Idaho Limited Electrical Refrigeration, Heating & Air Conditioning Installer Practice Exam Guide
What's on the exam
Questions per topic, out of 45This practice exam follows the official content outline for the Idaho Limited Electrical Refrigeration, Heating & Air Conditioning Installer exam: 2017 National Electrical Code, NFPA – Introduction, 2017 National Electrical Code, NFPA – Chapter 1, 2017 National Electrical Code, NFPA – Chapter 2, 2017 National Electrical Code, NFPA – Chapter 3, 2017 National Electrical Code, NFPA – Chapter 4, 2017 National Electrical Code, NFPA – Chapter 7, 2017 National Electrical Code, NFPA Calculations.
- Free practice exam: 10 questions per attempt, retake as often as you like.
- Full practice exam: 45 questions on a 2 hours clock, a new draw from our bank every attempt.
2017 National Electrical Code, NFPA – Introduction 2 items
Our study plan for this topic: Purpose and scope of the NEC (practical safeguarding of persons and property); NEC scope: covered and not-covered installations (90.2); Code arrangement and chapter hierarchy (90.3); Authority having jurisdiction (AHJ): enforcement powers and special permission; Mandatory vs. permissive rules and explanatory material (shall/shall not vs. shall be permitted); Equipment examination, listing, and approval for safety (90.7); Units of measurement: SI and inch-pound dual system (90.9); Wiring planning for future expansion and circuit enclosure limitations (90.8).
2017 National Electrical Code, NFPA – Chapter 1 3 items
Our study plan for this topic: Key NEC definitions and terminology (Article 100); Equipment approval, listing, and labeling requirements; Electrical connections, splices, and conductor temperature limitations; Working space and clearance requirements around electrical equipment; Guarding of live parts and arc-flash hazard warning; Equipment marking and identification of disconnecting means; Enclosure type selection for environmental conditions; Wiring integrity, conductor materials, and approved wiring methods.
2017 National Electrical Code, NFPA – Chapter 2 10 items
Our study plan for this topic: Grounding and bonding requirements for services and separately derived systems; Grounding electrode system types, installation, and sizing; Equipment grounding conductor types, sizing, and identification; Bonding of piping systems, structural metal, and service equipment; GFCI and AFCI protection requirements for branch circuits; Branch-circuit load calculations and conductor ampacity requirements; Overcurrent protection devices, ratings, and location requirements; Feeder and service load calculation methods including demand factors.
2017 National Electrical Code, NFPA – Chapter 3 6 items
Our study plan for this topic: Conductor ampacity tables and temperature correction/adjustment factors (Article 310); Conductor types, insulation designations, and permitted uses by location (Article 310); Protection of cables and raceways against physical damage through framing members and structural elements (Article 300); Underground wiring installation requirements and minimum burial depths (Article 300); Wiring in ducts, plenums, and air-handling spaces (Article 300); Box and conduit body fill calculations and minimum sizing for outlet, device, pull, and junction boxes (Article 314); Installation requirements for flexible conduit types: FMC, LFMC, and LFNC — uses, securing, and grounding (Articles 348, 350, 356); Installation requirements for rigid and nonmetallic conduit systems: RMC, EMT, and PVC — supports, bends, and grounding (Articles 344, 358, 352).
2017 National Electrical Code, NFPA – Chapter 4 16 items
Our study plan for this topic: Motor branch-circuit conductor sizing and ampacity requirements (Article 430, Part II); Motor overload protection selection and settings (Article 430, Part III); Motor branch-circuit short-circuit and ground-fault protective device ratings (Article 430, Part IV); Motor disconnecting means types, ratings, and location requirements (Article 430, Part IX); Motor controller ratings, markings, and design requirements (Article 430, Parts VII–VIII); Air-conditioning and refrigerating equipment branch-circuit conductors, disconnecting means, and overload protection (Article 440); Fixed electric space-heating equipment branch circuits, overcurrent protection, and disconnecting means (Article 424); Appliance branch-circuit ratings, overcurrent protection, and disconnecting means (Article 422).
2017 National Electrical Code, NFPA – Chapter 7 7 items
Our study plan for this topic: Class 1, Class 2, and Class 3 circuit definitions and classifications; Power source requirements for Class 1, Class 2, and Class 3 circuits; Overcurrent protection for Class 1 circuits; Wiring methods for Class 1, Class 2, and Class 3 circuits; Separation requirements between Class 2/Class 3 and power circuits; Cable types and listing requirements for Class 2, Class 3, and PLTC cables; Installation of Class 2 and Class 3 cables in specific locations (plenums, risers, ducts); Circuits and equipment operating at less than 50 volts.
2017 National Electrical Code, NFPA Calculations 1 item
Our study plan for this topic: Branch-circuit conductor sizing for motor loads (125% rule, Article 430.22); Motor branch-circuit short-circuit and ground-fault protective device ratings (Table 430.52); Motor overload protection selection and trip current percentages (Article 430.32); Hermetic refrigerant motor-compressor branch-circuit conductor ampacity (Article 440.32); Branch-circuit short-circuit and ground-fault protection for hermetic refrigerant motor-compressors (Article 440.22); Feeder and service load calculations including motor loads (Articles 220.40, 220.50); Conductors supplying multiple motors or combined motor and other loads (Articles 430.24, 440.33); Full-load current values from NEC motor tables (Tables 430.247, 430.248, 430.249, 430.250).
Sample 1 — 2017 National Electrical Code, NFPA – Chapter 4
Question: A continuous-duty motor rated more than 1 hp is protected by a thermal protector integral with the motor. If the motor full-load current is 9 amperes or less, the ultimate trip current of the thermal protector shall not exceed what percentage of the motor full-load current?
- A. 140 percent
- B. 170 percent
- C. 125 percent
- D. 156 percent
Correct Answer: B
NEC 430.32(A)(2) limits the ultimate trip current of a thermally protected motor to 170 percent of full-load current where the full-load current is 9 amperes or less, 156 percent for 9.1 through 20 amperes, and 140 percent for currents greater than 20 amperes.
Reference: NEC 2017 Section 430.32(A)(2)
Sample 2 — 2017 National Electrical Code, NFPA – Chapter 2
Question: You install a packaged rooftop air-conditioning unit on a commercial building. A 125-volt, single-phase, 15- or 20-ampere receptacle outlet must be provided for servicing the equipment. The receptacle must be on the same level as the unit and located within what maximum distance of it?
- A. 50 ft
- B. 25 ft
- C. 75 ft
- D. 15 ft
Correct Answer: B
NEC 2017, Section 210.63 requires a 125-volt, single-phase, 15- or 20-ampere receptacle outlet at an accessible location for servicing heating, air-conditioning, and refrigeration equipment, located on the same level and within 7.5 m (25 ft) of the equipment. The same section also prohibits connecting that receptacle to the load side of the equipment disconnecting means.
Reference: NEC 2017 Section 210.63
Sample 3 — 2017 National Electrical Code, NFPA – Chapter 7
Question: The input leads of a transformer supplying a Class 2 circuit are permitted to be smaller than 14 AWG, but not smaller than 18 AWG, provided the insulation is suitable and the leads do not exceed what length?
- A. 450 mm (18 in.)
- B. 250 mm (10 in.)
- C. 150 mm (6 in.)
- D. 305 mm (12 in.)
Correct Answer: D
The exception to NEC 2017, 725.127 permits input leads of a transformer or other power source supplying Class 2 and Class 3 circuits to be smaller than 14 AWG but not smaller than 18 AWG, if they are not over 305 mm (12 in.) long and have insulation complying with 725.49(B).
Reference: NEC 2017 Section 725.127 Exception
- Your results break the score down by outline topic.
- The real exam's passing score: a minimum score of 70.
- Keep practicing until you pass consistently, not just once.
- Answer what you know first and bookmark the rest. Our practice exams let you bookmark and come back.
- Work your bookmarks on the second pass.
- Real exam pace: about 2 minutes 40 seconds per question.
- After each attempt, look up every miss in your book.
| Questions | 45 questions |
| Time limit | 2 hours |
| Passing score | a minimum score of 70 |
| Books in the exam room | Open book |
| Exam fee | $75 |
- Your score is shown on screen at the end of the exam and a score report is provided, with a diagnostic report of strengths and weaknesses if you fail.
- If you do not pass, you may retake the exam as many times as needed, paying an examination fee for each attempt.
Source: Examination Scheduling Procedures / Examination Guide (Idaho PSI Candidate Bulletin), Effective 7/9/2026. Check the bulletin before test day: fees and rules can change.