Kansas City, MO Master Gas Pipe Fitter (ICC G33, 2018 IFGC) Exam Study Guide
This guide covers what you need for the Kansas City, MO Master Gas Pipe Fitter (ICC G33, 2018 IFGC) exam: the key facts from the official bulletin, the topics it tests, the reference books, sample questions with answers, and a plan to prepare. Pearson VUE gives the exam.
Kansas City, MO Master Gas Pipe Fitter (ICC G33, 2018 IFGC) Exam at a Glance
Here are the exam's key facts from the official bulletin:
| Questions | 75 questions |
| Time limit | 3 hours |
| Passing score | a minimum score of 70 |
| Books in the exam room | Open book |
| Exam fee | $115 |
On exam day
- Questions are four-option multiple choice with one correct answer.
References you may bring
- International Fuel Gas Code (2018)
Scheduling, changes and retakes
- Exams are scheduled through Pearson VUE at www.pearsonvue.com/ICC.
- Results for electronically administered examinations are available immediately after the exam is completed.
- You must wait 10 days before retaking a failed exam.
- After passing, contact the jurisdiction for any other requirements needed to become licensed.
Source: Kansas City, Missouri Examination Information Bulletin (ICC Contractor/Trades), PUBLISHED November 10, 2025. Check the bulletin before test day: fees and rules can change.
What the Kansas City, MO Master Gas Pipe Fitter (ICC G33, 2018 IFGC) Exam Covers
The official content outline has 6 topics:
| Topic | Questions | Share of the exam |
|---|---|---|
| General Requirements | 37 | 49% |
| Water Heaters | 4 | 5% |
| Appliances and Equipment | 11 | 15% |
| Fuel Supply System Sizing | 4 | 6% |
| Combustion Air | 10 | 13% |
| Chimneys and Vents | 9 | 12% |
How to Prepare for the Kansas City, MO Master Gas Pipe Fitter (ICC G33, 2018 IFGC) Exam
Start with the books. This is an open-book exam, so the references on the bulletin's list are your main study tool. Get the editions the bulletin names.
Learn where things are. Read the table of contents and the index of each book until you know where every major subject lives. On test day, finding an answer fast matters more than memorizing it.
Highlight the sections you use most. Check the bulletin's rules on tabs and markings before you add any.
Spend most of your time on the biggest topics. General Requirements and Appliances and Equipment make up 64% of the exam.
Take timed practice exams. The clock trains you to find answers at the pace the real exam needs: about 2 minutes 24 seconds per question.
Aim to pass more than once. One passing score can be luck. Several in a row means you're ready.
Reference Books for the Kansas City, MO Master Gas Pipe Fitter (ICC G33, 2018 IFGC) Exam
The only reference listed for this open-book exam is the 2018 International Fuel Gas Code.
Where to get them:
On Test Day
- Go through the whole exam first. Answer every question you know and bookmark the ones you don't. Every exam lets you come back to bookmarked questions, but some lock the questions you've seen once you take a break, so work your bookmarks before any break.
- Then go back to your bookmarks and work them out.
- Don't let one question eat your time. You have 3 hours for 75 questions, which is about 2 minutes 24 seconds per question.
- Before you finish, answer anything you skipped. A blank can't earn a point.
Study Tips
On technical questions, don't get bogged down in unfamiliar terminology. If you don't recognize a term, you're unlikely to figure it out on the spot—acknowledge it quickly and move on. Use the surrounding context, answer choices, and familiar terms to guide your reasoning, but don't linger on any single difficult question.
Practicing against a ticking clock is the best way to beat exam-clock anxiety. Use these timed tests to build your pacing, so you learn to move steadily and never burn too long on a single question. By test day, the format feels routine.
If you're stuck on a problem, don't waste time—move on. Before you do, however, quickly eliminate any obviously wrong answer choices. Even ruling out one or two options significantly improves your odds of guessing correctly. Eliminate what you can, make your best guess, then move on.
You're given plenty of time, so use as much of it as you need. Don't get rattled when other people finish early — finishing first isn't a prize. Work at your own steady pace and review your answers before you submit.
Sample Kansas City, MO Master Gas Pipe Fitter (ICC G33, 2018 IFGC) Practice Questions
These questions come from our practice question bank, each with its answer and reference.
Sample 1 — Chimneys and Vents
Question: The remaining space surrounding a chimney liner or gas vent installed within a masonry chimney flue shall NOT be used to supply what?
- A. Combustion air
- B. Return air for a forced-air system
- C. Ventilation air to an adjacent room
- D. Drainage for condensate
Correct Answer: A
Per IFGC Section 503.5.10, the remaining space surrounding a chimney liner, gas vent, special gas vent, or plastic piping installed within a masonry, metal, or factory-built chimney shall not be used to supply combustion air. An exception exists for direct-vent appliances designed for installation in a solid fuel-burning fireplace.
Reference: IFGC 2018 Section 503.5.10
Sample 2 — Water Heaters
Question: The aggregate input rating of all unvented gas appliances installed in a room or space shall not exceed what maximum value per cubic foot of room volume?
- A. 20 Btu/h per cubic foot
- B. 30 Btu/h per cubic foot
- C. 10 Btu/h per cubic foot
- D. 40 Btu/h per cubic foot
Correct Answer: A
Per IFGC Section 621.5, the aggregate input rating of all unvented appliances installed in a room or space shall not exceed 20 Btu/h per cubic foot of volume of such room or space.
Reference: IFGC 2018 Section 621.5
Sample 3 — Fuel Supply System Sizing
Question: Steel tubing used in a fuel gas piping system must comply with which standard?
- A. ASTM A106
- B. ASTM A254
- C. ASTM A53/A53M
- D. ASTM A312
Correct Answer: B
Per IFGC Section 403.5.1, steel tubing shall comply with ASTM A254. Options A, B, and D are standards for steel pipe (not tubing), as listed in Section 403.4.2.
Reference: IFGC 2018 Section 403.5.1
Sample 4 — General Requirements
Question: A residence is piped with corrugated stainless steel tubing that is not listed with an arc-resistant jacket. The required bonding jumper runs from the gas piping system to the electrical service grounding electrode system. What is the maximum permitted length of that bonding jumper?
- A. 25 feet
- B. 100 feet
- C. 75 feet
- D. 50 feet
Correct Answer: C
IFGC 310.2.3 limits the length of the bonding jumper between the connection to the gas piping system and the connection to the grounding electrode system to 75 feet. Any additional grounding electrodes installed to meet this requirement must themselves be bonded to the service (or lightning protection) grounding electrode system.
Reference: IFGC 2018 Section 310.2.3
Why Practice Online Instead of With a PDF
A PDF shows you questions. It doesn't show you the clock. Our practice exams are timed and on a screen, so you practice finding answers under time pressure, not just reading them. Each attempt draws a new set of questions from our bank, and your results break the score down by outline topic so you know what to study next.