Idaho HVAC Specialty Journeyman Exam
Practice at the real exam's pace
Every practice exam shows your time per question against the real exam's clock (2:24 here), and each topic lands in one of these:
What's on the exam
Questions per topic, out of 50Topics
2018 International Fuel Gas Code (IFGC) - Chapter 1
Idaho HVAC Specialty Journeyman Exam
Key Concepts
Scope (Section 101.2). The code applies to installation of fuel-gas piping systems, fuel gas appliances, gaseous hydrogen systems and related accessories per Sections 101.2.1 through 101.2.5. Exception: detached one- and two-family dwellings and multiple single-family dwellings (townhouses) not more than three stories high with separate means of egress, and their accessory structures, shall comply with the International Residential Code.
Piping pressures (Section 101.2.2). Covers natural gas piping with an operating pressure of 125 psig (862 kPa gauge) or less, and LP-gas at 20 psig (140 kPa gauge) or less, except as provided in Section 402.7. Coverage extends from the point of delivery to the outlet of the appliance shutoff valves, and includes design, materials, components, fabrication, assembly, installation, testing, inspection, operation and maintenance.
Gas appliances (Section 101.2.3). Requirements include installation, combustion and ventilation air and venting and connections to piping systems.
2018 International Fuel Gas Code (IFGC) - Chapter 2
Idaho HVAC Specialty Journeyman Exam
Key Concepts
Purpose and structure of Chapter 2. Chapter 2 exists to maintain a consensus on the specific meaning of each term contained in the code. It is split into Section 201 (IFGC) General and Section 202 (IFGC) General Definitions.
Section 201.1 Scope. Unless otherwise expressly stated, the words and terms listed in Chapter 2 have the meanings indicated in that chapter, for the purposes of the code and standard.
Section 201.2 Interchangeability. Words in the present tense include the future; the masculine gender includes the feminine and neuter; the singular includes the plural and the plural, the singular.
Section 201.3 Terms Defined in Other Codes. "Where terms are not defined in this code and are defined in the International Building Code, International Fire Code, International Mechanical Code or International Plumbing Code, such terms shall have meanings ascribed to them as in those codes." (Idaho note: IDAPA 24.39.70 states that all references to the International Plumbing Code are construed as referring to the Idaho State Plumbing Code as adopted and amended by the Idaho State Plumbing Board.)
2018 International Fuel Gas Code (IFGC) - Chapter 3
Key Concepts
Listing, labeling and prohibited locations - Appliances "shall be listed and labeled for the application in which they are used unless otherwise approved in accordance with Section 105"; approval of unlisted appliances is based on approved engineering evaluation (§301.3). - A permanent factory-applied nameplate must show manufacturer's name or trademark, model number, serial number and, for listed appliances, the testing agency seal; the label includes the hourly Btu/h rating, approved fuel type and minimum clearance requirements (§301.5). - Appliances, equipment and systems regulated by this code shall not be located in an elevator shaft (§301.15). - Appliances shall not be located in sleeping rooms, bathrooms, toilet rooms, storage closets or surgical rooms, or spaces opening only into them, except per the six listed conditions (§303.3): direct-vent appliances (Item 1); a single wall-mounted unvented room heater in a bathroom at not more than 6,000 Btu/h (Item 3); the same in a bedroom at not more than 10,000 Btu/h (Item 4), both equipped per §621.6 and meeting the volume criteria of §304.5; a clothes dryer in a residential bathroom/toilet room with a permanent opening of not less than 100 square inches (Item 6). - Pit installations: sides of the…
2018 International Fuel Gas Code (IFGC) - Chapter 4
Key Concepts
- Scope. Chapter 4 governs the design, installation, modification and maintenance of piping systems, from the point of delivery to the connections with the appliances (Section 401.1). Utility service piping inside buildings follows the structural safety and fire protection provisions of the International Building Code (Section 401.1.1); LP-gas storage follows the International Fire Code and NFPA 58 (Section 401.2).
- Modifications and added appliances. In modifying or adding to existing systems, sizes shall be maintained in accordance with Chapter 4 (Section 401.3). Where an additional appliance is to be served, the existing piping shall be checked for adequate capacity for all appliances served; if inadequate, the existing system shall be enlarged or separate piping of adequate capacity provided (Section 401.4, Page 4-1).
- Identification of piping. For other than steel pipe, exposed piping shall be identified by a yellow label marked "Gas" in black letters, spaced at intervals not exceeding 5 feet (1524 mm); marking is not required on pipe in the same room as the appliance served (Section 401.5).
- Multiple meters. Where two or more meters are installed on the same premises but supply separate consumers, the piping systems **shall not be interconnected on the…
2018 International Fuel Gas Code (IFGC) - Chapter 5
Key Concepts
General venting requirements (Section 501) - Every appliance shall discharge products of combustion to the outdoors, except appliances exempted by Section 501.8 (501.2). - Where an appliance with a mechanical forced draft system creates a positive pressure in the venting system, the venting system shall be designed for positive pressure applications (501.6). - Unvented appliances in Items 5 through 11 (booster water heater, refrigerators, counter appliances, room heaters listed for unvented use, direct-fired makeup air heaters, other listed unvented appliances, specialized limited-input appliances): where aggregate input exceeds 20 Btu per hour per cubic foot of room volume, one or more must be vented so the remaining unvented input does not exceed that limit (501.8). - Connectors shall connect to a masonry chimney flue not less than 12 inches above the lowest portion of the interior of the chimney flue (501.9; see also 503.10.10). - Appliance connections to a chimney or vent with a power exhauster shall be made on the inlet side of the exhauster (501.10). - Masonry flue linings for residential-type/low-heat and Category I appliances: clay lining per ASTM C315, listed systems per UL 1777, or approved materials resisting flue gases to 1,800°F (501.12, 501.13, 503.5.3).…
2018 International Fuel Gas Code (IFGC) - Chapter 6
Idaho HVAC Specialty Journeyman Exam — 2018 International Fuel Gas Code (IFGC) (Idaho), Chapter 6
Key Concepts
Scope (Section 601.1). Chapter 6 governs approval, design, installation, construction, maintenance, alteration and repair of the specifically identified appliances. Nearly every section also requires installation "in accordance with the manufacturer's instructions."
Vented wall furnaces (Section 608). - Door swing: located so a door cannot swing within 12 inches (305 mm) of an air inlet or air outlet, measured at right angles to the opening. Doorstops or door closers shall not be installed to obtain this clearance (608.4). - Ducts shall not be attached to wall furnaces; casing extension boots are prohibited unless listed as part of the appliance (608.5). - Installed between bathrooms and adjoining rooms, they shall not circulate air from bathrooms to other parts of the building (608.3).
2018 International Fuel Gas Code (IFGC) - Chapter 7
2018 International Fuel Gas Code (IFGC), Chapter 7 (with related Chapter 1 and Chapter 2 provisions)
Key Concepts
Scope and jurisdiction - "Gaseous hydrogen systems shall be regulated by Chapter 7." (Section 101.2.1) - Gaseous hydrogen systems are within the code's scope. Items outside the scope (Section 101.2.4) include portable LP-gas appliances not connected to a fixed fuel piping system (item 1), oxygen-fuel gas cutting and welding systems (item 4), LP-gas installations at utility gas plants (item 8), and installation of hydrogen gas, LP-gas and compressed natural gas (CNG) systems on vehicles (item 15). - Chapter 2 (Section 202) defines "HYDROGEN FUEL-GAS ROOM" and "HYDROGEN-GENERATING APPLIANCE" by directing the reader to See Section 702.1. - Installation shall comply with Chapter 7 and Chapters 53 and 58 of the International Fire Code; compressed gases also comply with IFC Chapter 50 (Section 701.1). Permits per Section 106 and the IFC (Section 701.2).