Philadelphia Master Electrician (ICC 211, 2020 NEC) Practice Exam Guide
What's on the exam
Questions per topic, out of 100This practice exam is laid out like the official content outline for the Philadelphia Master Electrician (ICC 211, 2020 NEC) exam: General Knowledge and Plan Reading, Services and Service Equipment, Feeders, Branch Circuits and Conductors, Wiring Methods and Materials, Equipment and Devices, Control Devices, Motors and Generators, Special Occupancies, Equipment, and Conditions.
Two ways to practice: the free practice exam gives you 10 questions per attempt, as often as you want. The full practice exam gives you 100 questions on a 5 hours clock, with a new draw from our question bank every time.
General Knowledge and Plan Reading 12 items
Our study plan for this topic: Electrical Theory and General Electrical Load Calculations; Code Definitions and Terms; Plan Reading; NEC Code Structure, Scope, and Enforcement (Article 90); General Requirements for Electrical Installations (Article 110); Working Space and Clearance Requirements for Electrical Equipment; Equipment Approval, Listing, Labeling, and Marking Requirements; Conductor Types, Sizes, and Electrical Connections.
Services and Service Equipment 16 items
Our study plan for this topic: Services and Fault Current; Service Load Calculations; Service Equipment & Service Conductors; Transformers; System Grounding and Bonding; Temporary Service Wiring; Service Disconnecting Means Requirements and Ratings; Overhead and Underground Service Conductor Installation and Clearances.
Feeders 4 items
Our study plan for this topic: Load Calculations; Equipment Grounding; Feeder conductor ampacity and minimum sizing requirements; Overcurrent protection for feeders; Feeder neutral load calculations; Demand factors for dwelling and non-dwelling feeder loads; Outside feeder clearances and installation requirements; Feeder disconnecting means for separate buildings and structures.
Branch Circuits and Conductors 16 items
Our study plan for this topic: Branch Circuit Calculation; Overcurrent Protection; Conductors; Required Outlets & GFCI/AFCI Protection; Equipment Grounding; Conductor Ampacity Tables and Temperature Ratings; Ampacity Correction and Adjustment Factors; Voltage Drop Calculations.
Wiring Methods and Materials 19 items
Our study plan for this topic: Raceway Installations; Underground Wiring Methods; Boxes and Enclosures; Cabinets, Panelboards, & Switchboards; Clearance and Guarding; Flexible Cords and Cables; Cable Types and Their Permitted and Prohibited Uses (NM, MC, AC, MI, TC, SE, UF, and specialty types); Conductor Fill Calculations and Conduit Sizing (Chapter 9 Tables, percent fill, nipple fill).
Equipment and Devices 10 items
Our study plan for this topic: Luminaires; Receptacles, Switches and Other Devices; Appliances and Other Equipment; Other Utilization Equipment; Heating and Cooling Equipment; Fixture Wire Types, Ampacities, and Installation Requirements; NEMA Receptacle and Attachment Plug Configurations; Luminaire Installation in Specific Locations (wet, damp, closets, bathtubs).
Control Devices 3 items
Our study plan for this topic: Switches, Disconnects and Controllers; Motor controller ratings and marking requirements (NEC 430.8, 430.83); Motor control circuit overcurrent protection and wiring methods (NEC 430.71–430.75); Disconnecting means for motors and controllers (NEC 430.101–430.113); Motor overload protection devices and settings (NEC 430.32–430.44); Industrial control panel overcurrent protection and short-circuit current ratings (NEC 409.21–409.22); Class 1 remote-control circuit requirements and overcurrent protection (NEC Article 725); Stop-start station and jogging control circuit configurations.
Motors and Generators 8 items
Our study plan for this topic: Motors; Generators; Motor circuit conductor sizing and ampacity requirements; Motor branch-circuit short-circuit and ground-fault protective device ratings (Table 430.52); Motor overload protection requirements and trip current percentages; Motor disconnecting means requirements and ratings; Motor controllers — ratings, marking, and design requirements; Full-load current table values for DC, single-phase, and three-phase AC motors.
Special Occupancies, Equipment, and Conditions 12 items
Our study plan for this topic: Special Occupancies; Swimming Pools and Similar Installations; Mobile Home and RV Parks; Data Processing Equipment; Miscellaneous Special Equipment; Emergency Systems; Signaling and Fire Alarm Systems; Hazardous Location Classification (Class I, II, III / Division and Zone Systems).
Sample 1 — Wiring Methods and Materials
Question: You are a journeyman electrician installing PVC conduit on the exterior of a warehouse. The area is subject to physical damage from forklifts and loading equipment. Which type of PVC conduit is identified for use in areas of physical damage?
- A. Schedule 40 PVC
- B. Type EB PVC
- C. Schedule 20 PVC
- D. Schedule 80 PVC
Correct Answer: D
Per NEC 352.10(F), PVC conduit used exposed in areas of physical damage shall be identified for the use. The Informational Note states that PVC Conduit, Type Schedule 80, is identified for areas of physical damage.
Reference: NEC 2020 Section 352.10(F)
Sample 2 — Services and Service Equipment
Question: A 400 A service uses 600 kcmil copper service conductors. What is the minimum size of a copper grounding electrode conductor that runs only to a concrete-encased electrode?
- A. 2 AWG
- B. 4 AWG
- C. 3/0 AWG
- D. 1/0 AWG
Correct Answer: B
Table 250.66 would require a 1/0 AWG copper grounding electrode conductor for 600 kcmil copper service conductors, but 250.66(B) says a grounding electrode conductor (or bonding jumper) that runs only to a concrete-encased electrode is not required to be larger than 4 AWG copper. So the minimum size required here is 4 AWG copper.
Reference: NEC 2020 Section 250.66(B), Table 250.66
Sample 3 — Branch Circuits and Conductors
Question: A single-family dwelling with a 120/240-volt, single-phase service has a calculated load of 154 amps. Using 75°C rated copper THWN-2 conductors, what is the minimum service conductor size?
- A. 1 AWG
- B. 1/0 AWG
- C. 2/0 AWG
- D. 3/0 AWG
Correct Answer: B
Step 1: A 154 A calculated load needs a service rated at least 154 A; the next standard rating is 175 A (240.6(A)).
Step 2: For a one-family dwelling supplied by a 120/240-volt, single-phase service, the NEC permits service conductors with an ampacity of not less than 83% of the service rating (310.12(A)): 175 A × 0.83 = 145.25 A.
Step 3: In the 75°C copper column of Table 310.16, 1 AWG = 130 A (too small) and 1/0 AWG = 150 A, so 1/0 AWG copper is the minimum. Table 310.12(A) likewise lists 1/0 AWG copper for a 175 A dwelling service.
2/0 AWG (175 A) is what you get by sizing for the full 154 A with Table 310.16 alone, without the dwelling allowance.
Reference: NEC 2020 Table 310.12 (310.12(A))
Your first attempt is an inspection, not a final grade. The results page breaks your score down by outline topic, so you can see which areas need work. Compare it with the real exam's passing score, a minimum score of 75, and keep practicing until you pass consistently.
- Answer what you know first and bookmark the rest. Our practice exams let you bookmark and come back.
- Work your bookmarks on the second pass.
- Keep your pace. The real exam works out to about 3 minutes per question.
- After each attempt, look up each missed question's reference in your book and read the section.
| Questions | 100 questions |
| Time limit | 5 hours |
| Passing score | a minimum score of 75 |
| Books in the exam room | Open book |
| Exam fee | $115 |
- Results for examinations taken electronically are available immediately after the examination is completed.
- A candidate must wait 10 days before retaking a failed exam.
Source: Philadelphia, Pennsylvania Contractor/Trades Examination Information Bulletin, PUBLISHED March 15, 2026. Check the bulletin before test day: fees and rules can change.