Kansas City, MO Master Mechanical (ICC G29, 2018 IMC/IFGC) Practice Exam Guide
What's on the exam
Questions per topic, out of 100This practice exam is built around the official content outline for the Kansas City, MO Master Mechanical (ICC G29, 2018 IMC/IFGC) exam: Administration General Regulations, Appliances & Mechanical Equipment, Exhaust and Ventilation Systems, Duct Systems, Combustion Air, Chimneys and Vents, Fuel Supply Systems.
There are two ways to practice. The free practice exam gives you 10 questions per attempt, and you can take it as many times as you like. The full practice exam gives you 100 questions on a 4 hours clock, with a new draw from our question bank each time.
Administration General Regulations 30 items
Our study plan for this topic: General Installation Requirements; Code Definitions and Terms; Plan Reading; Testing; Permits and Permit Applications; Code Official Authority and Enforcement; Inspections and Inspection Procedures; Violations, Stop Work Orders, and Penalties.
Appliances & Mechanical Equipment 27 items
Our study plan for this topic: Heating Equipment & Gen App Installation; Water Heaters and Boilers; Cooling and Refrigeration Systems; Hydronic and Other Systems; Refrigerant Classification and Safety Groups (ASHRAE 34 toxicity/flammability designations); Machinery Room Requirements (construction, ventilation rates, refrigerant detectors, emergency controls); Refrigerant Piping Materials, Joints, and Installation Restrictions; Maximum Allowable Refrigerant Quantities by Occupancy Type.
Exhaust and Ventilation Systems 11 items
Our study plan for this topic: Exhaust Fan & Product Conveying Systems; Commercial Hoods & Kitchen Ventilation; Clothes Dryer Exhaust Systems; Domestic Cooking Exhaust Equipment; Hazardous Exhaust Systems; Smoke Control Systems; Exhaust Discharge Location & Outlet Termination Requirements; Mechanical Ventilation Rates & Outdoor Air Requirements.
Duct Systems 12 items
Our study plan for this topic: Duct Construction, Installation & Plenums; Smoke and Fire Dampers; Return Air Openings and Restrictions; Duct Insulation, Coverings, and Vapor Retarders; Flexible Ducts and Air Connectors; Duct Joints, Seams, and Sealing Requirements; Smoke Detection Systems Control for Air Distribution; Air Filters in HVAC Systems.
Combustion Air 6 items
Our study plan for this topic: Venting of Fuel Burning Appliances; Indoor combustion air requirements — standard method (50 cubic feet per 1,000 Btu/h); Known air-infiltration-rate method for determining required volume (Equations 3-1 and 3-2); Outdoor combustion air — two-permanent-openings and one-permanent-opening methods with sizing criteria; Combination indoor and outdoor combustion air method; Mechanical combustion air supply systems and appliance interlock requirements; Louvers, grilles, and screens — net free area calculations and motorized louver interlocks; Combustion air duct construction, installation, and termination requirements.
Chimneys and Vents 8 items
Our study plan for this topic: Venting of Fuel Burning Appliances; Chimney and Vent Connectors; Appliance categories and vent system type selection (Table 503.4/802.2); Vent and chimney termination height and location requirements; Sizing of Category I appliance venting systems using code tables; Masonry chimney construction, lining, and flue requirements; Factory-built chimney listing, installation, and clearance requirements; Draft hoods, draft controls, and vent dampers.
Fuel Supply Systems 6 items
Our study plan for this topic: Fuel Supply Installation, Testing and Sizing; Piping materials, fittings, and joint types for gas systems; CSST bonding and electrical continuity requirements; Pressure regulators, shutoff valves, and flow controls; Piping support intervals and protection against physical damage; Prohibited locations and underground installation requirements for gas piping; Purging procedures and leak detection methods; Fuel oil piping materials, joints, valves, and system installation.
Sample 1 — Administration General Regulations
Question: A low-speed ceiling fan that circulates large volumes of air is classified as a high-volume, large-diameter fan when its diameter is greater than what dimension?
- A. 5 feet
- B. 8 feet
- C. 7 feet
- D. 6 feet
Correct Answer: C
IMC 2018 Section 202 defines a high-volume, large-diameter fan as a low-speed ceiling fan that circulates large volumes of air and that is greater than 7 feet (2134 mm) in diameter.
Reference: IMC 2018 Section 202 — High-Volume, Large-Diameter Fan
Sample 2 — Appliances & Mechanical Equipment
Question: What is the minimum clearance to combustible materials required for exhaust ducts serving commercial (Type 2) clothes dryers?
- A. 3 inches
- B. 12 inches
- C. 1 inch
- D. 6 inches
Correct Answer: D
Per IFGC Section 614.9, ducts serving commercial (Type 2) clothes dryers shall have a minimum clearance of 6 inches to combustible materials.
Reference: IFGC 2018 Section 614.9
Sample 3 — Duct Systems
Question: You are specifying PVC duct and fittings for an underground air distribution run beneath a slab. What is the maximum design temperature permitted for a system utilizing plastic duct and fittings?
- A. 250°F
- B. 150°F
- C. 125°F
- D. 120°F
Correct Answer: B
IMC 2018 Section 603.8.3 limits the maximum design temperature for systems using plastic duct and fittings to 150°F. Plastic duct is permitted only in underground installations and must have a minimum pipe stiffness of 8 psi at 5-percent deflection per ASTM D2412.
Reference: IMC 2018 Chapter 6 — Section 603.8.3 Plastic ducts and fittings
Your first score is just a starting point. After every attempt, the results page shows how you did on each outline topic, so you can see what to work on next. Compare your score with the real exam's passing score, a minimum score of 70, and keep at it until you pass consistently.
- Start with the questions you know. Go through the whole exam once and bookmark anything you're unsure about. Our practice exams let you bookmark and come back.
- Circle back to your bookmarks on the second pass.
- Keep an eye on your pace. The real exam works out to about 2 minutes 24 seconds per question.
- Turn every miss into a lesson. After each attempt, look up each missed question's reference in your book and read the section.
| Questions | 100 questions |
| Time limit | 4 hours |
| Passing score | a minimum score of 70 |
| Books in the exam room | Open book |
| Exam fee | $115 |
- Results for electronically administered examinations are available immediately after the exam is completed.
- You must wait 10 days before retaking a failed exam.
Source: Kansas City, Missouri Examination Information Bulletin (ICC Contractor/Trades), PUBLISHED November 10, 2025. Check the bulletin before test day: fees and rules can change.