening method for outdoor combustion air (IFGC 304.6.2)vsTwo-permanent-openings method with horizontal ducts (IFGC 304.6.1)

The one-permanent-opening method requires 1 square inch per 3,000 Btu/h of total input (and not less than the sum of the areas of all vent connectors), while each opening of the two-opening horizontal-duct method requires 1 square inch per 2,000 Btu/h of total input; 1 in² per 4,000 Btu/h reflects the vertical two-opening method.

IFGC 2018 Section 304.6.2 — One-permanent-opening method
Wood louvers of unknown design/free areavsMetal louvers and grilles of unknown design/free area

Per IFGC 304.10, when design and free area are not known, wood louvers are assumed to have 25-percent free area and metal louvers and grilles 75-percent free area, so the same 100 in² net free area needs 400 in² gross with wood versus 133 in² with metal.

IFGC 2018 Section 304.10 — Louvers and grilles
Fire damper in a duct not part of a smoke control systemvsFire damper located in a smoke control system

Per IMC 607.3.3.1 Item 1, the non-smoke-control damper's actuation device operates at approximately 50°F above normal duct temperature but not less than 160°F; the 350°F figure is the maximum operating temperature permitted under Item 2 for dampers in a smoke control system.

IMC 2018 Chapter 6 — Section 607.3.3.1 Fire damper actuation device
Indoor purging of gas pipingvsOutdoor purging of gas piping

Per IFGC 406.7.1, piping systems with a design operating gas pressure greater than 2 psig must be purged outdoors; indoor purging (such as through an appliance burner) is allowed only for systems at 2 psig or less that also do not meet the size and length criteria of Table 406.7.1.1.

IFGC 2018 Section 406.7.1
Halocarbon refrigerant machinery room emergency exhaustvsAmmonia system machinery room ventilation

Per IMC 1105.6.3.2, halocarbon machinery room emergency exhaust on detector actuation is Q = 100 × √G (G = design refrigerant mass of the largest system with parts in the room), while the 30 air-changes-per-hour rate applies only to ammonia systems.

IMC 2018 Chapter 11 — Section 1105.6.3.2, Book
Gas piping materials permittedvsCast-iron pipe

Per IFGC 403.4.1 steel pipe, copper tubing and CSST are permitted when meeting their respective standards, but cast-iron pipe shall not be used for gas piping.

IFGC 2018 Section 403.4.1
CSST without an arc-resistant jacketvsAbove-ground gas piping other than CSST

CSST lacking an arc-resistant jacket requires a bonding jumper not smaller than 6 AWG copper wire or equivalent (IFGC 310.2.2), while each above-ground portion of a gas piping system other than CSST that is likely to become energized must be electrically continuous and bonded to an effective ground-fault current path (IFGC 310.1).

IFGC 2018 Section 310.2.2
Appliance in a private garage (IFGC 305.5)vsAppliance in a public/repair garage frequented by motor vehicles (IMC 304.6)

IFGC 305.5 requires appliances in private garages to be installed with a minimum clearance of 6 feet above the floor (exception where protected from vehicle impact with ignition source elevated per 305.3), while IMC 304.6 requires not less than 8 feet above the floor in public/repair garages and, where vehicles can pass under the appliance, not less than 1 foot higher than the tallest vehicle garage door opening.

IFGC 2018 Section 305.5
Type I hood exhaust fan started by direct appliance interlockvsType I hood exhaust fan started by temperature or radiant energy sensors

Per IMC 507.1.1, where one or more temperature or radiant energy sensors are used instead of a direct interlock, the fan must activate not more than 15 minutes after the first appliance served by that hood is turned on.

IMC 2018 Section 507.1.1
Appliances required to be ventedvsAppliances not required to be vented (IFGC 501.8)

Vented wall furnaces, Category I furnaces and draft-hood-equipped water heaters require venting systems, while direct-fired makeup air heaters are listed in Item 9 as not required to be vented; however, where appliances in Items 5 through 11 exceed an aggregate 20 Btu/h per cubic foot of room volume, one or more must be provided with venting.

IFGC 2018 Section 501.8

Key Terms

Longest length method (IFGC 402.4.1) IFGC 2018 Section 402.4.1
A gas pipe sizing method in which the size of each section is determined from the longest length of piping from the point of delivery to the most remote outlet and the load of that section.
Branch length method (IFGC 402.4.2) IFGC Section 402.4.2, Branch Length Method; Table 402.4(2), Schedule 40 Metallic Pipe (natural gas, 0.5 in. w.c. drop)
A gas pipe sizing method in which each branch is sized using its own length measured from the meter (e.g., 30 ft + 20 ft of main to the tee + 15 ft of branch = 65 ft, read in the 70-ft row).
Refrigeration capacity rating (IMC 202) IMC 2018 Section 202 — Refrigeration Capacity Rating
A rating in which 1 horsepower, 1 ton and 12,000 Btu/h all mean the same quantity.
CSST bonding jumper (IFGC 310.2.2, 310.2.3) IFGC 2018 Section 310.2.2
For CSST without an arc-resistant jacket, a jumper not smaller than 6 AWG copper wire or equivalent, whose length between the gas piping connection and the grounding electrode system connection shall not exceed 75 feet (added electrodes must be bonded to the electrical service grounding electrode system).
Standard method for indoor combustion air (IFGC 304.5.1) IFGC 2018 Section 304.5.1
A method requiring a minimum room volume of 50 cubic feet per 1,000 Btu/h of appliance input rating.
Mechanical combustion air supply interlock (IFGC 304.9.2) IFGC 2018 Section 304.9.2
Each appliance served by a mechanical combustion air supply system must be interlocked with that system to prevent main burner operation when the mechanical air supply system is not in operation.
Fire damper actuation device (IMC 607.3.3.1) IMC 2018 Chapter 6 — Section 607.3.3.1 Fire damper actuation device
The device that closes a fire damper, operating at approximately 50°F above the normal duct temperature but not less than 160°F, except that 350°F is the maximum operating temperature permitted for dampers in a smoke control system.
Type B or L gas vent termination (IFGC 503.6.6) IFGC 2018 Section 503.6.6
A Type B or L gas vent shall terminate not less than 5 feet in vertical height above the highest connected appliance draft hood outlet or flue collar.
Vent connector (IFGC 503.10.7, 503.10.8, 501.9) IFGC 2018 Section 503.10.7
The connector must be installed without dips or sags and slope upward toward the vent or chimney not less than 1/4 inch per foot; a single-wall connector's maximum horizontal length is 75 percent of the chimney or vent height (except engineered systems), and it must connect to a masonry chimney flue not less than 12 inches above the lowest portion of the flue interior.
Draft hood relief opening (IFGC 503.12.7) IFGC 2018 Section 503.12.7
The draft hood must be located so its relief opening is not less than 6 inches from any surface except that of the appliance it serves and the connected venting system.
Mechanical draft venting system terminal (IFGC 503.8, Item 2) IFGC 2018 Section 503.8
Excluding direct-vent appliances, the terminal shall be not less than 4 feet below, 4 feet horizontally from, or 1 foot above any door, operable window or gravity air inlet into any building.
Vent insulation shield (IFGC 502.4) IFGC 2018 Section 502.4
Where vents pass through attic space, the shield shall terminate not less than 2 inches above the insulation materials and be secured in place to prevent displacement.
Unvented room heater (IFGC 621.3, 621.4, 621.6) IFGC 2018 Section 621.3
A room heater whose input rating shall not exceed 40,000 Btu/h, prohibited in Group A, E and I occupancies, and equipped with an oxygen-depletion-sensitive safety shutoff that shuts off gas when oxygen is depleted to the manufacturer's specified concentration but not lower than 18 percent.
Appliance shutoff valve location (IFGC 409.1.2) IFGC 2018 Section 409.1.2
Shutoff valves are prohibited in concealed locations and in furnace plenums.
Means of access to roof equipment (IMC 306.5) IMC 2018 Section 306.5
A permanent interior or exterior means of access, not requiring portable ladders, is required where personnel must climb higher than 16 feet above grade to reach equipment on a roof or elevated structure, measured to the top of the parapet where access involves climbing over parapet walls.
Operation of replacement equipment before inspection (IMC 107.2) IMC 2018 Section 107.2
Heating equipment or appliances replacing existing units serving an occupied portion of a structure may be operated provided no portion is concealed by permanent construction and an inspection request is filed not more than 48 hours after the replacement work is completed.

Formulas to Know

Dwelling unit continuous outdoor air ventilation (IMC 403.3.2.1, Equation 4-9)QOA = 0.01 × Afloor + 7.5 × (Nbr + 1); example: 0.01(2,400 sq ft) + 7.5(4 + 1) = 24 + 37.5 = 61.5 cfm (omitting the '+1' gives the 54 cfm distractor)
Refrigeration machinery room emergency exhaust on detector actuation (IMC 1105.6.3.2, Equation 11-2)Q = 100 × √G, where G = design mass of refrigerant (lb) in the largest system with any part in the room; examples: 100 × √900 = 3,000 cfm; 100 × √625 = 2,500 cfm (30 ACH applies only to ammonia systems)
Repair garage exhaust for CNG, LNG and other lighter-than-air fueled vehicles, other than hydrogen (IMC 502.16.2.1)Not less than 1 cfm per 12 cubic feet of room volume (lighter-than-air fuels other than hydrogen); examples: 60 × 30 × 10 = 18,000 ft³ ÷ 12 = 1,500 cfm; 4,800 ft³ ÷ 12 = 400 cfm
Gas demand in cubic feet per hour for table sizing (IFGC longest length/branch methods, Table 402.4(2))cfh = total connected Btuh ÷ 1,000 (natural gas, 1,000 Btu per cu ft); examples: (65,000 + 40,000 + 50,000) ÷ 1,000 = 155 cfh; 247 cfh × 1,000 = 247,000 Btuh of capacity
Dryer exhaust duct maximum straight length (IFGC 614.8.4.1 and Table 614.8.4.1)Maximum straight duct = 35 ft total equivalent length − sum of fitting equivalent lengths; example: two 4-in. radius mitered 90° elbows (5 ft each = 10 ft) + one 4-in. radius mitered 45° elbow (2 ft 6 in.) = 12 ft 6 in.; 35 − 12.5 = 22 ft 6 in.
Hydronic piping hydrostatic test (IMC 1208.1)Test at 1.5 × maximum system design pressure but not less than 100 psi, for not less than 15 minutes; example: 1.5 × 60 psi = 90 psi, so the 100 psi floor governs
Fire damper actuation temperature (IMC 607.3.3.1, Item 1)Approximately normal duct temperature + 50°F, but not less than 160°F; examples: 140 + 50 = 190°F; 100 + 50 = 150°F → 160°F governs
Combustion air opening free area from outdoors (IFGC 304.6.1, 304.6.2)One-permanent-opening method: 1 in² per 3,000 Btu/h total input and not less than the sum of all vent connector areas (example: 90,000 ÷ 3,000 = 30 in²); two-opening horizontal duct method: 1 in² per 2,000 Btu/h per opening (90,000 → 45 in²); vertical two-opening figure is 1 in² per 4,000 Btu/h (22.5 in²)
Gross opening area behind louvers of unknown free area (IFGC 304.10)Gross area = required net free area ÷ assumed free area (wood louvers 25 percent; metal louvers/grilles 75 percent); example: 100 in² ÷ 0.25 = 400 in² for wood (÷ 0.75 = 133 in² for metal)
Natural ventilation through an adjoining room (IMC 402.2, 402.3)Opening between rooms = not less than 8 percent of the interior room floor area but not less than 25 sq ft (0.08 × 240 = 19.2 → 25 sq ft governs); openable area to outdoors = 4 percent of the TOTAL floor area ventilated (0.04 × (240 + 360) = 24 sq ft)