South Carolina Residential Plumbing
Practice at the real exam's pace
Every practice exam shows your time per question against the real exam's clock (2:46 here), and each topic lands in one of these:
What's on the exam
Questions per topic, out of 65Topics
General Plumbing Knowledge and Regulations
Key Concepts
Testing systems (IRC P2503) - Building sewer: insert a test plug at the connection with the public sewer, fill and pressurize to not less than a 10-foot head of water; pressure shall not decrease for not less than 15 minutes (IRC P2503.4; IRC 2018 p. 617). - DWV rough-in water test: fill each section to not less than 10 feet above the highest fitting connection, hold 15 minutes, prove leak free by visual inspection. Air test: 5 psi gauge or 10 inches of mercury column for not less than 15 minutes without introducing additional air (IRC P2503.5.1). - Shower liner test: fill floor and receptor with potable water to a depth of not less than 2 inches measured at the threshold, retain not less than 15 minutes, no evidence of leakage (IRC P2503.6). - Water-supply system: test at not less than the working pressure of the system, or for piping systems other than plastic, an air test of not less than 50 psi (345 kPa), held not less than 15 minutes (IRC…
Piping, Valves, and Controls
South Carolina Residential Plumbing | 6 questions (9% of exam)
Key Concepts
Protection and penetrations - Any pipe passing through a foundation wall shall be provided with a relieving arch, or a pipe sleeve shall be built into the wall; the sleeve shall be two pipe sizes greater than the pipe passing through (IRC P2603.4; IPC 305.3). - Where plastic sheathing prevents metallic piping from direct contact with steel framing, concrete, masonry or corrosive soil, the sheathing shall be not less than 0.008 inch (8 mil) and shall be plastic (IRC P2603.3; IPC 305.1). Cast iron, ductile iron and galvanized steel are excepted from the contact prohibition (IPC 305.1). - Exterior water supply piping shall be installed not less than 6 inches below the frost line and not less than 12 inches below grade (IPC 305.4).
Fixtures and Equipment
Key Concepts
Minimum fixtures for dwellings. Per IPC Table 403.1, "One- and two-family dwellings and lodging houses with five or fewer guestrooms" require 1 water closet per dwelling unit, 1 lavatory per dwelling unit, 1 bathtub/shower per dwelling unit, 1 kitchen sink per dwelling unit, and 1 automatic clothes washer connection per dwelling unit (IPC 2021, Page 4-3).
Fixture clearances. Per IRC P2705.1, Item 5: a water closet, lavatory or bidet shall not be set closer than 15 inches from its center to any side wall, partition or vanity, nor closer than 30 inches center-to-center between adjacent fixtures. There shall be a clearance of not less than 21 inches in front of a water closet, lavatory or bidet to any wall, fixture or door (IRC 2024, P2705.1).
Water Supply
Key Concepts
Materials and certification - Water service pipes, water distribution pipes and the connecting pipes, fittings, control valves, faucets and appurtenances used to dispense water intended for human ingestion shall be evaluated and listed as conforming to NSF 61 (IRC P2609.5). - Plastic pipe, fittings and components shall be third-party certified as conforming to NSF 14 (IRC P2609.3; IPC 303.3). - Lead content in pipe and fittings used in the water supply system shall be not greater than 8 percent (IRC P2906.2). Pipe and fittings supplying water for drinking or cooking must have a weighted average of 0.25-percent lead or less (IRC P2906.2.1). Solders and fluxes in potable water-supply systems: not greater than 0.2 percent lead (IRC P2906.15). - Water service pipe/tubing installed underground and outside the structure: working pressure rating not less than 160 psi at 73°F (IRC P2906.4 / IPC 605.3). Hot water distribution pipe and tubing: pressure rating not less than 100 psi at 180°F (IPC 605.4). - Water service pipe shall be not less than ¾ inch diameter (IPC…
Drain, Waste and Vent and Sewers
Key Concepts
Slope and fall. Horizontal drainage piping 2½ inches and less: slope not less than ¼ inch per foot (2-percent slope) — IRC P3005.3; IPC Table 704.1. Pipe 3 inches or more (IRC P3005.3): not less than ⅛ inch per foot (1-percent). Per IPC Table 704.1, 3 to 6 inches = ⅛ inch per foot and 8 inches or larger = 1/16 inch per foot. Drainage fittings shall be designed to maintain ¼ unit vertical in 12 units horizontal (2-percent slope) grade — P3002.3.1.
Cleanouts. Intervals of not more than 100 feet on horizontal drainage pipes and building drains (P3005.2.1) and on building sewers smaller than 8 inches (P3005.2.2); sewers 8 inches and larger need a manhole not more than 200 feet from the building drain/sewer junction (P3005.2.2). A cleanout serves the building drain–sewer junction at the junction or within 10 feet developed length upstream (P3005.2.3). A change of horizontal direction greater than 45 degrees requires a cleanout; where more than one such change occurs within 40 feet of developed length, the first…
Isometric Analysis
Obtaining information from isometric drawings
Key Concepts
- Isometric drawings are the standard way venting is illustrated. Appendix N of the IRC illustrates a variety of venting methods using isometric drawings (IRC 2018, Appendix N, Page 893).
- Pipe sizes printed on the Appendix N figures:
- Water closet drain — 3 inches (Figure N1, Page 893; Figure N3, Page 895)
- Lavatory drain — 1¼ inches, consistently, in Figures N1 through N5 (Pages 893–897)
- Tub drain — 1½ inches (Figure N2, Page 894; Figures N1(C) and N3, Page 895)
- Shared vertical wet-vent portion, double-bath arrangement — 2 inches (Figure N2, Page 894)
- Clothes washer standpipe drain, single stack two-story system — 2 inches (Figure N5, Page 897)
- Kitchen group connection, waste stack venting — 2-1/2 inches (Figure N6, Page 898)
- Which figure shows what: N1 single-bath wet vent; N2 double-bath wet vent; N3 horizontal wet venting (wet-vented portion runs horizontally along the branch drain); N4(A) vertical wet venting (wet-vented section runs vertically through the stack, with a shower…
Safety
Key Concepts
First aid and medical services (Subpart D, §1926.50) - The employer must insure availability of medical personnel for advice and consultation, and make provisions for prompt medical attention before the project starts (§1926.50(a), (b)). - Where no infirmary, clinic, hospital, or physician is reasonably accessible, a person holding a valid first-aid certificate from the U.S. Bureau of Mines, the American Red Cross, or equivalent verifiable training must be available at the worksite (§1926.50(c)). - First aid supplies must be easily accessible; kit contents go in a weatherproof container with individual sealed packages for each item type, and must be checked before being sent out on each job and at least weekly on each job to ensure expended items are replaced (§1926.50(d)(1), (d)(2)). - In areas where 911 emergency dispatch services are not available, telephone numbers of physicians, hospitals, or ambulances must be conspicuously posted (§1926.50(f)(1)).
Specialty Applications
South Carolina Residential Plumbing — 6 questions (9% of exam)
Key Concepts
Backflow prevention
- Reduced pressure principle, double check, pressure vacuum breaker, reduced pressure detector fire protection, double check detector fire protection, spill-resistant vacuum breaker backflow preventer assemblies, and hose connection backflow preventers shall be tested at the time of installation, immediately after repairs or relocation, and at least annually (IPC Section 312.10.2; IPC 2021, Page 3-5).
- Critical level of an atmospheric-type vacuum breaker: set not less than 6 inches (152 mm) above the highest elevation of downstream piping and the flood level rim of the fixture or device (IRC 2024, Section P2902.3.2).
- Critical level of a pressure vacuum breaker and spill-resistant vacuum breaker assembly: set not less than 12 inches (304 mm) above the highest elevation of downstream piping and the flood level rim (IRC 2024, Section P2902.3.4).
- Backflow preventers shall not be located in areas subject to freezing except where removable by unions, or protected by heat, insulation or both (IRC P2902.6.2).
Water heaters and storage tanks