Idaho State Portion 40 questions
Key Distinctions
Festoon lighting is a string of outdoor lights suspended between two points, while outline lighting is an arrangement of light sources used to outline or call attention to features such as the shape of a building.
NEC 2017 Article 100 (Definitions: Festoon Lighting; Outline Lighting)The main bonding jumper is the connection between the grounded circuit conductor and the equipment grounding conductor at the service; the system bonding jumper serves a similar function at a separately derived system.
NEC 2017 Article 100 (Definition: Bonding Jumper, Main)An insulated conductor is encased within material of composition and thickness recognized by the Code as electrical insulation, while a covered conductor is encased in material not recognized as electrical insulation.
NEC 2017 Article 100 (Conductor, Insulated)The first group is marked by a printed tag attached to the coil, reel, or carton per 310.120(B)(3), while the second group is durably surface marked under 310.120(B)(1).
NEC 2017 Section 310.120(B)(3)240.4(B) permits the next higher standard rating above conductor ampacity only where that selected rating does not exceed 800 amperes; where the overcurrent device is rated over 800 amperes, 240.4(C) requires the conductor ampacity to be equal to or greater than the device rating.
NEC 2017 Section 240.4(B)Per 240.10, supplementary overcurrent protection shall not be used as a substitute for required branch-circuit overcurrent devices or in place of required branch-circuit protection.
NEC 2017 Section 240.10Per 240.4(F), 2-wire single-phase and delta-delta 3-wire secondary conductors are permitted to be protected by the primary-side device, but single-phase (other than 2-wire) and multiphase (other than delta-delta, 3-wire) secondary conductors shall not be considered protected by the primary device.
NEC 2017 Section 240.4(F)Equipment 1000 volts or less installed above a lay-in ceiling requires an opening not smaller than 22 in. × 22 in., whereas the 22 in. × 30 in. dimension applies to a crawl space access opening.
NEC 2017 Section 110.26(A)(4)(a)Chapters 1 through 4 apply generally to all electrical installations; Chapters 5, 6 and 7 cover special occupancies, special equipment or other special conditions and may supplement or modify Chapters 1 through 7, and Chapter 8 (communications systems) is independent except where specifically referenced.
NEC 2017 Section 90.3Per 90.5(C), explanatory material such as informational notes is included for informational purposes only and is not enforceable as a requirement of the Code.
NEC 2017 Section 90.5(C)Table 240.6(A) lists standard device ratings such as 45, 70 and 110 amperes (85 amperes is not listed), while 210.18 recognizes only 15, 20, 30, 40 and 50 amperes as ratings for other than individual branch circuits — so 25- and 60-ampere standard devices are not recognized branch-circuit ratings.
NEC 2017 Table 240.6(A)The unit load for a retail occupancy is 1.9 VA per square foot in NEC 2020 Table 220.12 / 2023 Table 220.42(A) / 2026 Table 120.42(A) (3 VA per square foot was the NEC 2017 unit load for stores), while Table 220.12 specifies 3 volt-amperes per square foot for dwelling units.
NEC 2020 Table 220.12 (2020), Table 220.42(A) (2023), Table 120.42(A) (2026); 220.14(I) (120.14(I) in 2026); NEC 2026 Table 120.42(A); NEC 2023 Table 220.42(A) and 220.14(I)Per 600.3(B), outline lighting is not required to be listed as a system where it consists of listed luminaires wired in accordance with Chapter 3 wiring methods.
NEC 2017 Section 600.3(B)Key Terms
Formulas to Know
(continuous load × 125%) + non-continuous load; worked example: (100 A × 125%) + 30 A = 155 A(area sq ft × 1.9 VA/sq ft) + (number of receptacle outlets × 180 VA); worked example: 3,500 × 1.9 = 6,650 VA, 20 × 180 = 3,600 VA, total 10,250 VA (1.9 VA/sq ft per NEC 2020 Table 220.12 / 2023 Table 220.42(A) / 2026 Table 120.42(A))(area sq ft × 3 VA/sq ft) + (1,500 VA × number of small-appliance circuits) + (1,500 VA × number of laundry circuits); worked examples: 2,000 sq ft, 2 small-appliance, 1 laundry = 6,000 + 3,000 + 1,500 = 10,500 VA; 1,800 sq ft, 3 small-appliance, 2 laundry = 5,400 + 4,500 + 3,000 = 12,900 VANot less than 180 VA for each single or each multiple receptacle on one yoke; a single piece of equipment consisting of a multiple receptacle of four or more receptacles is calculated at not less than 90 VA per receptacleAt least one 125-volt, single-phase, 15- or 20-ampere receptacle within 450 mm (18 in.) of the top of the show window for each 3.7 m (12 linear ft) or major fraction thereof; worked example: 44 ft = three full 12-ft sections (36 ft) + 8 ft (a major fraction) = 4 receptacle outletsUse the 31% column of Chapter 9, Table 1; sum conductor areas and pick the smallest trade size whose 31% area is at least that sum. Examples: 2 × 0.0211 (10 AWG THHN) = 0.042 sq in → ½ in. EMT (0.094 sq in); 2 × 0.0507 (6 AWG THHN) = 0.101 sq in → ¾ in. EMT (0.165 sq in)Sum of (quantity × Table 5 area per conductor), including the equipment grounding conductor at its actual area (Chapter 9 Note 3); worked example: 7 × 0.0211 + 3 × 0.0133 + 1 × 0.0133 = 0.201 sq inInsulated conductors (1 each) + all EGCs counted as 1 + clamps + stud + device yoke (2); conductors wholly inside the box (pigtails) are not counted. Worked example: 4 + 1 + 0 + 0 + 2 = 7 allowancesAdd the parallel conductor areas, then size from Table 250.102(C)(1); worked example: 2 × 350 kcmil = 700 kcmil (over 600 through 1,100 kcmil) → 2/0 AWG copperNot more than the equivalent of four quarter bends (360 degrees total) between pull points such as conduit bodies and boxes