South Carolina Residential Electrical
Practice at the real exam's pace
Every practice exam shows your time per question against the real exam's clock (3:00 here), and each topic lands in one of these:
What's on the exam
Questions per topic, out of 60Topics
General Electrical Knowledge
13 questions · 22% of the exam
Key Concepts
Series circuits (Ugly's, Series Circuits, pp. 3–4) - Rule 1: Total current equals the current in any other part of the circuit: IT = I₁ = I₂ = I₃. - Rule 2: Total voltage is the sum of the voltages across all parts: ET = E₁ + E₂ + E₃. - Rule 3: Total resistance is the sum of all resistances: RT = R₁ + R₂ + R₃.
Parallel circuits (Ugly's, Parallel Circuits, pp. 5–7) - Total current is the sum of the branch currents: IT = I₁ + I₂ + I₃. - Voltage across any branch equals the voltage across every other branch and the total: ET = E₁ = E₂ = E₃. - Total resistance is always less than the resistance of any branch. Larger resistance draws smaller current, in either series or parallel.
Services, Feeders, and Branch Circuits
Key Concepts
Services - Service disconnecting means for a one-family dwelling: not less than 100 amperes, 3-wire (NEC 2023, 230.79(C)). - No more than six service disconnecting means grouped in any one location for each service (NEC 2023, 230.71(A)/(B)). - Service-entrance conductors supplying continuous and noncontinuous loads: ampacity not less than the noncontinuous load plus 125 percent of the continuous load (NEC 2023, 230.42(A)(1)). - 3-wire, single-phase dwelling service or main power feeder: conductor ampacity permitted to be 83 percent of the service rating (NEC 2023, 310.12 / 310.15(B)(7)). IRC 2024, E3603.1.2 states the same 83 percent for a feeder rated 100 through 400 amperes supplying the entire load of a one-family dwelling. - Service-entrance cables supported within 12 in. of every service head, gooseneck, or connection to a raceway or enclosure, and at intervals not exceeding 30 in. (NEC 2023, 230.51(A)). - Where it is impracticable to locate the service head above the…
Overcurrent Protection
Topic: Overcurrent Protection
Key Concepts
Protection of conductors (general). Conductors, other than flexible cords, flexible cables, and fixture wires, shall be protected against overcurrent in accordance with their ampacities specified in 310.14, unless otherwise permitted or required in 240.4(A) through (H). [NEC 2023, 240.4]
Small conductors — 240.4(D). Unless specifically permitted in 240.4(E) or (G), the overcurrent protection shall not exceed the values in 240.4(D)(1) through (D)(8) after any correction factors for ambient temperature and number of conductors have been applied. For 14 AWG copper the maximum is 15 amperes [240.4(D)(4)].
Devices rated 800 A or less — 240.4(B). The next higher standard overcurrent device rating above the conductor ampacity is permitted where: the conductors are not part of a branch circuit supplying more than one receptacle for cord-and-plug-connected portable loads; the conductor ampacity does not correspond to a standard fuse or breaker rating; and the next higher standard rating does not exceed 800…
Grounding and Bonding
South Carolina Residential Electrical
Key Concepts
Performance requirements (NEC 2023, 250.4) - Grounded systems shall be connected to earth in a manner that limits voltage imposed by lightning, line surges, or unintentional contact with higher-voltage lines and that stabilizes the voltage to earth during normal operation — 250.4(A)(1). - Normally non-current-carrying conductive materials enclosing conductors or equipment shall be connected to earth so as to limit the voltage to ground on those materials — 250.4(A)(2) — and shall be connected together and to the supply source to establish an effective ground-fault current path — 250.4(A)(3). - The effective ground-fault current path must be a low-impedance circuit facilitating operation of the overcurrent device or ground detector for high-impedance grounded systems. The earth shall not be considered an effective ground-fault current path — 250.4(A)(5). - On ungrounded systems, the low-impedance path facilitates operation of overcurrent devices should a second ground fault from a different phase occur…
Conductors and Cables
Key Concepts
Selecting a conductor - Minimum size for copper conductors rated 0–2000 volts is 14 AWG (NEC 310.3(A); also IRC E3406.3). - Conductors 8 AWG and larger installed in raceways shall be stranded, unless specifically permitted elsewhere to be solid (NEC 310.3(C); IRC E3406.4). - Conductors may be connected in parallel only in sizes 1/0 AWG and larger (NEC 310.10(G)(1)). - Insulation ratings, Table 310.4(1): THHN 90°C, dry and damp only; THW 75°C, dry and wet; RHW 75°C, dry and wet; TW 60°C, dry and wet; RHH 90°C, dry and damp; SIS and TBS are switchboard/switchgear wiring only. - Wet-location types per NEC 310.10(C) include MTW, RHW, RHW-2, TW, THW, THW-2, THHW, THWN, THWN-2, XHHW, XHHW-2, and ZW. RHH and THHN are not on that list. - No conductor shall be used so that its operating temperature exceeds that designated for the type of insulated conductor involved (NEC 310.14(A)(3)). - Corrected and adjusted…
Raceways and Boxes
(4 questions, 7% of the exam)
Key Concepts
Bends. The total degrees of bends in a run shall not exceed 360 degrees between pull points (four quarter bends). This same rule appears in RMC 344.24(B), IMC 342.24(B), PVC 352.24(B), FMC 348.24(B), LFMC 350.24(B) and EMT 358.24(B).
Trade sizes. RMC: minimum trade size ½ [344.20(A), exception for motor leads per 430.245(B)]; maximum trade size 6 [344.20(B)]. IMC: minimum ½ [342.20(A)]; maximum 6 [342.20(B)]. EMT: minimum ½, maximum 6 [358.20]. PVC: minimum ½, maximum 6 [352.20]. FMC: minimum ½ [348.20(A), with listed 3/8 exceptions]; maximum 4 [348.20(B)]. LFMC: minimum ½ [350.20(A)]; maximum trade size 4 [350.20(B)]. FMT: minimum ½, maximum ¾ [360.20].
Lighting
(4 questions, 7% of the exam)
Key Concepts
Clothes closets (NEC 410.16) - Permitted types [410.16(B)]: surface-mounted or recessed incandescent or LED luminaires with completely enclosed light sources; surface-mounted or recessed fluorescent luminaires; surface-mounted fluorescent or LED luminaires identified as suitable for installation within the clothes closet storage space. - Not permitted [410.16(C)]: incandescent luminaires with open or partially enclosed lamps, and pendant luminaires or lampholders. - Storage space [410.16(A); IRC E4003.12]: bounded by side and back walls, from floor vertically to 6 ft (1.8 m) or the highest clothes-hanging rod, 24 in. (600 mm) horizontally from sides and back; continuing to the ceiling at 12 in. (300 mm) or the shelf width, whichever is greater. Where both sides of a rod are accessible, the space includes 12 in. on either side of the rod. - Clearances to the nearest point of storage space [410.16(D)]: see table below. Exception: surface-mounted fluorescent or LED luminaires…
Specialty – pool/spa, garages, generators, wheelchair lifts
Key Concepts
Generators - Conductors from the generator output terminals to the first distribution device(s) containing overcurrent protection shall have an ampacity not less than 115 percent of the nameplate current rating of the generator. Exception: where the design and operation of the generator prevent overloading, not less than 100 percent is permitted (NEC 2023, 445.13(A)). - Stationary generators shall be listed; one-of-a-kind or custom units may be field labeled (445.6). Each generator needs an accessible nameplate with manufacturer, frequency, phases, kW or kVA rating, power factor, normal volts and amperes, and rated ambient temperature, plus marking indicating whether the neutral is bonded to the frame (445.11). - Generators other than cord-and-plug-connected portable units require one or more disconnecting means that simultaneously open all ungrounded conductors and are lockable open per 110.25 (445.18(A)). - One- and two-family dwellings: for other than cord-and-plug-connected portable generators, an emergency shutdown device shall be located **outside the dwelling…
Safety
South Carolina Residential Electrical · Safety
Key Concepts
Fall protection - Top edge height of top rails, or equivalent guardrail system members, shall be 42 inches (1.1 m) plus or minus 3 inches (8 cm) above the walking/working level — §1926.502(b)(1). - Fall protection training must be certified in writing; the record shall contain the name or other identity of the employee trained, the date(s) of the training, and the signature of the person who conducted the training or the signature of the employer — §1926.503(b)(1). - Subpart M does not apply when employees are making an inspection, investigation, or assessment of workplace conditions prior to the actual start of construction work or after all construction work has been completed — §1926.500(a)(1). - Unprotected sides and edges of stairway landings shall be provided with guardrail systems (criteria in subpart M) — §1926.1052(c)(12).