EN ES
Study Course

Oklahoma Refinery Electrical Journeyman

100 questions 240 minutes 70% to pass 12 topics 2:24 per question Open book
Try 10 free questions Free Cheat Sheet Official Bulletin

Practice at the real exam's pace

Every practice exam shows your time per question against the real exam's clock (2:24 here), and each topic lands in one of these:

Ready Find it faster Study it Needs both Rushing: slow down

What's on the exam

Questions per topic, out of 100
General Electrical Knowledge10
Electrical Installation Requirements4
Services, Feeders, and Branch Circuits6
Overcurrent Protection6
Grounding and Bonding10
Conductors and Cables6
Raceways and Boxes6
Low Voltage, Alarms, Signaling Systems, and Communications4
Lighting and Signs4
Safety5
Motors and Transformers4
Hazardous Locations35

Topics

Open a topic to read its key concepts

General Electrical Knowledge

10 on exam · 62 practice questions

Key Concepts

NEC arrangement and enforcement - Chapters 1, 2, 3, and 4 apply generally; Chapters 5, 6, and 7 apply to special occupancies, special equipment, or other special conditions and may supplement or modify the requirements in Chapters 1 through 7 (NEC 2023, 90.3). - Chapter 8 covers communications systems and is not subject to Chapters 1 through 7 except where specifically referenced in Chapter 8; Chapter 9 consists of tables applicable as referenced; informative annexes are informational only (90.3). - The authority having jurisdiction for enforcement has the responsibility for making interpretations of the rules, deciding on approval of equipment and materials, and granting special permission (90.4(B)). - Mandatory rules are characterized by "shall" or "shall not"…

Electrical Installation Requirements

4 on exam · 17 practice questions

Key Concepts

Branch-circuit ratings (NEC 210.18). "Branch circuits recognized by this article shall be rated in accordance with the maximum permitted ampere rating or setting of the overcurrent device. The rating for other than individual branch circuits shall be 10, 15, 20, 30, 40, and 50 amperes." Exception No. 2: "Branch circuits rated 10 amperes shall not supply receptacle outlets." NEC 210.23(A)(2) likewise bars a 10-ampere branch circuit from supplying receptacle outlets, fixed appliances (except as permitted for individual branch circuits), garage door openers, and laundry equipment.

Services, Feeders, and Branch Circuits

6 on exam · 29 practice questions

Key Concepts

Number and routing of services. A building or other structure served shall be supplied by only one service unless permitted in 230.2(A) through (D) — special conditions (fire pumps, emergency systems, legally required standby, optional standby, interconnected power production, enhanced-reliability systems), special occupancies by special permission, capacity requirements in excess of 2000 amperes at 1000 volts or less, or different characteristics (230.2). Service conductors supplying a building shall not pass through the interior of another building (reference text 230.3; the verified question cites NEC 2023, Section 230.5). Conductors are considered outside a building where installed under not less than 50 mm (2 in.) of concrete beneath it, or in conduit under not less than 450 mm (18…

Overcurrent Protection

6 on exam · 29 practice questions

Key Concepts

  • Scope. Parts I through VII of Article 240 give general requirements for overcurrent protection and OCPDs not more than 1000 volts, nominal; Part VIII covers supervised industrial installations at not more than 1000 volts (240.1). Systems over 1000 volts ac, 1500 volts dc are covered by Article 245 (245.1).
  • Conductor protection. Conductors other than flexible cords, flexible cables, and fixture wires are protected per their ampacities in 310.14 (240.4). Small-conductor limits (240.4(D)): 18 AWG Cu 7 A, 16 AWG Cu 10 A, 14 AWG copper-clad aluminum 10 A, 14 AWG Cu 15 A (240.4(D)(4)), 12 AWG Al/CCA 15 A, 12 AWG Cu 20 A, 10 AWG Al/CCA 25 A, 10 AWG Cu 30 A. -…

Grounding and Bonding

10 on exam · 50 practice questions

Key Concepts

  • Purpose of grounding. Grounded systems shall be connected to earth in a manner that limits voltage imposed by lightning, line surges, or unintentional contact with higher-voltage lines and that stabilizes the voltage to earth during normal operation (250.4(A)(1)). The earth shall not be considered an effective ground-fault current path (250.4(A)(5)).
  • Load-side grounded conductor. A grounded conductor shall not be connected to normally non-current-carrying metal parts, to EGCs, or be reconnected to ground on the load side of the service disconnecting means, except as otherwise permitted in Article 250 (250.24(B)).
  • Ungrounded systems. Ungrounded ac systems operating at not less than 120 V and at 1000 V or less shall have ground detectors installed (250.21(B)), and…

Conductors and Cables

6 on exam · 30 practice questions

Key Concepts

Selecting conductors (Article 310) - Minimum size for general wiring up to and including 2000 volts: 14 AWG copper or 12 AWG aluminum/copper-clad aluminum — 310.3(A). - Copper-clad aluminum: copper shall form a minimum 10 percent of the cross-sectional area of a solid conductor or each strand — 310.3(B). - Where installed in raceways, conductors 8 AWG and larger shall be stranded unless permitted or required elsewhere to be solid — 310.3(C). - Wet-location insulations: MTW, RHW, RHW-2, TW, THW, THW-2, THHW, THWN, THWN-2, XHHW, XHHW-2, XHWN, XHWN-2, ZW — 310.10(C). THHN is dry and damp only [310.10(B)]. - Table 310.4(1) specialty ratings: SIS 90°C, switchboard and switchgear wiring only; MTW 60°C machine tool wiring in wet…

Raceways and Boxes

6 on exam · 29 practice questions

Key Concepts

Box fill (314.16(B)) — The volumes in 314.16(B)(1) through (B)(6) are added together; the box volume calculated per 314.16(A) shall not be less than that total. No allowance is required for small fittings such as locknuts and bushings. - Conductor fill uses Table 314.16(B)(1): 14 AWG = 32.8 cm³ (2.00 in.³), 12 AWG = 36.9 cm³ (2.25 in.³), 10 AWG = 41.0 cm³ (2.50 in.³), 8 AWG = 49.2 cm³ (3.00 in.³), 6 AWG = 81.9 cm³ (5.00 in.³), 16 AWG = 1.75 in.³, 18 AWG = 1.50 in.³. - Clamps, 314.16(B)(2): one or more internal cable clamps = a single allowance based on the largest conductor present in the box. No allowance for a connector whose…

Low Voltage, Alarms, Signaling Systems, and Communications

4 on exam · 18 practice questions

Oklahoma Refinery Electrical Journeyman

Key Concepts

Emergency system circuit wiring (Article 700, Part II) - Fire-protection requirements of 700.10(D)(2) through (D)(4) apply in: assembly occupancies for not less than 1000 persons; buildings above 23 m (75 ft) in height; educational occupancies with more than 300 occupants — 700.10(D)(1). - Feeder-circuit wiring must meet one of the conditions of 700.10(D)(2): in spaces fully protected by an approved automatic fire protection system; protected by a listed electrical circuit protective system with a minimum 2-hour fire rating; a listed fire-resistive cable system with a minimum 2-hour fire rating; protected by a listed fire-rated assembly with a minimum 2-hour rating containing only emergency circuits; or encased in a minimum of 50 mm (2…

Lighting and Signs

4 on exam · 20 practice questions

Key Concepts

Listing & general (Part I). All luminaires, lampholders, and retrofit kits shall be listed — 410.6. Reconditioned luminaires, lampholders, ballasts, LED drivers, lamps, and retrofit kits are not permitted — 410.2.

Locations (Part II). Luminaires in wet locations shall be marked suitable for wet locations; damp-location luminaires shall be marked suitable for wet or damp locations — 410.10(A). No cord/chain/cable-suspended luminaires, lighting track, pendants, or paddle fans with light kits within a zone 900 mm (3 ft) horizontally and 2.5 m (8 ft) vertically from the top of the tub rim or shower threshold — 410.10(D). Combustible material shall not be subjected to temperatures in excess of 90°C (194°F) — 410.11. Lampholders over highly combustible material shall…

Safety

5 on exam · 25 practice questions

Key Concepts

Sanitation and first aid - Where showers are required by a particular standard, one shower for each 10 employees of each sex, or numerical fraction thereof, who must shower during the same shift — §1926.51(f)(4)(ii). - First aid supplies must be easily accessible; kit contents go in a weatherproof container with individual sealed packages for each type of item, checked before being sent out on each job and at least weekly on each job — §1926.50(d)(1)–(2). - If no infirmary, clinic, hospital or physician is reasonably accessible, a person holding a valid first-aid certificate must be available at the worksite — §1926.50(c). Where 911 is unavailable, physician/hospital/ambulance numbers must be conspicuously posted — §1926.50(f)(1). - Housekeeping: scrap…

Motors and Transformers

4 on exam · 20 practice questions

Oklahoma Refinery Electrical Journeyman (4 questions, 4% of exam)

Key Concepts

Determining the current to use. For general motor applications, the values in Table 430.247, 430.248, 430.249 and 430.250 are used instead of nameplate current to determine conductor ampacity, switch current ratings, and branch-circuit short-circuit and ground-fault (SC/GF) protection ratings [430.6(A)(1)]. Nameplate current ratings are used for separate motor overload protection [430.6(A)(2)]. For ac adjustable-voltage, variable-torque drive systems, use the maximum operating current marked on the motor or control nameplate; if it does not appear, use 150 percent of the values in Table 430.249 and Table 430.250 [430.6(C)].

Hazardous Locations

35 on exam · 154 practice questions

Oklahoma Refinery Electrical Journeyman · NEC 2023 · 35 questions (35%)

Key Concepts

Scope and documentation - Article 500 does not cover Zone 0, Zone 1, or Zone 2 locations — those are covered by Article 505 [500.1(B)]. - Areas designated hazardous (classified) or determined to be unclassified shall be documented on an area classification drawing and associated documentation, available to the AHJ [500.4].

Classification - Class I, Div. 1: ignitible concentrations of flammable gases/vapors exist under normal operating conditions [500.5(B)(1)]. - Class I, Div. 2: includes areas where ignitible concentrations are normally prevented by positive mechanical ventilation and might become hazardous through failure or abnormal operation of the ventilating equipment [500.5(B)(2)]. - Class II = combustible dust [500.5(C)];…

Final Practice Exam
100 questions · 240 min · timed simulation of the real exam
Never the same exam twice. Every attempt is drawn fresh from 483 questions, about 4 full exams' worth, and questions you haven't seen come first.

Required Books

Open-book exam
2023 Edition
National Electrical Code 2023
Buy on Amazon
OSHA Standards for the Construction Industry
Buy on Amazon
2020 Edition
Ugly's Electrical References 2020
Buy on Amazon
2005 (1st ed, NEC-2005)
Hazardous Locations
2024 Edition
International Residential Code for One- and Two-Family Dwellings 2024
Buy on Amazon
As an Amazon Associate we earn from qualifying purchases.
$59.95/monthCancel anytime. Instant access.