Planning and Estimating
Key Concepts
Rainfall data and drainage factors. Rainfall intensity is given in inches per hour for a five-minute duration or one-hour duration, from U.S. Weather Bureau records (SMACNA Architectural Sheet Metal Manual, 7th ed., Ch. 1, Rainfall Intensity—Downspout Capacity). Table 1-2 lists, per city, Column A storms "exceeded only once in 10 years" and Column B storms "exceeded only once in 100 years," each with a 5-minute intensity and the calculated roof area drained per downspout area. That drainage factor (e.g., 160 ft²/in.²) is roof area drained per in.² of downspout.
Downspout sizing considerations (Ch. 1). Downspouts of less than 7.00 in.² (4515 mm²) cross section should not be used except for small areas such as porches and canopies. Size must be constant throughout its length; conductor heads every 40 ft (12.2 m); offsets of more than 10 ft (3.0 m) can affect capacity; gutter outlet capacity should match downspout capacity.
Gutters (Ch. 1, Gutter Sizing / Rectangular Gutter Design). 50 ft (15 m) is the practical maximum gutter length served by one downspout, and gutter sections should not exceed 50 ft between ends or expansion joints.
Scuppers (Appendix G). Head H is the depth of water at a point 6 ft (1.8 m) back from the scupper opening; codes typically set 1 in. as minimum head. Provide one scupper for each interior roof drain where scuppers are secondary (overflow) drainage.
Expansion allowances. Roof-located expansion joints use curbs not less than 10 in. (254 mm) high (Ch. 5, Building Expansion Joints — General); caps are formed in sections not exceeding 10 ft (3 m) joined by standing seams (Fig. 5-1). Wall expansion lap = calculated building expansion plus 1 in. (25 mm) (Fig. 5-7).
Fabrication
Key Concepts
Beading and crossbreaking (Section 2.1.1(6), Figure 2-10). Not required when liner or external insulation is used, width is less than 19 in., pressure class is over 3 in. wg, duct gage is over 20 gage (1.0 mm), or unbraced panel area is 10 sq ft (0.93 m²) or less. Otherwise one or the other must be used. Neither affects reinforcement spacing.
Reinforcement attachment (S1.40). Intermediate-type reinforcement supplementing a joint must be attached to the duct wall within 3 in. (76 mm) of the joint by weld, bolt, screw or blind rivet, with fastening within 2 in. (51 mm) of duct corners and at intervals not exceeding 12 in. (305 mm).
Fastener projection (S1.41). Fastenings shall not project into duct interiors more than 1/2 in. (13 mm); steel fasteners on steel duct; pull-through mandrel blind rivets that leave leakage holes are prohibited.
Ties (S1.19, S1.21, S1.23, S1.28). Internal ties and connections must sustain 75 percent of the duct construction pressure class load, applied as 5.2 lb/sq ft per inch wg over duct width × reinforcement interval. Tie straps, positive pressure only, are 1 in. x 1/8 in. minimum galvanized steel, smallest edge facing airflow. Up to 120 in. width, ties go at even subdivisions of duct width not exceeding 60 in. (1524 mm). Over 120 in. wide, tie rods at joints plus intermediates at intervals not exceeding 60 in. for 6 in. wg or less; at 10 in. wg the maximum is 48 in. (Figure 2-14).
Midpanel tie rods (Section 2.7.1). Acceptable through 96 in. (2400 mm) width with joint spacing of 6 ft (1.8 m) or less using joints already qualified as reinforcement. Not allowed: unprotected exterior duct, where condensation or grease collects, underground/in-slab/under-slab duct, non-parallel-side fittings, where air velocity exceeds 2500 fpm (12.7 m/s), and near fans where SYSTEM EFFECT FACTORS apply.
Installation
Key Concepts
Gutters, downspouts and drainage - Gutter ends or expansion joints (with at least one downspout between them) must be no more than 50 ft (15.2 m) apart unless specially designed (Ch. 1, Fig. 1-1(e)). - Hanging gutter brackets, cradles and straps: 36 in. (910 mm) maximum centers, with spacers alternately between them (Ch. 1, Hanging Gutter Installations — General). - Built-in gutter front edge must be lower than the back by 1 in. per foot of gutter width, 1 in. (25 mm) absolute minimum (Ch. 1, Fig. 1-1(g), Fig. 1-21). - Soldered gutter laps are riveted on 2 in. (50 mm) centers; where metal cannot be soldered/welded, a 1 in. (25 mm) minimum sealed lap is riveted on 1 in. (25 mm) centers, with sealant over all rivets (Ch. 1, Fig. 1-1(f), Fig. 1-3).
Flashings - Gravel-stop roof flange: 3 3/4 in. (95 mm) minimum, 4 1/4 in. (108 mm) maximum, recessed 1/2 in. (13 mm) behind the nailer edge (Ch. 2, Design Data). - Counter flashing receivers elevated 10 in. (254 mm) above finished roof; counter flashing covers a 4 in. (100 mm) minimum of base flashing (Ch. 4, General). - Reglet cut in existing masonry joint: 1 1/2 in. (38 mm) minimum depth, flashing spring-held, reglet filled with sealant (Ch. 4, Fig. 4-4E). - Ledge flashing on a frame building turns up 6 in. (152 mm) on sheathing; the 4 in. (100 mm) turn-up applies to masonry ledges with step counter flashing (Ch. 4, Fig. 4-16). - Coping dying into a taller wall: end cap integral with/soldered to a flange flashing 4 in. (100 mm) minimum width built into the intersected wall (Ch. 3, Fig. 3-8D). - Rectangular penetration flashing laps over lower / under higher panels: 12 in. (305 mm) minimum with double rows of sealant or butyl tape (Ch. 8, General). - Large curb penetration: back of curb 12 in. (305 mm) minimum height; upper panel hemmed edge 16 in. (406 mm) minimum from the curb **or 6 in. (150 mm) above a level line from top of curb — whichever point is…
Safety
Key Concepts
PPE (GISO Group 2) - Protective equipment must be distinctly marked to identify the manufacturer; exception for employer-manufactured shields, barriers, etc. — §3380(b). - The written hazard-assessment certification must identify the workplace evaluated, the person certifying, the date(s) of the assessment, and identify itself as a certification of hazard assessment — §3380(f)(2). PPE selection is a separate duty under §3380(f)(1)(A). - Hand protection against cuts/lacerations/abrasions is not required where the §3380(f) assessment finds the risk infrequent and superficial — §3384(a) Exception. Gloves may not be worn where entanglement in moving machinery is a danger, except on equipment with a momentary contact device (§3941) — §3384(b). - Footwear purchased after January 26, 2007: ASTM F 2412-05 and F 2413-05 — §3385(c)(1). - Helmet markings: manufacturer, ANSI designated standard number and date, ANSI designated class and impact type — §3381(d). Type I = blow to top only; Type II = top or sides — §3381(c). - Welding filter shade table is a guide; shades more dense than listed may be used — §3382(b). Corrective lenses: only the three arrangements in §3382(c).
IIPP and heat - Training documentation: employee name or other identifier, training dates, type(s) of training, and training providers; kept at least 1 year — §3203(b)(2). - Labor/management committee must meet regularly, not less than quarterly — §3203(c)(1). - Tailgate/toolbox meetings at least every 10 working days — CSO §1509(e). - High-heat procedures apply at 95°F or above (pre-shift meetings, observation, water reminders) — §3395(e). A heat wave is a predicted high of at least 80°F that is at least 10 degrees above the average high of the preceding five days; all employees closely observed — §3395(g)(1).
HazCom / LOTO - Labels revised within 6 months (§5194(f)(11)); SDS updated within 3 months (§5194(g)(5)). In construction, alternative written materials must identify and accompany the containers — §5194(f)(7). - Tagout attachment: non-reusable, attachable by hand, self-locking, minimum unlocking strength no less than 50 pounds — §3314(e). Annual periodic inspection by an authorized employee other than the one using that procedure — §3314(j)(1).