Exam Cheat Sheet · Quick Reference

Philadelphia Master Electrician Exam (ICC 211, 2020 NEC)

Pennsylvania  ·  Pearson Vue

Verified, not estimated. Every figure below is drawn from the official exam structure we maintain — question counts, passing standard and topic weighting. Practice questions are grounded in the source law with statute citations. We omit any figure we can't verify rather than guess at it.
Total questions
100
Passing score
75%
Exam time
300 min
Administered by
Pearson Vue
Format
Reference materials allowed

Pennsylvania State Portion 100 questions

General Knowledge and Plan Reading 12 Q · 12%
Electrical Theory and General Electrical Load CalculationsCode Definitions and TermsPlan ReadingNEC Code Structure, Scope, and Enforcement (Article 90)General Requirements for Electrical Installations (Article 110)Working Space and Clearance Requirements for Electrical EquipmentEquipment Approval, Listing, Labeling, and Marking RequirementsConductor Types, Sizes, and Electrical ConnectionsCommon Electrical Distribution Systems and Wiring Diagram SymbolsAC/DC Circuit Theory: Series, Parallel, and Combination CircuitsPower Factor, Impedance, Reactance, Inductance, and Capacitance Calculations
Services and Service Equipment 16 Q · 16%
Services and Fault CurrentService Load CalculationsService Equipment & Service ConductorsTransformersSystem Grounding and BondingTemporary Service WiringService Disconnecting Means Requirements and RatingsOverhead and Underground Service Conductor Installation and ClearancesGrounding Electrode System Types and InstallationSurge-Protective Devices (SPDs) and Surge Arresters at ServicesService Equipment Workspace, Guarding, and Labeling RequirementsAvailable Fault Current Field Marking and Short-Circuit Current Ratings
Feeders 4 Q · 4%
Load CalculationsEquipment GroundingFeeder conductor ampacity and minimum sizing requirementsOvercurrent protection for feedersFeeder neutral load calculationsDemand factors for dwelling and non-dwelling feeder loadsOutside feeder clearances and installation requirementsFeeder disconnecting means for separate buildings and structuresCommon neutral conductor provisions for feedersGround-fault protection of equipment for feeder disconnects
Branch Circuits and Conductors 16 Q · 16%
Branch Circuit CalculationOvercurrent ProtectionConductorsRequired Outlets & GFCI/AFCI ProtectionEquipment GroundingConductor Ampacity Tables and Temperature RatingsAmpacity Correction and Adjustment FactorsVoltage Drop CalculationsConductor Identification and Color CodingMultiwire Branch Circuit RequirementsBranch Circuit Voltage LimitationsConduit Fill Calculations
Wiring Methods and Materials 19 Q · 19%
Raceway InstallationsUnderground Wiring MethodsBoxes and EnclosuresCabinets, Panelboards, & SwitchboardsClearance and GuardingFlexible Cords and CablesCable Types and Their Permitted and Prohibited Uses (NM, MC, AC, MI, TC, SE, UF, and specialty types)Conductor Fill Calculations and Conduit Sizing (Chapter 9 Tables, percent fill, nipple fill)Conduit Bending Techniques (90-degree, offset, saddle, back-to-back, developed length, shrink)Securing and Supporting Requirements for Wiring Methods (support intervals for RMC, PVC, EMT, FMC, LFMC, cables)Wireway, Auxiliary Gutter, Busway, and Cable Tray Systems (fill limits, uses permitted, splices and taps)NEMA Enclosure Types and Environmental Ratings +2 more
Equipment and Devices 10 Q · 10%
LuminairesReceptacles, Switches and Other DevicesAppliances and Other EquipmentOther Utilization EquipmentHeating and Cooling EquipmentFixture Wire Types, Ampacities, and Installation RequirementsNEMA Receptacle and Attachment Plug ConfigurationsLuminaire Installation in Specific Locations (wet, damp, closets, bathtubs)Recessed Luminaire Clearances and Thermal Protection RequirementsLighting Track Installation and Load RequirementsLow-Voltage Lighting System Requirements (Article 411)Disconnecting Means for Fixed Electric Heating and A/C Equipment +1 more
Control Devices 3 Q · 3%
Switches, Disconnects and ControllersMotor controller ratings and marking requirements (NEC 430.8, 430.83)Motor control circuit overcurrent protection and wiring methods (NEC 430.71–430.75)Disconnecting means for motors and controllers (NEC 430.101–430.113)Motor overload protection devices and settings (NEC 430.32–430.44)Industrial control panel overcurrent protection and short-circuit current ratings (NEC 409.21–409.22)Class 1 remote-control circuit requirements and overcurrent protection (NEC Article 725)Stop-start station and jogging control circuit configurationsHand-off-automatic (HOA) control circuit wiring
Motors and Generators 8 Q · 8%
MotorsGeneratorsMotor circuit conductor sizing and ampacity requirementsMotor branch-circuit short-circuit and ground-fault protective device ratings (Table 430.52)Motor overload protection requirements and trip current percentagesMotor disconnecting means requirements and ratingsMotor controllers — ratings, marking, and design requirementsFull-load current table values for DC, single-phase, and three-phase AC motorsLocked-rotor code letters and locked-rotor current calculationsPhase converters — installation, conductor sizing, and disconnecting means
Special Occupancies, Equipment, and Conditions 12 Q · 12%
Special OccupanciesSwimming Pools and Similar InstallationsMobile Home and RV ParksData Processing EquipmentMiscellaneous Special EquipmentEmergency SystemsSignaling and Fire Alarm SystemsHazardous Location Classification (Class I, II, III / Division and Zone Systems)Specific Hazardous Location Occupancies (Garages, Hangars, Motor Fuel Dispensing, Bulk Storage, Spray/Dip/Coating)Health Care Facilities Wiring and Isolated Power SystemsStandby and Alternate Power Systems (Emergency, Legally Required, Optional, COPS)Alternative and Distributed Energy Systems (Solar PV, Wind, Fuel Cell, Energy Storage) +3 more

Key Distinctions

Surge arrestervsSurge-protective device (SPD)

Per NEC 2020 Article 100, a surge arrester limits surge voltages by discharging or bypassing surge current and prevents continued flow of follow current while remaining capable of repeating these functions, whereas an SPD limits transient voltages by diverting or limiting surge current.

NEC 2020 Article 100 — Definitions, Surge Arrester
SwitchgearvsSwitchboard / panelboard

Per NEC 2020 Article 100, switchgear is completely enclosed on all sides and top with sheet metal (except ventilating openings and inspection windows) and contains primary power circuit switching/interrupting devices with buses and connections, while a switchboard is generally accessible from the rear and not intended for installation in cabinets and a panelboard is designed for assembly in a cabinet (a motor control center principally contains motor control units).

NEC 2020 Article 100 — Definitions, Switchgear
Voltage to ground — ungrounded circuitsvsVoltage to ground — grounded circuits

Per NEC 2020 Article 100, for ungrounded circuits voltage to ground is the greatest voltage between the given conductor and any other conductor of the circuit, while for grounded circuits it is the voltage between the given conductor and the grounded point or conductor.

NEC 2020 Article 100 — Definitions, Voltage to Ground
Optional dwelling calculation, NEC 220.82(B)vsExisting dwelling additional-load calculation, NEC 220.83(A)

220.82(B) takes 100 percent of the first 10 kVA plus 40 percent of the remainder of the listed loads, while 220.83(A) (used when no additional air-conditioning or electric space-heating equipment is being installed) takes 100 percent of the first 8 kVA plus 40 percent of the remainder.

NEC 2020 Section 220.82(B)
Feeder disconnect for a one-family dwelling, NEC 225.39(C)vsFeeder/branch-circuit disconnect for all other installations, NEC 225.39(D)

A one-family dwelling's feeder disconnecting means must be rated not less than 100 amperes, 3-wire, while all installations other than one-circuit, two-circuit, or one-family dwelling disconnects require not less than 60 amperes; installations of not more than two 2-wire branch circuits require not less than 30 amperes under 225.39(B).

NEC 2020 Section 225.39(C)
Bending radius for Type AC and Type NM cablevsBending radius for interlocked-armor/corrugated-sheath Type MC cable

The inner-edge radius shall not be less than five times the cable diameter for Type AC (320.24) and Types NM/NMC (334.24), but not less than seven times the external diameter of the metallic sheath for interlocked-type armor or corrugated sheath Type MC (330.24(B)).

NEC 2020 Section 320.24
Nontime-delay fuse for AC polyphase motor (Table 430.52)vsDual-element (time-delay) fuse for AC polyphase motor (Table 430.52)

For AC polyphase motors other than wound-rotor, the nontime-delay fuse maximum is 300 percent of full-load current while the dual-element time-delay fuse maximum is 175 percent, with the next higher standard size permitted under 430.52(C)(1) Exception No. 1 when the calculation does not match a standard size.

NEC 2020 Table 430.52
Table 430.52(C)(1) maximum inverse time circuit breaker (250%)vs430.52(C)(1) Exception No. 2 increase where the motor fails to start

The table maximum for an inverse time circuit breaker is 250 percent of motor full-load current, but if the motor will not start at that rating the breaker may be increased only up to 400 percent of full-load current for motors of 100 A or less (300 percent above 100 A), which is a cap rather than simply the next standard size.

NEC Section 430.52(C)(1), Exception No. 2; Table 430.52(C)(1)
120/240-volt, three-phase, four-wire delta high-leg systemvs277/480-volt, three-phase, four-wire wye system

In the delta high-leg system the B phase (higher phase voltage to ground) must be colored orange or tagged — and per NEC 110.15 the conductor or busbar with the higher phase voltage to ground on a 4-wire delta system with a grounded phase-winding midpoint must be durably and permanently marked orange or by other effective means — whereas in the 277/480-volt wye system the C phase ungrounded conductor is colored yellow.

Ugly's Electrical References, 2023 ed., Common Electrical Distribution Systems, Page 13 (2020 ed.: Common Electrical Distribution Systems)
Dwelling-unit kitchen countertop receptaclesvsOther-than-dwelling (commercial) kitchen receptacles

Dwelling kitchen countertop receptacles require GFCI protection per 210.8(A)(6) and AFCI protection per 210.12(A) for 120-volt, single-phase, 15- and 20-ampere branch circuits supplying outlets, while in other than dwelling units 210.8(B)(2) requires GFCI protection for 125-volt through 250-volt receptacles on single-phase branch circuits rated 150 volts or less to ground and 50 amperes or less in kitchens or areas with a sink and permanent provisions for food preparation or cooking.

NEC 2020 Section 210.8(A)(6) and 210.12(A)
Overhead clearance over areas accessible to pedestrians only, NEC 225.18(1)vsOverhead clearance over public streets and areas subject to truck traffic, NEC 225.18(4)

For overhead spans of open conductors not over 1000 volts, clearance shall be not less than 3.0 m (10 ft) above finished grade where the voltage does not exceed 150 volts to ground and the area is accessible to pedestrians only, but not less than 5.5 m (18 ft) over public streets, alleys, roads, parking areas subject to truck traffic, driveways on other than residential property, and other land traversed by vehicles.

NEC 2020 Section 225.18(1)
Free conductor length where the box opening is less than 200 mm (8 in.)vsGeneral free conductor rule

Per NEC 300.14, where the opening to an outlet, junction, or switch point is less than 200 mm (8 in.) in any dimension each conductor must extend at least 75 mm (3 in.) outside the opening, which is a distinct requirement from the general 150 mm (6 in.) free conductor rule.

NEC 2020 Section 300.14

Key Terms

Surge arrester NEC 2020 Article 100 — Definitions, Surge Arrester
Per NEC 2020 Article 100, a protective device for limiting surge voltages by discharging or bypassing surge current that also prevents continued flow of follow current while remaining capable of repeating these functions.
Surge-protective device (SPD) NEC 2020 Article 100 — Definitions, Surge Arrester
A device that limits transient voltages by diverting or limiting surge current, as distinguished from a surge arrester in NEC 2020 Article 100.
Inverter NEC 2020 Article 100 — Definitions, Inverter
Per NEC 2020 Article 100, equipment that changes dc to ac (a rectifier does the opposite, ac to dc).
Switchgear NEC 2020 Article 100 — Definitions, Switchgear
Per NEC 2020 Article 100, an assembly completely enclosed on all sides and top with sheet metal (except for ventilating openings and inspection windows) containing primary power circuit switching, interrupting devices, or both, with buses and connections, accessed through doors or removable covers.
Panelboard NEC 2020 Article 100 — Definitions, Switchgear
Per NEC 2020 Article 100, equipment designed for assembly in a cabinet (shown on wiring plans as a solid filled rectangle).
Continuous load NEC 2020 Article 100
Per NEC 2020 Article 100, a load where the maximum current is expected to continue for 3 hours or more; continuous loads typically require conductors and devices rated at 125 percent of the continuous load current.
Authority having jurisdiction (AHJ) NEC 2020 Section 90.4
Per NEC 90.4, the authority having jurisdiction for enforcement of the Code is responsible for making interpretations of the rules, deciding on approval of equipment and materials, and granting special permission contemplated in a number of the rules.
Installations not covered by the NEC NEC 2020 Section 90.2(B)(1)
Per NEC 2020 90.2(B)(1), the Code does not cover installations in ships, watercraft other than floating buildings, railway rolling stock, aircraft, or automotive vehicles other than mobile homes and recreational vehicles.
Supply-side bonding jumper (separately derived system) NEC 2020 Section 250.30(A)(2)
Per NEC 250.30(A)(2), where the source of a separately derived system and the first disconnecting means are in separate enclosures, a supply-side bonding jumper shall be installed with the circuit conductors from the source enclosure to the first disconnecting means enclosure.
System bonding jumper of the screw type NEC 2020 Section 250.28(B)
Per NEC 250.28(B), where a main bonding jumper or a system bonding jumper is a screw only, the screw shall be identified with a green finish that is visible with the screw installed.
High-impedance grounded neutral system NEC 2020 Section 250.36
Per NEC 250.36, a system in which a grounding impedance limits ground-fault current to a low value; permitted for 3-phase AC systems of 480 volts to 1000 volts provided all specified conditions are met.
Type P cable (Article 337) Ugly's Electrical References 2020, Page 119
Per the 2020 NEC summary, Article 337 is a new article covering use, installation, and construction specifications for up through 2000-volt Type P cable, a factory assembly of one or more insulated flexible tinned copper conductors commonly used in drilling rig applications for offshore and onshore environments.
Type S flexible cord NEC 2020 Table 400.4
Per NEC Table 400.4, a hard service cord rated 600V with thermoset insulation and thermoset outer covering, suitable for pendant or portable use in damp locations with an extra-hard usage rating.
Pull point NEC 2020 Section 358.26
A point such as a conduit body that terminates a conduit section for bend-counting purposes, so that each section between pull points may contain up to 360 degrees of bends (NEC 2020 358.26 for EMT; NEC 2023/2026 358.24(B)).
S₃ (electrical plan symbol) Ugly's Electrical References 2020, Page 125
Designates a three-way switch on an electrical plan (S₂ is a double-pole switch, S₄ a four-way switch, and Sₑ an electrolier switch).
DPDT Ugly's Electrical References 2020, Page 126
Double Pole Double Throw — a drawing abbreviation for a switching contact that controls two separate circuits, each with two positions.

Formulas to Know

Ohm's Law basic relationshipsAmperes = Watts ÷ Volts (1500 W ÷ 120 V = 12.5 A); Ohms = Volts ÷ Amperes (240 V ÷ 8 A = 30 ohms); E = I × R (10 A × 12 ohms = 120 V)
Ohm's Law power formulasP = E × I (volts × amperes = watts); P = E² ÷ R (240² ÷ 20 = 2,880 W); R = E² ÷ P (14,400 ÷ 1,200 = 12 ohms, same as R = E ÷ I)
Three-phase kilowatts from measured volts, amps and power factorkW = (E × I × PF × 1.73) ÷ 1000; example: (460 × 52 × 0.80 × 1.73) ÷ 1000 ≈ 33 kW (1.73 = √3, used in all three-phase formulas)
Three-phase amperes when horsepower is knownI = (HP × 746) ÷ (E × %EFF × PF × 1.73)
Conductor sizing for continuous plus noncontinuous loadsService-entrance conductors (230.42(A)(1)): ampacity not less than noncontinuous load + 125% of continuous load — example 150 A + (80 A × 1.25) = 250 A. Feeder (2020 NEC 215.2(A)(1)(a)): (100 A × 125%) + 30 A = 155 A minimum.
Motor circuit conductor ampacityBranch-circuit conductors (430.22(A)): 125% of motor full-load current — example 65 A × 125% = 81.25 A. Feeder (430.24): 125% of the highest-rated motor + sum of full-load currents of the other motors — example (65 A × 125%) + 40 A = 121.25 A. Wye-start, delta-run conductors between controller and motor (430.22(C)): not less than 72% of motor full-load current (58% × 1.25).
Motor branch-circuit short-circuit and ground-fault protection maximums (Table 430.52)AC polyphase motor other than wound-rotor: nontime-delay fuse 300% of FLC (65 A × 300% = 195 A; 52 A × 300% = 156 A), dual-element time-delay fuse 175% of FLC (65 A × 175% = 113.75 A). Inverse time circuit breaker: up to 250% of FLC (single-phase motor example, 50 A × 2.5 = 125 A). Where the calculated value is not a standard size, 430.52(C)(1) Exception No. 1 permits the next higher standard size per 240.6(A) (195 A → 200 A); 430.52(C)(1) Exception No. 2 permits increase if the motor fails to start but shall in no case exceed 400% of FLC for motors of 100 A or less (300% above 100 A), e.g., 50 A × 4 = 200 A.
Motor overload device maximum trip/ratingPer 430.32(A)(1), for a continuous-duty motor with marked service factor of 1.15 or greater, a separate overload device shall trip at or be rated not more than 125% of nameplate full-load current — example 14 A × 125% = 17.5 A
One-family dwelling service conductor 83% rulePer 310.12(A), for a service rated 100 through 400 amperes supplying the entire load of a one-family dwelling on a single-phase 120/240-volt system, service conductors are permitted an ampacity not less than 83% of the service rating — example 200 A × 0.83 = 166 A
Ampacity adjustment for more than three current-carrying conductors (Table 310.15(C)(1))7–9 current-carrying conductors: 70% of the table values; 10–20 current-carrying conductors: 50% — example 10 AWG THHN copper at 90°C = 40 A, 40 × 0.50 = 20 A adjusted ampacity