Oklahoma Plumbing Journeyman and Natural Gas
Code edition notice: Oklahoma's PSI candidate bulletin (effective August 31, 2026) allows either the 2018 or the 2024 edition of the International Plumbing Code (IPC) and International Fuel Gas Code (IFGC) on this exam from October 8, 2026 through December 13, 2026. Starting December 14, 2026, only the 2024 editions are permitted.
This practice exam cites the 2018 editions, which remain valid on the real exam through December 13. We are updating to the 2024 editions before the changeover. If you test on or after December 14, study with and bring the 2024 books.
Practice at the real exam's pace
Every practice exam shows your time per question against the real exam's clock (2:07 here), and each topic lands in one of these:
What's on the exam
Questions per topic, out of 85Topics
General Plumbing Knowledge and Regulations
Oklahoma Plumbing Journeyman and Natural Gas — 10 questions (12%)
Key Concepts
Code scope and applicability (IPC 2018, Ch. 1) - IPC Section 101.2: the code applies to "the erection, installation, alteration, repairs, relocation, replacement, addition to, use or maintenance of plumbing systems." It also regulates nonflammable medical gas, inhalation anesthetic, vacuum piping, nonmedical oxygen systems, and sanitary and condensate vacuum collection systems. Fuel gas distribution piping and equipment, fuel-gas-fired water heaters and water heater venting systems are regulated by the International Fuel Gas Code. Appendix provisions "shall not apply unless specifically adopted." - Section 101.2 Exception: detached one- and two-family dwellings and multiple single-family dwellings (townhouses) not more than three stories high with separate means of egress, and their accessory structures, comply with the International Residential Code. - Section 102.1: where a general and a specific requirement conflict,…
Piping, Valves, and Control Valves
Key Concepts
Prohibited and restricted materials - Cast-iron pipe shall not be used (IFGC 403.4.1). Cast-iron flanges are permitted, but cast-iron bushings shall not be used, and cast-iron fittings shall not be used in systems containing flammable gas-air mixtures (403.10.5, Item 5). - PVC and CPVC plastic pipe, tubing and fittings shall not be used to supply fuel gas (403.6). - Aluminum-alloy pipe shall not be used in exterior locations or underground (403.4.4); the same restriction applies to aluminum-alloy tubing (403.5.4). - Copper and copper alloy pipe/tubing shall not be used if the gas contains more than an average of 0.3 grains of hydrogen sulfide per 100 standard cubic feet (0.7 mg per 100 liters) (403.4.3, 403.5.3).
Fixtures and Equipment
Key Concepts
Minimum facilities (IPC 2018, Section 403) - Fixture counts come from Table 403.1 based on actual use; occupant load is determined by the International Building Code (Section 403.1). - Nightclubs, bars, taverns and dance halls: water closets 1 per 40 male and 1 per 40 female; lavatories 1 per 75; drinking fountain 1 per 500; 1 service sink (Table 403.1). - Separate facilities for each sex are not required where the total occupant load, including employees and customers, is 15 or fewer (Section 403.2 Exception 2), or in business occupancies where the maximum occupant load is 25 or fewer (Section 403.2 Exception 4). - Travel to required public and employee toilet facilities in occupancies other than covered and open mall buildings shall not exceed 500 feet (152 m), and facilities shall be not more than one story…
Water Supply
Key Concepts
Pressure limits and pressure-reducing valves - Where static water pressure within a building exceeds 80 psi, an approved water pressure-reducing valve with strainer shall be installed to reduce the pressure to not greater than 80 psi static (UPC §604.8; also cited as IPC 2018 §604.8). Under UPC §604.8 the valve conforms to ASSE 1003 or CSA B356. - Where street water main pressures fluctuate, the building water distribution system shall be designed for the minimum pressure available (UPC §604.6). - Where street main pressure is insufficient, the supply shall be supplemented by an elevated water tank, a hydropneumatic pressure booster system, or a water pressure booster pump (IPC 2018 §606.5.1). - A low-pressure cutoff shall be installed on all booster pumps to prevent a vacuum or negative pressure when a positive pressure of 10 psi or less…
Drains and Sewers
Oklahoma Plumbing Journeyman and Natural Gas | 10 questions, 12% of exam
Key Concepts
Slope of horizontal drainage (IPC 2018, Table 704.1 / Section 704.1) - 2½ inches or less: minimum 1/4 inch per foot - 3 to 6 inches: minimum 1/8 inch per foot - 8 inches or larger: minimum 1/16 inch per foot - Piping upstream of a grease interceptor: not less than 1/4 inch per foot (2-percent slope), regardless of pipe size (Section 704.1)
Stack connections (Section 704.3). Horizontal branches shall connect to the bases of stacks at a point not less than 10 times the diameter of the drainage stack downstream from the stack.
Vents
Key Concepts
General / use limitations - The vent system must permit admission or emission of air so that the seal of any fixture trap is not subjected to a pressure differential of more than 1 inch of water column (249 Pa) — IPC 2018, 901.2. - The plumbing vent system shall not be utilized for purposes other than venting of the plumbing system — IPC 2018, 901.4.
Vent terminals (903) - Where a roof is used for assembly, promenade, observation deck, sunbathing deck or similar purposes, open vent pipes terminate not less than 7 feet above the roof — 903.1. - An open vent terminal shall not be located directly beneath any door, openable window or other air intake opening, and shall not be within 10 feet horizontally of such an opening **unless it is 3 feet or…
Traps, Interceptors, Indirect, and Special Waste
Key Concepts
Fixture traps (Section 1002.1). Each plumbing fixture shall be separately trapped by a liquid-seal trap. The vertical distance from the fixture outlet to the trap weir shall not exceed 24 inches (610 mm), and the horizontal distance shall not exceed 30 inches (762 mm), measured from the centerline of the fixture outlet to the centerline of the inlet of the trap. A fixture shall not be double trapped. Exceptions include fixtures with integral traps; a combination plumbing fixture on one trap where one compartment is not more than 6 inches deeper than the other and the waste outlets are not more than 30 inches apart; and (IPC 2018, Exception 3) a grease interceptor serving as the trap for a single fixture or a combination sink of not more than three compartments, where the vertical distance from fixture…
Isometric Analysis
Oklahoma Plumbing Journeyman and Natural Gas | 7 questions, 8% of exam
Key Concepts
- Offset terminology. The distance between the centerlines of two parallel pipes is the offset; "set" is a shortened version of the word offset. The offset is the c-c length when the parallel pipes are connected with 90° fittings. (Ch. 1 / Unit 17, Offset, Diagonal, Rise, and Run, p. 64)
- Diagonal / travel. If two parallel pipes are connected by fittings other than 90°, the center-to-center length of the connecting pipe is the diagonal, often referred to as travel. Diagonal construction is preferred to 90° fittings because there is less restriction to flow. (Unit 17, p. 64)
- Rise vs. run. Rise and run are the same distance; the name changes with orientation — parallel vertical pipes give a rise, parallel horizontal pipes…
Fuel Gas
Key Concepts
Venting heights and terminations - A Type B or L gas vent shall terminate not less than 5 feet in vertical height above the highest connected appliance draft hood or flue collar; a Type B-W vent not less than 12 feet above the bottom of the wall furnace (503.6.6). - Chimneys for residential-type or low-heat appliances shall extend not less than 3 feet above the highest point where they pass through a roof and not less than 2 feet higher than any portion of a building within 10 feet horizontally; chimneys for medium-heat appliances not less than 10 feet higher than any portion of any building within 25 feet. Chimneys shall also extend not less than 5 feet above the highest connected draft hood outlet or flue collar (503.5.4). - A mechanical draft venting system (excluding direct-vent…
Safety
Key Concepts
Fall protection trigger. Each employee on a walking/working surface with an unprotected side or edge 6 feet (1.8 m) or more above a lower level must be protected by guardrail systems, safety net systems, or personal fall arrest systems — §1926.501(b)(1). Subpart M does not apply when employees are making an inspection, investigation, or assessment of workplace conditions prior to the start of construction work or after all construction work is completed — §1926.500(a)(1).
Guardrail systems — §1926.502(b): - Top edge height of top rails: 42 inches (1.1 m) plus or minus 3 inches (8 cm) above the walking/working level — §1926.502(b)(1). - Midrails, screens, mesh, intermediate vertical members, solid panels and equivalent members must withstand, without failure, a force of at least 150 pounds (666 N) applied in any downward or outward direction at any point…