Exam Cheat Sheet · Quick Reference
North Carolina Electrical Contractor - Ground Water Pump (SP-WP)
North Carolina · PSI Services Contractor
North Carolina State Portion 40 questions
Key Distinctions
Per 90.3, Chapter 8 is NOT subject to the requirements of Chapters 1 through 7 except where those requirements are specifically referenced in Chapter 8.
NEC 2020 Section 90.3Per 90.5(C), informational notes are included for informational purposes only and are not enforceable as requirements of the Code.
NEC 2020 Section 90.5(C)220.82(B) takes not less than 100% of the first 10 kVA plus 40% of the remainder, while 220.83(A) takes the first 8 kVA at 100% and the remainder at 40%.
NEC 2020 Section 220.82(B)The two-circuit installation requires a rating of not less than 30 amperes, while the one-family dwelling feeder disconnect requires not less than 100 amperes, 3-wire.
NEC 2020 Section 225.39(B)The 100-ampere, 3-wire minimum applies specifically to the dwelling's own feeder disconnect; all other installations (such as a detached garage supplied by a feeder, not serving as the dwelling's main disconnect) require not less than 60 amperes.
NEC 2020 Section 225.39(C)Where the voltage does not exceed 150 volts to ground and the area is accessible to pedestrians only, clearance is not less than 3.0 m (10 ft); over public streets, alleys, roads, parking areas subject to truck traffic and nonresidential driveways it is not less than 5.5 m (18 ft).
NEC 2020 Section 225.18(1)Nontime-delay fuses are rated at 300% of motor full-load current, while dual element time-delay fuses have a maximum rating of 175% of full-load current (other than wound-rotor).
NEC 2020 Table 430.52, NEC 430.52(C)(1), NEC 240.6(A)Branch-circuit conductors for a single continuous-duty motor must be not less than 125% of that motor's full-load current, while feeder conductors must be not less than 125% of the highest-rated motor plus the sum of the full-load currents of the other motors.
NEC 2020 Section 430.22Controller-to-motor conductors for a part-winding motor need not less than 62.5% of full-load current, whereas the line-side branch-circuit conductors use 125% and a wye-start, delta-run motor uses 72%.
NEC 2020 Section 430.22(D)GFCI protection is required for receptacles serving countertop surfaces, and AFCI protection is separately required for all 120-volt, single-phase, 15- and 20-ampere branch circuits supplying outlets in dwelling unit kitchens — both apply.
NEC 2020 Section 210.8(A)(6) and 210.12(A)The EGC is run with the supply conductors and connected to the building disconnecting means and grounding electrode(s), while any installed grounded conductor shall NOT be connected to the EGC or to the grounding electrode(s) there.
NEC 2020 Section 250.32(B)(1)Per the NASCLA Summary of Business Legal Structures table, a C corporation allows unlimited shareholders with no personal liability and is taxed at the corporate level plus tax on dividends (double taxation), while an S corporation is limited to 100 shareholders and uses pass-through taxation.
NASCLA Contractors Guide, North Carolina Electrical (14th ed.), Chapter 2 — Summary of Business Legal Structures tableKey Terms
Formulas to Know
Ampacity ≥ 125% × motor full-load current; example: 125% × 65 A (50 HP, 480 V, 3-phase) = 81.25 AAmpacity ≥ (125% × FLC of highest-rated motor) + sum of FLCs of other motors; example: (125% × 65 A) + 40 A = 121.25 A300% × FLC, then next higher standard size permitted if not standard; example: 300% × 65 A = 195 A → 200 A standard fuse175% × FLC before exceptions; example: 65 A × 175% = 113.75 A, then next higher standard rating permitted per 430.52(C)(1) Ex. 1Not more than 125% × nameplate FLC; example: 28 A × 125% = 35 A (if insufficient, 430.32(C) permits incremental increases up to 140%)Ampacity ≥ 62.5% × motor FLC; example: 34 A × 0.625 = 21.25 AAmpacity permitted to be not less than 83% × service rating; example: 200 A × 0.83 = 166 AAdjusted ampacity = table ampacity × 50%; example: 10 AWG THHN copper 90°C = 40 A → 40 × 0.50 = 20 AAmbient for correction factors = outdoor temperature + 33°C (60°F); example: 40°C + 33°C = 73°C (104°F + 60°F = 164°F)Distance ≥ (6 × trade size of largest raceway) + sum of diameters of all other raceway entries on the same wall; example: (6 × 2) + 1 = 13 in.