EN ES
Study Course

West Virginia Electrical Contractor

75 questions 180 minutes 70% to pass 10 topics 2:24 per question Open book
Try 10 free questions Free Cheat Sheet Official Bulletin

Practice at the real exam's pace

Every practice exam shows your time per question against the real exam's clock (2:24 here), and each topic lands in one of these:

Ready Find it faster Study it Needs both Rushing: slow down

What's on the exam

Questions per topic, out of 75
Motors & Controls5
Equipment for General Use6
Special Occupancies2
Special Equipment4
Special Conditions4
Wiring Methods & Materials20
Communication Systems3
General Electrical Knowledge12
Plan Reading2
Wiring & Protection17

Topics

Open a topic to read its key concepts

Motors & Controls

5 on exam · 39 practice questions

Key Concepts

Controller marking (NEC 2023, 430.8). A motor controller is marked with the manufacturer's name or identification, voltage, current or horsepower rating, short-circuit current rating, and other data needed to indicate suitable applications. Combination motor controllers employing adjustable instantaneous trip circuit breakers "shall be clearly marked to indicate the ampere settings of the adjustable trip element."

Terminals (430.9). Controllers and control circuit device terminals are connected with copper unless identified for a different conductor (430.9(B)); control circuit devices with screw-type pressure terminals used with 14 AWG or smaller copper must be torqued to a minimum of 0.8 N·m (7 lb-in.) unless identified for a different torque value (430.9(C)).

Equipment for General Use

6 on exam · 42 practice questions

Key Concepts

Luminaires — location and clearance - Luminaires in damp locations must be marked suitable for wet locations or suitable for damp locations [410.10(A)]. - No cord-connected luminaires, chain/cable/cord-suspended luminaires, lighting track, pendants, or ceiling-suspended paddle fans with light kits within 900 mm (3 ft) horizontally and 2.5 m (8 ft) vertically of the bathtub rim or shower stall threshold [410.10(D)]. - Clothes closets: permitted types are surface-mounted or recessed incandescent/LED with completely enclosed light sources, surface-mounted or recessed fluorescent, and surface-mounted fluorescent or LED identified for use in the storage space [410.16(B)]. Incandescent with open or partially enclosed lamps, and pendant luminaires or lampholders, are not permitted [410.16(C)]. Minimum clearance to storage space: 300 mm (12 in.) for surface-mounted incandescent/LED with completely enclosed source; 150 mm (6 in.) for surface-mounted fluorescent and recessed luminaires [410.16(D)]. - A…

Special Occupancies

2 on exam · 10 practice questions

Key Concepts

Scope of the division vs. zone articles - Article 500 does not cover Zone 0, Zone 1, or Zone 2 locations, nor Zone 20, Zone 21, or Zone 22 locations — NEC 2023, 500.1(B). - Zone 0, 1, and 2 (flammable gases, vapors, or liquids) are covered by Article 505 — 505.1(A). Zone 20, 21, and 22 (combustible dusts, combustible or ignitible fibers/flyings) are covered by Article 506 — 506.1(A). Each of those articles excludes Class I/II/III Division 1 and 2 locations from its own scope — 505.1(B), 506.1(B). - Article 501 covers Class I, Division 1 and 2 locations — 501.1. Article 502 covers Class II, Division 1 and 2 — 502.1.

Special Equipment

4 on exam · 22 practice questions

Key Concepts

Electric signs and outline lighting (Art. 600) - Each commercial building and each commercial occupancy accessible to pedestrians must have at least one sign/outline lighting outlet in an accessible location at each entrance to each tenant space, supplied by a branch circuit rated at least 20 A that supplies no other load — NEC 600.5(A). - Branch-circuit ratings: neon tubing installations shall not be rated in excess of 30 A [600.5(C)(1)]; all other signs and outline lighting not to exceed 20 A [600.5(C)(2)]. All sign branch circuits are continuous loads [600.5(C)]. - Enclosures: sheet steel not less than 0.41 mm (0.016 in.) thick; sheet copper or aluminum not less than 0.51 mm (0.020 in.) — 600.8(C). - Bonding: listed FMC or listed LFMC enclosing neon secondary conductors is permitted as the bonding means where **total cumulative length…

Special Conditions

4 on exam · 20 practice questions

Key Concepts

Cables for power-limited circuits (Article 722) - Cables installed in buildings shall be listed (722.135(A)) and marked per 722.179(B): the AWG size or circular mil area repeated at intervals not exceeding 610 mm (24 in.); all other markings repeated at intervals not exceeding 1.0 m (40 in.). - Class 3 single conductors used as other wiring within buildings shall be listed Type CL3 and not smaller than 18 AWG (722.179(A)(8)). - LP cables are marked with the suffix "-LP (XXA)," where XXA designates the current limit in amperes per conductor the cable can carry without exceeding its temperature rating (722.179(A)(9)); example: "CL2-LP (0.6A) 75°C 23 AWG 4-pair." - Class 2 cables: voltage rating not less than 150 volts; Class 3: not less than 300 volts; both not less than 60°C (722.179(A)(14)). - Nonmetallic cable ties and accessories…

Wiring Methods & Materials

20 on exam · 129 practice questions

West Virginia Electrical Contractor | 20 questions (27% of exam)

Key Concepts

Conductors (Article 310) - Minimum size up to 2000 V: 14 AWG copper, 12 AWG aluminum or copper-clad aluminum [310.3(A)]. For copper-clad aluminum, copper must form a minimum 10 percent of the cross-sectional area of a solid conductor or each strand [310.3(B)]. - Parallel conductors: permitted only in sizes 1/0 AWG and larger [310.10(G)(1)], and each must be the same length, same material, same circular mil area, same insulation type, and terminated in the same manner [310.10(G)(2)]. Same manufacturer/production lot is not required. - Dwelling services/feeders 100–400 A, single-phase: ampacity not less than 83 percent of the rating [310.12(A), (B)]; Table 310.12(A) applies if no adjustment or correction factors are needed. - Final ampacity after correction/adjustment may not exceed the termination temperature rating [310.15(A), 110.14(C)]. - Bare…

Communication Systems

3 on exam · 15 practice questions

West Virginia Electrical Contractor — 3 questions (4% of exam)

Key Concepts

Grounding, bonding, and interruption

  • Masts and metal structures supporting antennas shall be grounded or bonded in accordance with 810.21, unless the antenna and its related supporting mast or structure are within a zone of protection defined by a 46 m (150 ft) radius rolling sphere — NEC 2023, 810.15.
  • Coaxial cables entering or attached to buildings: the outer conductive shield shall be grounded in accordance with 820.100, as close as practicable to the point of entrance (entering) or point of attachment or termination (terminating outside) — 820.93(A), (B). Where the outer conductive shield is grounded, no other protective devices shall be required — 820.93.
  • **Grounding of a coaxial drop cable shield by means of a protective device that does not interrupt the grounding system…

General Electrical Knowledge

12 on exam · 95 practice questions

Key Concepts

Code arrangement and definitions (Article 90, Article 100) - Chapters 1, 2, 3, and 4 apply generally; Chapters 5, 6, and 7 cover special occupancies, equipment, and conditions. Chapter 8 covers communications systems and is not subject to Chapters 1 through 7 except where specifically referenced in Chapter 8; Chapter 9 consists of tables applicable as referenced (90.3). - Mandatory rules use shall/shall not; permissive rules use shall be permitted/shall not be required (90.5). SI units appear first, inch-pound in parentheses (90.9(B)). - Continuous Load — maximum current expected to continue for 3 hours or more (Article 100). - Identified — recognizable as suitable for the specific purpose, function, use, environment, application where described in a particular Code requirement. Compare Approved (acceptable to the AHJ), Listed, Labeled (Article 100). - Accessible, Readily — reached quickly without tools…

Plan Reading

2 on exam · 12 practice questions

Key Concepts

Definitions drive almost every plan-reading question. Article 100 is the authority.

  • Continuous Load — a load where the maximum current is expected to continue for 3 hours or more. That classification triggers the 125 percent sizing requirements for conductors and overcurrent devices. (NEC 2023, Article 100 — Definition of Continuous Load)
  • Demand Factor — the ratio of the maximum demand of a system, or part of a system, to the total connected load of that system or part. (NEC 2023, Article 100 — Definition of Demand Factor)
  • Multiwire Branch Circuit — two or more ungrounded conductors that have a voltage between them, plus a neutral having equal voltage to each ungrounded conductor. (NEC 2023, Article 100 — Definition of Branch Circuit, Multiwire)
  • Feeder — all circuit conductors between the service equipment, the **source…

Wiring & Protection

17 on exam · 95 practice questions

West Virginia Electrical Contractor | 17 questions (23%)

Key Concepts

Branch circuits (Art. 210). Branch circuits rated 10 amperes shall not supply receptacle outlets [210.18, Exc. No. 2]. OCPD rating ≥ noncontinuous load + 125% of continuous load [210.20(A)]. Ranges rated 8¾ kW or more require a minimum 40-ampere branch circuit [210.19(C)]. At least one 120-volt, 20-ampere branch circuit is required for attached garages and detached garages with electric power, with no other outlets on it [210.11(C)(4)]. AFCI protection is required in dormitory units for outlets in bedrooms, living rooms, hallways, closets, bathrooms and similar rooms [210.12(C)].

Final Practice Exam
75 questions · 180 min · timed simulation of the real exam
Never the same exam twice. Every attempt is drawn fresh from 479 questions, about 6 full exams' worth, and questions you haven't seen come first.

Required Books

Open-book exam
17th Edition
American Electricians' Handbook, 17th Edition
Buy on Amazon
2023 Edition
National Electrical Code 2023
Buy on Amazon
As an Amazon Associate we earn from qualifying purchases.
$59.95/monthCancel anytime. Instant access.