Exam Cheat Sheet · Quick Reference
ICC F34 Journeyman Gas Pipe Fitter Exam (2015 IFGC)
National · Pearson Vue
National State Portion 55 questions
Key Distinctions
The longest length method sizes every section of the system from the single table row for the length to the most remote outlet, while the branch length method sizes each branch from that branch's own meter-to-outlet length (mains on the longest run still use the longest-run row).
IFGC Section 402.4.1, Longest Length Method; Table 402.4(2), Schedule 40 Metallic Pipe (natural gas, 0.5 in. w.c. drop)Per 2015 IFGC Section 402.4, Equation 4-1 is used for systems operating at less than 1 1/2 psi and Equation 4-2 for systems at 1 1/2 psi and above (the 2 psi figure is only an inlet-pressure heading in certain capacity tables).
IFGC 2015 Section 402.4 (Equations 4-1 and 4-2)Under Section 304.6.1 the two-permanent-openings method requires 1 square inch per 4,000 Btu/h for each opening communicating directly with the outdoors or through vertical ducts, versus 1 square inch per 2,000 Btu/h where horizontal ducts are used.
IFGC 2015 Section 304.6.1The two-opening method sizes each opening by Btu/h input (Section 304.6.1), while the one-opening method (Section 304.6.2), with the opening commencing within 12 inches of the top of the enclosure, additionally requires appliance clearances of not less than 1 inch from sides and back and 6 inches from the front.
IFGC 2015 Section 304.6.1Same-story openings each need a minimum free area of 1 square inch per 1,000 Btu/h of total input but not less than 100 square inches, while openings in doors or floors joining different stories need a total minimum free area of 2 square inches per 1,000 Btu/h of total input.
IFGC 2015 Section 304.5.3.1Section 618.2 sizes outdoor and return air ducts/openings from the furnace OUTPUT rating capacity (2 square inches per 1,000 Btu/h output); using the input rating is a common error.
IFGC 2015 Section 618.2Section 503.7.7, Item 1 allows a ventilated thimble only 2 inches larger in diameter where there is a run of not less than 6 feet of metal pipe in the open between the draft hood outlet and the thimble; otherwise listed draft-hood appliances require 4 inches larger, with 6-inch and 12-inch figures applying to unlisted draft-hood appliances and to residential/low-heat appliances respectively.
IFGC 2015 Section 503.7.7Per Section 503.6.4, the first case may terminate above a sloped roof in accordance with Figure 503.6.4, while the second must terminate not less than 2 feet above the roof penetration and 2 feet above any portion of a building within 10 feet horizontally.
IFGC 2015 Section 503.6.4Under the Section 202 'Appliance Type' definitions, flue-entrance combustion products of a medium-heat appliance exceed 1,000°F but are not greater than 2,000°F, whereas at or below 1,000°F the appliance is a low-heat (residential) appliance.
IFGC 2015 Section 202 (definition of 'Appliance Type')Section 406.4.2 sets the general duration at not less than 1/2 hour for each 500 cubic feet of pipe volume or fraction thereof, but for a system of less than 10 cubic feet or a system in a single-family dwelling the duration shall be not less than 10 minutes.
IFGC 2015 Sections 406.4.1 and 406.4.2Section 101.2 Exception sends detached one- and two-family dwellings and multiple single-family dwellings (townhouses) not more than three stories high with separate means of egress, plus their accessory structures, to the International Residential Code instead of the fuel gas code.
IFGC 2015 Section 101.2Section 101.2.4, Item 3 excludes raw material/feedstock applications 'except for piping to special atmosphere generators,' so that generator piping remains regulated, while atomic energy plant fuel gas piping, railroad switch heating LP-gas systems, and temporary LP-gas piping not becoming part of the permanent system are outside the scope.
IFGC 2015 Section 101.2.4Key Terms
Formulas to Know
cfh = Btuh ÷ 1,000; Btuh capacity = table cfh × 1,000 (e.g., 40,000 Btuh = 40 cfh; 247 cfh = 247,000 Btuh; 44 cfh = 44,000 Btuh)Use the measured length; where the table has no matching row, use the next longer row (15 ft → 20-ft row; 45 ft → 50-ft row; 75 ft → 80-ft row; 95 ft → 100-ft row)Find the length from the meter to the most remote outlet, take that row (or next longer), and size every section in that one row for the load it carries; pick the smallest size whose capacity meets the load (e.g., 190 cfh in the 50-ft row: 3/4 in = 151 cfh too small, 1 in = 284 cfh)Each branch is sized on its own meter-to-outlet length (main run to tee + branch run; e.g., 15 + 8 = 23 ft → 30-ft row; 38 ft → 40-ft row; 50 ft → 50-ft row), while main sections are sized on the longest run lengthSpare cfh = table capacity of installed size at that length − appliance demand in cfh (e.g., 137 − 80 = 57 cfh; 44 − 40 = 4 cfh; 322 − 150 = 172 cfh)Test pressure = 1 1/2 × proposed maximum working pressure, but not less than 3 psig (2 psig × 1.5 = 3 psig)Highest end of scale not greater than 5 × test pressure (5 × 3 psig = 15 psig maximum)Not less than 1/2 hour for each 500 cubic feet of pipe volume or fraction thereof (1,200 ÷ 500 = 2.4 → 3 increments × 1/2 hr = 1 1/2 hours); for a system under 10 cubic feet or in a single-family dwelling, not less than 10 minutesVolume = total appliance input ÷ 1,000 × 50 cubic feet (120,000 ÷ 1,000 × 50 = 6,000 cubic feet)Not less than 2 square inches of unobstructed area per 1,000 Btu/h of furnace OUTPUT rating capacity (120,000 ÷ 1,000 × 2 = 240 square inches), unless manufacturer's instructions state larger