Tennessee - NASCLA-Accredited Trade Examination For Electrical Contractor
Practice at the real exam's pace
Every practice exam shows your time per question against the real exam's clock (2:42 here), and each topic lands in one of these:
What's on the exam
Questions per topic, out of 100Topics
Project Design & Management
Key Concepts
Scheduling (NASCLA Ch. 8 — Scheduling and Project Management) - Three main scheduling methods: calendar scheduling, bar chart (Gantt) scheduling, and critical path method (CPM). - Both bar chart and calendar scheduling share one main weakness: they do not show the interdependencies of activities — a delay in one task does not show its impact on other tasks (Bar Chart Scheduling section). - Calendar scheduling's primary advantage is linking tasks to specific dates (other projects, material delivery dates, payment schedules, employee vacations and holidays); it works for smaller, less complex projects (Calendar Scheduling section). - CPM graphically illustrates the interdependent relationship of tasks. The critical path is the sequence of tasks that determines project duration; a one-week delay on it delays the project one week. Activities with "zero float" are critical activities. - The superintendent generally oversees all daily operations; the foreman supervises specific areas by trade (carpentry foreman: rough/finish carpentry; masonry…
Safety
Key Concepts
Energized work permits and safe work condition - An energized electrical work permit is required when work is performed within the restricted approach boundary, or when the employee interacts with equipment where conductors are not exposed but an increased likelihood of injury from arc flash exists — NFPA 70E 130.2(A). - Permit elements include the circuit/equipment description, work description, justification for energized work, safe work practices, shock and arc flash risk assessment results, means to restrict unqualified persons, evidence of a job briefing, and energized work approval signature(s) — 130.2(B)(1)–(9). - No permit is needed if a qualified person uses appropriate practices and PPE for testing, troubleshooting, or voltage measuring; thermography/ultrasound/visual inspection, access and egress, or housekeeping where the restricted approach boundary is not crossed — 130.2(C). - On the sample permit, Part I is completed by the requester (circuit/location, work to be done, justification for not de-energizing); Part II items (risk…
Electrical Theory and Principles
Key Concepts
Ohm's Law. Current is directly proportional to voltage (Theory 12.6(A)(1)) and inversely proportional to resistance (Theory 12.6(A)(2)). The formula I = E/R transposes to E = I × R (volts) and R = E/I (ohms) — Theory 12.6(B) and the Ohm's Law Formula Circle, Theory 12.7. Resistance is the opposition to current flow and exists in every component, including the source and the wiring (Theory 12.4(A)).
Utilization voltages. Residential lights and receptacles operate at 120V; ranges, dryers, and air conditioning at 120/240V or 240V (Theory 12.3(A)(1)). In commercial and industrial occupancies the voltage is often 277V for lighting and 480V for motors and air-conditioning units (Theory 12.3(A)(2)).
Meters. Voltmeters connect in parallel with the load (Theory 12.3(B)). Series-connected handheld ammeters are typically limited to a maximum of 10 amperes (Theory 12.5(B)(1)); clamp-on ammeters read into the thousands of amperes without opening the circuit (Theory 12.5(B)(2)). Ohmmeters measure resistance in ohms (Theory 12.4(B)).…
General Code Requirements
Tennessee NASCLA Electrical Contractor Exam — 17 questions (17%)
Key Concepts
Article 90 — Arrangement and Units - Chapters 1, 2, 3, and 4 apply generally. Chapters 5, 6, and 7 apply to special occupancies, special equipment, or other special conditions and may supplement or modify the requirements in Chapters 1 through 7 (90.3). - Chapter 8 covers communications systems and is not subject to Chapters 1 through 7 except where specifically referenced in Chapter 8. Chapter 9 consists of tables applicable as referenced (90.3). - SI units shall appear first, with inch-pound units immediately following in parentheses; conversion from inch-pound to SI is based on hard conversion except as provided in 90.9(C) (90.9(B)). Exception: tables in Informative Annex C are permitted to list trade sizes before SI units.
Wiring and Protection
Key Concepts
Feeders and branch circuits - Feeder conductors: minimum ampacity = noncontinuous load + 125% of the continuous load (215.2(A)(1)). The same 125% rule applies to the feeder overcurrent device rating (215.3). - Branch-circuit OCPD supplying continuous loads: rating not less than 125% of the continuous load (210.20(A)). - Up to three sets of 3-wire feeders, or two sets of 4-wire or 5-wire feeders, may use a common neutral (215.4(A)). - Voltage drop: conductors sized to prevent a drop exceeding 3 percent at the farthest outlet, with total feeder + branch circuit drop not exceeding 5 percent (210.19, Informational Note; 215.2(A)(2), IN No. 2). - Feeders supplying dwelling units, dormitory units, hotel/motel guest rooms and suites, and patient sleeping rooms of nursing/limited-care facilities require a Type 1 or Type 2 SPD with a nominal discharge current rating (In) not less than 10 kA (215.18).
Wiring Methods & Materials
Tennessee NASCLA Electrical Contractor | 16 questions (16%)
Key Concepts
Protection of wiring (300.4) - Bored holes: edge of hole not less than 32 mm (1¼ in.) from the edge of the wood member; where that cannot be maintained, protect with a steel plate or bushing at least 1.6 mm (1/16 in.) thick — 300.4(A)(1). - Notches in wood members: steel plate at least 1.6 mm (1/16 in.) thick — 300.4(A)(2). - Parallel to framing members/furring strips: nearest outside surface not less than 32 mm (1¼ in.) from the nearest edge; otherwise 1.6 mm plate or sleeve. RMC, IMC, rigid nonmetallic conduit and EMT are excepted — 300.4(D). - Under metal-corrugated sheet roof decking: not less than 38 mm (1½ in.) from the lowest surface of the decking to the top of the cable, raceway, or box; RMC and IMC with listed steel or malleable iron fittings excepted — 300.4(E). - 4 AWG or…
General Equipment Use
Tennessee NASCLA Electrical Contractor Exam · 13 questions (13%)
Key Concepts
Motor circuit conductors (Art. 430, Part II) - Conductors supplying a single continuous-duty motor: not less than 125% of the motor full-load current per 430.6(A)(1) — 430.22. - Rectifier-supplied dc motors — conductors between rectifier output terminals and motor: 190% (single-phase, half-wave) or 150% (single-phase, full-wave) of motor FLC — 430.22(A). - Wye-start, delta-run: line-side conductors 125%; conductors between controller and motor not less than 72% of FLC (58% × 1.25) — 430.22(C). Part-winding uses 62.5% (50% × 1.25) — 430.22(D). - Intermittent duty, 30- and 60-minute rated motor: 90% of nameplate current — Table 430.22(E). - 18 AWG copper permitted for a motor with FLC greater than 3.5 A and ≤ 5 A when given maximum Class 10 or Class 10A overload protection — 430.22(G)(1). - Several motors: 125% of the highest rated motor's FLC + 100% of all other motors' FLC,…
Special Occupancies, Special Equipment, and Special Conditions
Key Concepts
Hazardous (classified) location basics - Class I, Division 1 = ignitible concentrations of flammable gases/vapors can exist under normal operating conditions (500.5(B)(1)). - Group D = MESG greater than 0.75 mm or MIC ratio greater than 0.80 (500.6(A)(4)). - Area classification must be documented on an area classification drawing available to the AHJ (500.4).
Seals (Article 501.15) - Conduit seals entering an explosionproof enclosure: within 450 mm (18 in.) of the enclosure or as required by the enclosure marking; only threaded couplings or explosionproof fittings (unions, reducers, elbows, capped elbows) between seal and enclosure (501.15(A)(1)). - Two explosionproof enclosures joined by a nipple/run not more than 900 mm (36 in.): one seal, located not more than 450 mm (18 in.) from either enclosure (501.15(A)(3)). - Division 1 and Division 2 boundary seals may be on either side, within 3.05 m (10 ft) of the boundary (501.15(A)(4), (B)(2)). - Sealing compound thickness ≥…
Communication Systems
Tennessee NASCLA Electrical Contractor Exam · NEC 2023, Chapter 8 (Articles 800, 805, 810, 820, 830, 840)
Key Concepts
Primary protection (805.90(A)) — A listed primary protector is required on each circuit run partly or entirely in aerial wire or aerial cable not confined within a block. A listed primary protector is also required on each circuit, aerial or underground, located within the block containing the building served so as to be exposed to accidental contact with electric light or power conductors operating at over 300 volts to ground. Where lightning exposure exists, each interbuilding circuit must be protected at each end. Primary protectors must be located in, on, or immediately adjacent to the structure served and as close as practicable to the point of entrance (805.90(B)), and must not be in hazardous (classified) locations or near easily ignitible material (805.90(C)). Article 840 systems: "the requirements of 805.90 shall apply" (840.90).