California C-10 Electrical Contractor Exam
California · PSI Services Contractor
California State Portion 115 questions
Key Distinctions
A motor branch circuit is the conductors and equipment between the motor branch-circuit short-circuit and ground-fault protective device and an individual motor, while a general branch circuit begins at the final overcurrent device protecting the circuit.
California Electrical Code 2025, Article 100 (Definition of Branch Circuit, Motor)A feeder is all circuit conductors between the service equipment, source of a separately derived system, or other power supply source and the final branch-circuit overcurrent device, not the conductors past that device (branch circuit) nor the utility-to-premises conductors (service).
California Electrical Code 2025, Article 100 (Definition of Feeder)A main is a supply circuit of the same wire size for its entire length, with no cutouts in series, to which other circuits connect through automatic cutouts at several points, while a feeder runs from the original source of energy to a distributing center with no other circuits connected between the two.
American Electricians' Handbook, 17th ed., Division 3, Secs. 11-18 (Circuit nomenclature)A monopole circuit is a PV subset with two output conductors, one positive and one negative, while a bipolar circuit is a dc circuit comprised of two monopole circuits of opposite polarity connected to a common reference point.
California Electrical Code 2025, Article 100 (Definition of Monopole Circuit)Compressed stranding presses only the outer layer of strands (diameter less than concentric but greater than compact), while compact stranding presses each layer of strands; concentric stranding is a straight central strand with helically laid layers and no pressing.
California Electrical Code 2025, Article 100 (Definitions of Stranding, Compressed; Stranding, Compact; Stranding, Concentric)Type UF conductors run 14 AWG copper or 12 AWG aluminum/copper-clad aluminum through 4/0 AWG (340.104), while 2 AWG is the upper limit for Types NM and NMC under 334.104.
California Electrical Code 2025, Section 340.104Three-wire control uses a momentary-contact pilot device plus a holding-circuit contact and provides undervoltage protection (motor stays off after voltage loss), while two-wire control uses a maintained-contact pilot device and provides only undervoltage release, permitting automatic restarting.
American Electricians' Handbook, 17th ed., Sec. 251, Electric Controller Terminology (Three-Wire Control; Two-Wire Control; Undervoltage Protection; Undervoltage Release)An outlet/branch-circuit AFCI used as the first outlet on NM-cable wiring limits the home run to 50 ft on 15-A and 70 ft on 20-A circuits, but the length limit does not apply if the home run is metal-enclosed (raceway, MC, AC) or if an AFCI breaker originates the circuit.
American Electricians' Handbook, 17th ed., Division 4, Sec. 77 (Arc-fault circuit interrupters)Low-voltage power circuit breakers, electromechanical protective relays and current transformers may be reconditioned, while GFE equipment, GFCIs, low-voltage fuseholders and nonrenewable fuses, molded-case circuit breakers, and low-voltage power circuit breaker electronic trip units shall not be.
California Electrical Code 2025, Section 240.2250.146(A) permits a receptacle yoke in direct metal-to-metal contact with a surface-mounted metal box but requires removal of at least one insulating washer when the receptacle has no contact yoke, while 250.146(B) covers contact devices/yokes listed as self-grounding for flush-type boxes.
California Electrical Code 2025, Section 250.146(A)For circuits over 250 volts to ground with no oversized, concentric, or eccentric knockouts, a shouldered fitting seated tightly against the box with one locknut inside is permitted, whereas the two-locknut method (inside and outside) applies to RMC and IMC.
California Electrical Code 2025, Section 250.97A wye–delta bank produces a 30-degree angular displacement between primary and secondary, while delta–delta and star–star banks have 0-degree displacement; banks with different angular displacements cannot be paralleled.
Ugly's Electrical References 2023, Three-Phase Standard Phase RotationFire pump supply conductors have a mandatory limit of 15 percent voltage drop at the controller terminals under locked-rotor/starting conditions, while the 3 percent feeder / 5 percent overall figures are nonmandatory recommendations for reasonable efficiency.
American Electricians' Handbook, 17th ed., Division 3, Sec. 35 (Allowable voltage drops)A panel is a preassembled installation unit of a small group of modules (often three or four) physically and electrically connected together, while a string is a series-connected set of modules.
Photovoltaic Systems, 3rd Edition, Chapter 4 (Modules and Arrays)Visual inspection of cord sets, caps, plugs, receptacles and cord- and plug-connected equipment is required before each day's use (except fixed receptacles/cord sets not exposed to damage), while continuity and terminal tests are required at intervals not exceeding 3 months (6 months for fixed items not exposed to damage).
Cal/OSHA Title 8, §2405.4(d)(3)Key Terms
Formulas to Know
E = I × R; I = E / R; R = E / I — e.g., 8 A × 15 Ω = 120 V; 240 V ÷ 48 Ω = 5 A; 12 V ÷ 0.5 A = 24 ΩP = E × I; I = P / E; P = I² × R — e.g., 120 V × 12.5 A = 1,500 W; 1,800 W ÷ 120 V = 15 A; (4 A)² × 25 Ω = 400 WP = √3 × V × I × cos θ; apparent power S = P ÷ PF (e.g., 200 kW ÷ 0.8 = 250 kVA). Raising PF at constant V and I raises real power; apparent power is unchanged.XL = 2πfL (f = frequency, L = inductance) — not 2πfCR = 1 / (1/r1 + 1/r2 + 1/r3); two-resistor shortcut R = (R1×R2)/(R1+R2); equal resistors R = R/n — e.g., 6, 12, 4 Ω parallel = 2 Ω; 12∥4 = 3 Ω; two 30 Ω = 15 ΩCombine parallel banks first, add series resistances for R_total, then I_total = E / R_total; branch voltage = I_total × R_parallel and branch current = that voltage ÷ branch resistance — e.g., 3 + (12∥4=3) = 6 Ω, 24/6 = 4 A, 12 V across pair, 12/4 = 3 A through R3Sum conductor allowances (each 12 AWG = 2.25 in.³) + one single allowance for internal cable clamps based on largest conductor + one single allowance for up to four EGCs + double allowance per yoke based on largest conductor connected — worked example: 4 insulated 12 AWG (9.00) + clamps (2.25) + EGCs (2.25) + receptacle yoke (4.50) = 18.00 in.³Enter overload tables at 58% of the across-the-line delta nameplate full-load current (elements carry winding/phase current) — worked example: 0.58 × 60 A = 34.8 A ≈ 35 AP = 100 − h − [10,000 ÷ (100 + m)], where m = markup based on cost and h = overhead as percent of gross sales — worked example: 10,000 ÷ 125 = 80, P = 100 − 20 − 80 = 0 percentCharge control required unless (maximum array charge current × 1 hour) is less than 3% of rated battery capacity in Ah (about C/33) — worked example: 3% of 400 Ah = 12 A, so control is required at 12 A or moreMark from end = stub height − take-up (take-up chart: ½" = 5 in, ¾" = 6 in, 1" = 8 in, 1¼" = 11 in) — e.g., 18 − 5 = 13 in; 12 − 6 = 6 in; 16 − 8 = 8 in; 16 − 11 = 5 inDistance between bends = multiplier × offset depth (22½° = 2.6, 30° = 2.0, 45° = 1.4, 60° = 1.2); shrink per inch of offset = 3/16 in at 22½°… applied values used: 1/4 in (30°), 3/8 in (45°), 1/2 in (60°); first mark = measured distance to obstruction + shrink — e.g., 30° over 4 in: 2.0×4 = 8 in apart, shrink 1/4×4 = 1 in, first mark at 30+1 = 31 inSide marks = 2.5 × obstruction height each side of the center mark (center bent 45°, sides 22½°); shrink = 3/16 in × obstruction height — e.g., 3 in pipe: 7½ in and 9/16 in shrink; 4 in: 10 in and 3/4 in; 5 in: 12½ in; 6 in: 15 inTotal = (regular hours × rate) + (overtime hours × 1.5 × rate) — e.g., 40×$30 + 8×$45 = $1,560; two weeks at 50 hr/wk per worker: 80×$25 + 20×$37.50 = $2,750, ×2 workers (200 hr ÷ 100 hr) = $5,500Quantity = required × (1 + waste %); apply volume discount to the whole order; free units = total ÷ 11 for buy-10-get-1-free, then tax the discounted base — e.g., 220 × $15 × 0.95 = $3,135; 50 × $120 = $6,000 + 7% tax = $6,420Total = base bid + change orders × (1 + markup) — e.g., $20,000 + $5,000 × 1.15 = $25,7501 hp = 746 W; kilo = 1,000 (2,400 W = 2.4 kW); milli = 1/1,000 (350 mA = 0.35 A); 1 kcmil = 1,000 circular mils