Exam Cheat Sheet · Quick Reference
Philadelphia Master Electrician Exam (ICC 211, 2020 NEC)
Pennsylvania · Pearson Vue
Pennsylvania State Portion 100 questions
Key Distinctions
Per NEC 2020 Article 100, a surge arrester limits surge voltages by discharging or bypassing surge current and prevents continued flow of follow current while remaining capable of repeating these functions, whereas an SPD limits transient voltages by diverting or limiting surge current.
NEC 2020 Article 100 — Definitions, Surge ArresterPer NEC 2020 Article 100, switchgear is completely enclosed on all sides and top with sheet metal (except ventilating openings and inspection windows) and contains primary power circuit switching/interrupting devices with buses and connections, while a switchboard is generally accessible from the rear and not intended for installation in cabinets and a panelboard is designed for assembly in a cabinet (a motor control center principally contains motor control units).
NEC 2020 Article 100 — Definitions, SwitchgearPer NEC 2020 Article 100, for ungrounded circuits voltage to ground is the greatest voltage between the given conductor and any other conductor of the circuit, while for grounded circuits it is the voltage between the given conductor and the grounded point or conductor.
NEC 2020 Article 100 — Definitions, Voltage to Ground220.82(B) takes 100 percent of the first 10 kVA plus 40 percent of the remainder of the listed loads, while 220.83(A) (used when no additional air-conditioning or electric space-heating equipment is being installed) takes 100 percent of the first 8 kVA plus 40 percent of the remainder.
NEC 2020 Section 220.82(B)A one-family dwelling's feeder disconnecting means must be rated not less than 100 amperes, 3-wire, while all installations other than one-circuit, two-circuit, or one-family dwelling disconnects require not less than 60 amperes; installations of not more than two 2-wire branch circuits require not less than 30 amperes under 225.39(B).
NEC 2020 Section 225.39(C)The inner-edge radius shall not be less than five times the cable diameter for Type AC (320.24) and Types NM/NMC (334.24), but not less than seven times the external diameter of the metallic sheath for interlocked-type armor or corrugated sheath Type MC (330.24(B)).
NEC 2020 Section 320.24For AC polyphase motors other than wound-rotor, the nontime-delay fuse maximum is 300 percent of full-load current while the dual-element time-delay fuse maximum is 175 percent, with the next higher standard size permitted under 430.52(C)(1) Exception No. 1 when the calculation does not match a standard size.
NEC 2020 Table 430.52The table maximum for an inverse time circuit breaker is 250 percent of motor full-load current, but if the motor will not start at that rating the breaker may be increased only up to 400 percent of full-load current for motors of 100 A or less (300 percent above 100 A), which is a cap rather than simply the next standard size.
NEC Section 430.52(C)(1), Exception No. 2; Table 430.52(C)(1)In the delta high-leg system the B phase (higher phase voltage to ground) must be colored orange or tagged — and per NEC 110.15 the conductor or busbar with the higher phase voltage to ground on a 4-wire delta system with a grounded phase-winding midpoint must be durably and permanently marked orange or by other effective means — whereas in the 277/480-volt wye system the C phase ungrounded conductor is colored yellow.
Ugly's Electrical References, 2023 ed., Common Electrical Distribution Systems, Page 13 (2020 ed.: Common Electrical Distribution Systems)Dwelling kitchen countertop receptacles require GFCI protection per 210.8(A)(6) and AFCI protection per 210.12(A) for 120-volt, single-phase, 15- and 20-ampere branch circuits supplying outlets, while in other than dwelling units 210.8(B)(2) requires GFCI protection for 125-volt through 250-volt receptacles on single-phase branch circuits rated 150 volts or less to ground and 50 amperes or less in kitchens or areas with a sink and permanent provisions for food preparation or cooking.
NEC 2020 Section 210.8(A)(6) and 210.12(A)For overhead spans of open conductors not over 1000 volts, clearance shall be not less than 3.0 m (10 ft) above finished grade where the voltage does not exceed 150 volts to ground and the area is accessible to pedestrians only, but not less than 5.5 m (18 ft) over public streets, alleys, roads, parking areas subject to truck traffic, driveways on other than residential property, and other land traversed by vehicles.
NEC 2020 Section 225.18(1)Per NEC 300.14, where the opening to an outlet, junction, or switch point is less than 200 mm (8 in.) in any dimension each conductor must extend at least 75 mm (3 in.) outside the opening, which is a distinct requirement from the general 150 mm (6 in.) free conductor rule.
NEC 2020 Section 300.14Key Terms
Formulas to Know
Amperes = Watts ÷ Volts (1500 W ÷ 120 V = 12.5 A); Ohms = Volts ÷ Amperes (240 V ÷ 8 A = 30 ohms); E = I × R (10 A × 12 ohms = 120 V)P = E × I (volts × amperes = watts); P = E² ÷ R (240² ÷ 20 = 2,880 W); R = E² ÷ P (14,400 ÷ 1,200 = 12 ohms, same as R = E ÷ I)kW = (E × I × PF × 1.73) ÷ 1000; example: (460 × 52 × 0.80 × 1.73) ÷ 1000 ≈ 33 kW (1.73 = √3, used in all three-phase formulas)I = (HP × 746) ÷ (E × %EFF × PF × 1.73)Service-entrance conductors (230.42(A)(1)): ampacity not less than noncontinuous load + 125% of continuous load — example 150 A + (80 A × 1.25) = 250 A. Feeder (2020 NEC 215.2(A)(1)(a)): (100 A × 125%) + 30 A = 155 A minimum.Branch-circuit conductors (430.22(A)): 125% of motor full-load current — example 65 A × 125% = 81.25 A. Feeder (430.24): 125% of the highest-rated motor + sum of full-load currents of the other motors — example (65 A × 125%) + 40 A = 121.25 A. Wye-start, delta-run conductors between controller and motor (430.22(C)): not less than 72% of motor full-load current (58% × 1.25).AC polyphase motor other than wound-rotor: nontime-delay fuse 300% of FLC (65 A × 300% = 195 A; 52 A × 300% = 156 A), dual-element time-delay fuse 175% of FLC (65 A × 175% = 113.75 A). Inverse time circuit breaker: up to 250% of FLC (single-phase motor example, 50 A × 2.5 = 125 A). Where the calculated value is not a standard size, 430.52(C)(1) Exception No. 1 permits the next higher standard size per 240.6(A) (195 A → 200 A); 430.52(C)(1) Exception No. 2 permits increase if the motor fails to start but shall in no case exceed 400% of FLC for motors of 100 A or less (300% above 100 A), e.g., 50 A × 4 = 200 A.Per 430.32(A)(1), for a continuous-duty motor with marked service factor of 1.15 or greater, a separate overload device shall trip at or be rated not more than 125% of nameplate full-load current — example 14 A × 125% = 17.5 APer 310.12(A), for a service rated 100 through 400 amperes supplying the entire load of a one-family dwelling on a single-phase 120/240-volt system, service conductors are permitted an ampacity not less than 83% of the service rating — example 200 A × 0.83 = 166 A7–9 current-carrying conductors: 70% of the table values; 10–20 current-carrying conductors: 50% — example 10 AWG THHN copper at 90°C = 40 A, 40 × 0.50 = 20 A adjusted ampacity