New Jersey Master HVACR Contractor Exam

50 questions 130 minutes 70% to pass 8 topics 2:36 per question Open book
Try 10 free questions Free Cheat Sheet Official Bulletin

Practice at the real exam's pace

Every practice exam shows your time per question against the real exam's clock (2:36 here), and each topic lands in one of these:

Ready Find it faster Study it Needs both Rushing: slow down

What's on the exam

Questions per topic, out of 50
Electrical Knowledge, Motors, and Controls7
Piping - Refrigeration, Hydronic, Steam, Process7
Heating and Cooling Principles, Theory, and Equipment8
Refrigerants and Refrigeration8
Fuel and LP Gas5
Combustion Air, Chimneys, Flues and Vents5
Ducts, Ventilation and Exhaust5
Load Calculations5

Topics

Open a topic to read its key concepts

Electrical Knowledge, Motors, and Controls

7 on exam · 36 practice questions

Key Concepts

Ohm's Law and the power wheel. Ohm's Law relates voltage (E, volts), current (I, amperes), and resistance (R, ohms): E = I × R, I = E ÷ R, R = E ÷ I. Power in watts is added through the chart formulas P = E × I, P = E² ÷ R, and P = I² × R (Ugly's Electrical References, 2023 ed., Ohm's Law, Page 1). Modern Refrigeration and Air Conditioning (22nd ed.) calls P = I × E Watt's law (Section 14.1.1, Page 273) and states Ohm's law resistance as R = E ÷ I (Section 13.1.3, Page 256).

Series circuits — three rules (Ugly's, Series Circuits, Page 3): - Rule 1: Total current equals the current in any other part of the circuit — IT = I₁ = I₂ = I₃. - Rule 2: Total voltage equals the sum of the voltage drops — ET = E₁ + E₂ + E₃. - Rule 3: Total resistance equals the sum of the resistances — RT = R₁ + R₂…

Piping - Refrigeration, Hydronic, Steam, Process

7 on exam · 34 practice questions

Key Concepts

Tubing identification and materials (Modern Refrigeration and Air Conditioning, 22nd ed., Ch. 5) - ACR tubing size is designated by the actual outside diameter; copper water tubing nominal size = OD minus 1/8″ (p. 71, Sec. 5.1.1). - Copper tubing comes in Type K (heavy wall) and Type L (medium wall); Type L is the commonly used type (Sec. 5.1.1). - Steel pipe is not generally used to circulate refrigerant; the major exception is ammonia refrigeration systems, because ammonia may chemically react with copper tubing (p. 74, Sec. 5.2.3). - Plastic pipe maximum service temperatures: ABS 180°F (82°C) (span –40°F to 180°F), PVC safe range –100°F to 175°F, CPVC 210°F (99°C); CPVC is rated for 100 psi (700 kPa) water pressure at 180°F (82°C) (p. 73, Sec. 5.2.2).

Heating and Cooling Principles, Theory, and Equipment

8 on exam · 41 practice questions

Key Concepts

Compression cycle dividers. The compressor divides the low side from the high side on the discharge end; the metering device is the other divider at the opposite end of the cycle (Ch. 8, p. 128).

Liquid line. All systems should have a liquid line filter-drier installed to keep moisture, dirt, and metal out of the metering device — install a new one whenever the system is opened to replace a component such as a TXV or capillary tube (Section 8.3.3, p. 130; Ch. 20). Some flash gas is acceptable, but excessive flash gas in the liquid line reduces evaporator efficiency and can damage an expansion valve (Section 8.3.2, p. 130).

Compressors. Scroll: vapor pockets shrink toward the center and discharge through the center port (Section 9.1.2, p. 141). Scroll capacity is modulated by a bypass port partway between the outer edge and the center of the fixed scroll, a variable-speed motor, or briefly separating the scrolls — not by cylinder unloaders (Section 9.1.2, p. 141). Reciprocating compressors with cylinder unloaders usually unload…

Refrigerants and Refrigeration

8 on exam · 38 practice questions

Refrigerants and Refrigeration (8 questions, 16%)

Key Concepts

Cylinders and cylinder safety - Recovery cylinders are identified by gray paint on the lower portion and yellow paint on the upper portion (Ch. 11, p. 189, Section 11.1.3). - A refillable refrigerant cylinder should be filled no more than 80% — liquid expands as temperature rises and can rupture an overfilled cylinder (Ch. 2, p. 21, "Refrigerant Cylinder Safety"). - DOT: cylinders that have contained a corrosive refrigerant must be inspected and recertified every five years; cylinders containing noncorrosive refrigerants every ten years (Ch. 11, p. 188). - Tare weight = the weight of the cylinder when empty, stamped on the cylinder; the digital scale subtracts it from total weight (Ch. 11, p. 215).

Fuel and LP Gas

5 on exam · 24 practice questions

Key Concepts

Combustion chemistry and air requirements - Natural gas requires 10 ft³ of air per 1 ft³ of gas for complete combustion; about 15 ft³ of air per cubic foot of gas is supplied to give 50% excess air (Modern Refrigeration and Air Conditioning 22nd ed., Ch. 33, p. 758). - LP gas requires 24 ft³ of air to burn 1 ft³ of gas; about 35 ft³ provides 50% excess air (p. 758–761 text). - Lower-efficiency furnaces take in 20%–50% excess air; higher-efficiency furnaces use as little as 10% (p. 758).

Combustion analysis targets - Ultimate CO₂ is approximately 11.9% for natural gas and 13.9% for LP gas, but after excess-air dilution the flue-gas CO₂ should be closer to 7.6% (natural gas) and 8.9% (LP gas) (p. 759). - Flue-gas O₂ should be 6%–9%, ideally 7.5%, for both fuels, condensing or noncondensing (p. 759). - ANSI maximum CO in furnace flue gas is 400 ppm; many manufacturers treat more than 50 ppm as a problem (p. 759). - Low CO₂ + high O₂…

Combustion Air, Chimneys, Flues and Vents

5 on exam · 23 practice questions

New Jersey Master HVACR Contractor Exam — 5 questions (10%)

Key Concepts

Combustion air (IFGC Chapter 3) - Where all combustion air is provided by a mechanical air supply system, air shall be supplied from the outdoors at a rate not less than 0.35 cfm per 1,000 Btu/h of total input rating of all appliances in the space (IFGC 304.9, Page 3-6). - Each appliance served shall be interlocked with the mechanical air supply system to prevent main burner operation when the air supply system is not operating (IFGC 304.9.2). - Indoor combustion air, standard method: minimum required volume is 50 cubic feet per 1,000 Btu/h of appliance input rating (IFGC 304.5.1). - Combustion air intake openings on the building exterior shall have their lowest side not less than 12 inches vertically above adjoining finished ground level (IFGC 304.11, Item 8). - Louvers/grilles of unknown design: assume wood louvers 25-percent free area, metal louvers and grilles 75-percent free area; screens not smaller than 1/4-inch mesh (IFGC 304.10). - IMC 701.2: **Manual dampers shall not…

Ducts, Ventilation and Exhaust

5 on exam · 25 practice questions

Key Concepts

Airflow and leakage testing - An air handler flowmeter is placed in the air stream of an air handler to measure the total airflow of a central system; these are typically sized to fit over a large return grille or in the space normally occupied by the system's air filter (Modern Refrigeration and Air Conditioning, 22nd ed., Ch. 31, p. 701). - Duct leakage test: after all registers and grilles are sealed, the ducts are pressurized to +25 Pa WRT the conditioned space; the airflow needed to maintain that pressure is cfm25 (Ch. 31, p. 703). - Per the IECC, maximum duct leakage is 4 cfm per 100 ft² of conditioned space when ducts are pressurized to 25 Pa, and 3 cfm per 100 ft² if the ductwork is tested before the air handler is installed (Ch. 31, Section 31.1.5, p. 703). - Duct testing is not required when the air handler and ductwork are contained within the building envelope (Code Alert, p. 703). - cfm50 is the measured airflow through a…

Load Calculations

5 on exam · 26 practice questions

NJ Master HVACR Contractor Exam — 5 questions (10%)

Key Concepts

Design conditions - Manual J indoor design "bulls eye": 70°F db for heating (Section 3, Page 3-6) and 75°F db at 50% RH for cooling (Sections 3-6, 3-7). - HTD = indoor heating db − 99% outdoor value; CTD = 1% outdoor value − indoor cooling db (Section 6-3, Worksheet A). - Heating outdoor db values are the ASHRAE 99 percent values — outdoor temp is colder than design about 1% of cold-month hours, roughly 85 to 90 hours per year (Section 18-1). - Textbook ASHRAE ODT selection: 99.6% for residences and small, poorly insulated office buildings; 99% for well-constructed, well-insulated buildings with a standard number of windows; 97.5% for large buildings with considerable thermal capacity and small total window area (Ch. 32, p. 722). IDT generally 70°F or 72°F; unheated spaces are assumed halfway between IDT and ODT.

Final Practice Exam
50 questions · 130 min · timed simulation of the real exam
Never the same exam twice. Every attempt is drawn fresh from 247 questions, about 4 full exams' worth, and questions you haven't seen come first.

Required Books

Open-book exam
2021 Edition
International Mechanical Code 2021
Buy on Amazon
2021 Edition
International Fuel Gas Code 2021
Buy on Amazon
8th Edition
Manual J - Residential Load Calculation
Buy on Amazon
22nd Edition
Modern Refrigeration and Air Conditioning, 22nd Edition
Not allowed in the exam room
Buy on Amazon
4th Edition, 2020 (ANSI/SMACNA 006-2020)